These meters are designed for use with TSP or HSP transmitters. The meter can be used for either local or remote indication of the sensed variable. All meters of the ASP-500 series are zero suppressed - taut band - 100° flat arc movement type with a sensitivity of 5000 ohm/volt. The meters are high accuracy 2% meters with ...

8000 Series Devices AT-8100 Series Remote Setpoint Adjuster ASP-500 Series Indicating Meter AD-8301 Positioner General Instructions AT-8100 Series Remote Setpoint Adjuster

ASP-500 Series Indicating Meter

These setpoint adjustors are to be used when the setpoint is to be remote from either the TP-8101 or CP-8102. Calibration is not normally required when used. Scale plate 1-7/8" by 2-1/16". Allow 1-1/2" depth behind mounting surface. 3/8" hole required. These meters are designed for use with TSP or HSP transmitters. The meter can be used for either local or remote indication of the sensed variable. All meters of the ASP-500 series are zero suppressed - taut band - 100° flat arc movement type with a sensitivity of 5000 ohm/volt. The meters are high accuracy 2% meters with a 1-1/2% repeatability and symmetry. All meters are 1 to 11 Vdc movements. These meters are ruggedized plastic with a black cover and clear face for easy viewing of the 2-1/2" scale length. Calibration is not normally a field adjustment. If the meter is out of calibration it should be replaced. Part No.

Meter Face Dimensions

ASP-521 ASP-522 ASP-561

3-1/4" Wide, 2-3/4" High

ASP-562 ASP-563

2-1/2" Scale

ASP-581

Scale Range* °C

°F

10 to 38

50 to 100

-1 to 26

30 to 80

-40 to 71

-40 to 160

-17 to 93

0 to 200

4 to 116

40 to 240

20 to 80% RH

*Scales dual marked in °C and °F.

Printed in U.S.A. 8/08

© Copyright 2008 TAC All Rights Reserved.

F-25795-2

AD-8301 Positioner

For either manual or minimum positioning control of 8000 Series controlled devices. Applied in 8000 system between controllers and controlled devices. Scale plate 1-7/8" by 2-1/16". Allow 1-1/2" depth behind mounting surface. 3/8" hole required. Application

Operation

Manual Control (Knob Pulled Out)

A 6 to 9 Vdc swing between min. and max. markings. CCW to CW rotation produced 1 to 15 Vdc. Calibration by positioning knob to scale.

Minimum Positioner (Knob Pushed In)

A 6 to 9 Vdc min. position level adjustable between min. to max. markings. CCW to CW rotation produces 1 to 15 Vdc. Calibration by positioning knob to scale.

Copyright 2008, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-25795-2

TAC 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL 61132-2940

www.tac.com

Requirements

Recommend Documents
These meters are designed for use with TSP or HSP transmitters. The meter can be used for either local or remote indication of the sensed variable. All meters of the ASP-500 series are zero suppressed - taut band - 100° flat arc movement type with a

8000 SERIES. MANY DAILY ON/OFF. OPERATIONS PER DAY. DUTY CYCLE. 24 HOUR TIME SWITCH. Duty cycling. Ventilating fans. Pumping. Irrigation. Process control. Laboratory experiments. For one or multiple daily. ON/OFF operations . SCHEDULING: Minimum ON s

Wood. Electrical. • .24 Amps at. 12 VDC/VAC. • .12 Amps at. 24 VDC/VAC .... For use with: Extended lip for 'knock-down' style frame installations. For use with ...

Camden Door Controls offers the widest range of high quality, feature rich and affordable pneumatic 'Request to Exit' switches in the industry. All switches ...

OPTIONAL RESERVE POWER: “L” models keep dial on time up to 16 hours during power outage . INPUT VOLTAGE: 120, 208-277VAC or. 480VAC, 60Hz ...

No cutting on frame required. Vertical adjustability to ... Strike body width decreased to 1-7/16" to increase frame compatibility. Five year limited warranty.

The devices are Underwriters. Laboratory (UL, USA and ULC, Canada) listed for Panic Exit Hardware or Fire Exit Hardware, and are certified to ANSI.

Ø M1. H5. L4. M3. Ø D1. SERIES 8000, 8400. SERIES 8200. Model. ØD1. ØD2. ØD3. ØD4. H1. H2. H3. H4. H5. H6. L1. L2. 8015. 8016. [1.25]. 31,8. [0.44]. 11,1.

8000-AAB Series. The PumPac 8000 Series is used in centrifugal pumps, .... Reversing thrust on bearing B (15˚). P = YFA. P = Dynamic equivalent radial load.