Quick Setup Guide 1. 2. 3. 4. - SupplyHouse.com

Report 5 Downloads 18 Views
Q 401

Quick Setup Guide tekmarNet®2 House Control 401

09/10 HVAC Systems Replaces: 06/09

1. Location

2. Install Junction Box

401

401

OR

3. Install Sensors

4. Line Voltage Wiring Back of House Control 401

Outdoor Sensors

(black)

DHW

(black) 401

Zone 4

Zone 3

Zone 4 Sensor with rear entry wiring

Sensor with bottom entry wiring

(black)

Zone 3

(black)

Zone 2

Zone 2

Sensor mounted onto 2" x 4" electrical box

DHW Pump

Zone 1 (black)

Pipe Sensors

Pump Power

Retaining Clip Universal Sensor 082

Strip wires 1/2 inch (13 mm). Installed wires are not removable. 12-18 AWG

(red)

Zone 1

L N

to pump grounds

G L N 115 V (ac) Sensor Well

1 of 4

© 2010

Q 401 - 09/10

5. Install Enclosure

6. Low Voltage Wiring tekmarNet ®2 Thermostats

Stage 2 Mod dc/mA Boil Exp. + tN4 C

+

DHW Call H8006B

House Control 401



Item

tN4

Menu

C

Setpoint Call

Setpoint Call

Sensors - No Power

DHW Tank Sensor 082

Made in Canada tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Zone 1 Zone 2 Zone 3 Zone 4

Stage 1

Boiler Supply Sensor 082

Com Boil Out Com DHW

Outdoor Sensor 070

tekmarNet ®4 Expansion to Wiring Centers, Timers, or User Switch tN4 Boil Expansion Modulating Boiler

2 1

Input Power Use at least 167°F

C

R (75°C) conductors

One or Two Stage Boiler T-T DHW Call from DHW Tank Aquastat (optional)

R C

Back of House Control 401

7. Install Cover

Menu

Item

House Co ntr

ol 402

© 2010

Q 401 - 09/10

2 of 4

L N

24 V (ac) Transformer 009

8. User Interface Display Menu Field

Item Field

Displays the current menu

Displays the name of the selected item

Status Fields Displays the current status of the control’s inputs, outputs and operation. Most symbols in the status field are only visible when the VIEW Menu is selected

VIEW ADJUST MONITOR MINMAX Calls Boil Exp

minhr sec PMAM WWSD Saving

Pumps

Zones 1234

DHW Setp DHW

Number Field Displays the current value of the selected item

12

Symbols

Calls

CALLS Displays any call for heat the control is receiving.

WWSD

Pumps

PUMPS Displays any pump currently operating.

°F°C minhr sec%

Zones 1234

Saving

WWSD Displays when the system is in Warm Weather Shut Down. °F, °C, %, HOURS, MINUTES, SECOND Units of measurement for current number.

ZONES Displays if an on-board zone is operating.

UNOCCUPIED Indicates that a User Switch or Timer has put the system into UnOccupied.

WARNING Displays if an error exists on the system.

BOILER Indicates that the boiler should be heating.

ENERGY SAVING INDICATOR Displays when the system is saving energy. See the Saving Indicator section.

MIN / MAX Displays when an operating temperature reaches a minimum or maximum value.

MINMAX

9. Access Level Press menu button until the Toolbox Menu item button to locate the access level setting.

is displayed. Press

ACCESS LEVEL INST (Installer) or USER Default = INST

Selects the Access Level of the control, which determines the Menu items available. USER provides the most limited level of access and shows the fewest possible items. When set to USER, all thermostats are locked and the number of thermostat settings available are reduced. 3 of 4

© 2010

Q 401 - 09/10

10. Critical Settings

Press menu button until the Adjust Menu is displayed. Press item button to locate the desired setting.

Item Field ADJUST

Range -60 to 45°F (-51.0 to 7.0°C) Default = 10°F (-12.0°C)

EMS2, EMS1, 4-20 0-10, 2STG, 1STG Default = 1STG

Access

Description

Installer

OUTDOOR DESIGN Typically set to the temperature of the coldest day of the year. The outdoor air temperature used in the boiler heating curve is used to determine the boiler target temperature.

Installer

BOILER TYPE The type of boiler connected to the control. 1STG = single one-stage on-off boiler 2STG = single two-stage on-off boiler 0-10 = 0-10 V (dc) modulating boiler 4-20 = 4-20 mA modulating boiler EMS1 = tekmar boiler staging controls EMS2 = Viessmann modulating boilers with OpenTherm

Installer

BOILER DESIGN The supply water temperature required for the boiler zones to heat the building on the typical coldest day of the year. Recommendations: High mass radiant floor = 120°F (50°C) Low mass radiant floor = 140°F (60°C) Fancoil or air handling unit = 190°F (90°C) Copper fin-tube convector = 180°F (80°C) Radiators = 160°F (70°C) Low profile baseboard = 150°F (65°C)

VIEW

70 to 200°F (21.0 to 93.5°C) Default = 180°F (82.0°C)

Set to

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2010 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

4 of 4

All specifications are subject to change without notice. Printed in Canada. Q 401 - 09/10.