submittal data

Report 27 Downloads 190 Views
 

 

 

SUBMITTAL DATA For: Approval   Order #:

Date:

Project:

55th Lyndale

Project #:

SPMN-011816-01

01/05/2016

Location:  

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

  Date 01/05/2016

Project Name 55th Lyndale

Project Number  

SPMN-011816-01

Client / Purchaser    

Submittal Summary Page   Qty

Tag #

Model #

Description

2

RTUs 1,3

ZF060S10B2FZZ40001

5 Ton, York Sunline Single Packaged R-410A Air Conditioner, 13.0 SEER / 10.8 EER, Single Stage Cooling, 100 MBH Output Stainless Steel, Single Stage Gas Heat • 1 HP Direct Drive Blower • Dry Bulb Economizer and Hood (No Barometric Relief Damper) • 208/230-3-60 • Return Air Smoke Detector • Microchannel Condenser Coil • 2" Pleated Filters (MERV 7) • Hinged & Tool Free Filter, Motor and Elec'l Access Panels • Simplicity® SE Controller with Discharge Air, Return Air, and Outside Air Sensor • Phase Monitor • Galvanized Steel Drain Pan

2

RTUs 1,3

1HG0401

Hail Guard Kit

2

RTUs 1,3

1RC0434

Roof Curb - 14" High, Flat, Uninsulated, Full Perimeter (Shipped Knocked Down)

2PE04703725

Power Exhaust Kit for 06 and 25 Voltages

2 1

RTU-2

ZF090S18D2D1HAD2A1

7.5 Ton, Single Packaged R-410A Air Conditioner, Standard Efficiency, 11.2 EER, Two Stage Cooling, 180 MBH Input Stainless Steel, Two Stage Gas Heat, 208/230-3-60, Standard Evaporator Coil, Standard Cabinet with Composite Drain Pan • 3 HP High Static Belt Drive Blower • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Hoods (Bottom or Horizontal End Return Only) with Economizer Fault Detection & Diagnostic • Return Air Smoke Detector (Bottom return only) • 2" Pleated Filters (MERV 8) • Microchannel Condenser Coil • Phase Monitor • Simplicity® SE Controller with Discharge Air, Return Air, and Outside Air Sensor • Hot Gas Bypass

1

RTU-2

1HG0415

Hail Guard Kit

1

RTU-2

1RC0471

Roof Curb - 14" High, Flat, Uninsulated, Full Perimeter (Shipped Knocked Down)

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

  Qty

Tag #

3

Model #

Description

S1-TH8320U1008

THERMOSTAT-TOUCH PROG 3H/2C (M12)

   

Equipment start-up and commissioning by a factory trained technician is recommended. Contact your supplying distributor or sales representative for additional information & guidance. Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

  Page: 4

Small Sunline Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:  ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2)

No Performance Data Available . . . . . .

Run Performance to view metrics . . . . . .

 

5 Ton • York Units are Manufactured at an ISO 9001 Registered Facility and Each Rooftop is Completely Computer-Run Tested Prior to Shipment.

Unit Features • Unit Cabinet Constructed of Powder Painted Steel, Certified At 1000 Hours Salt Spray Test (ASTM B-117 Standards)

• Through-the-Curb and Through-The-Base Utility Connections • Either Supply and/or Return can be Field Converted from Vertical to

 

• • • • • • • • • •

Horizontal Configuration without Cutting Panels. Full Perimeter Base Rails with Built in Rigging Capabilities Hinged & Tool Free Filter, Motor and Electrical Access Panels Galvanized Steel Drain Pan Single Stage Cooling Solid Core Liquid Line Filter Driers Microchannel Condenser Coil 100 MBH Output Stainless Steel, Single Stage Gas Nominal Heat 1 HP Direct Drive Blower 2" Pleated Filters (MERV 7) Replacement Filters: 2 - (15" x 20" x 1" or 2") and 1 - (14" x 25" x 1" or 2"). Unit accepts 1" or 2" wide filters. Single Point Power Connection Phase Monitor Return Air Smoke Detector Dry Bulb Economizer and Hood (No Barometric Relief Damper) Short Circuit Current: 5kA RMS Symmetrical

• • • • • Standard Unit Controller: Simplicity Control Board • An Integrated Low-Ambient Control, Anti-Short Cycle Protection, Lead-Lag,



Fan On and Fan off Delays, Low Voltage Protection, On-Board Diagnostic and Fault Code Display. Allows all units to operate in the cooling mode down to 0 °F outdoor ambient without additional components or intervention. Safety Monitoring - Monitors the High and Low-Pressure Switches, the Freezestats, the Gas Valve, if Applicable, and the Temperature Limit Switch on Gas and Electric Heat Units. The Unit Control Board will Alarm on Ignition Failures, Safety Lockouts and Repeated Limit Switch Trips.

BAS Controller • Simplicity SE Controller with Discharge Air, Return Air, and Outside Air Sensor

Warranty • One (1) Year Limited Warranty on the Complete Unit • Five (5) Year Warranty - Compressors and Electric Heater Elements • Fifteen (15) Year Warranty - Stainless Steel Tubular Heat Exchangers

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

Page: 5

Small Sunline Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:  ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2)

 

Factory Installed Options

ZF060S10B2FZZ40001  

Product Category:

| Z

 

Product Identifier:

F

   

  York Sunline Single Packaged R-410A Air Conditioner  

 

  13.0 SEER / 10.8 EER  

 

Nominal Cooling Capacity:

060  

Heat Type and Nominal Heat Capacity:

S10  

5 Ton 

 

Single Stage Cooling   100 MBH Output Stainless Steel, Single Stage Gas Heat   1 HP Direct Drive Blower 

  Airflow:

B

 

   

Dry Bulb Economizer and Hood (No Barometric Relief Damper)  2" Pleated Filters (MERV 7)  

 

Voltage:

2

  208/230-3-60  

 

 

Installation Options:

F

  Return Air Smoke Detector  

 

Microchannel Condenser Coil 

 

 

Hinged & Tool Free Filter, Motor and Elec'l Access Panels 

 

Additional Options:

ZZ

Product Generation:

4

  Simplicity® SE Controller with Discharge Air, Return Air, and Outside Air Sensor  Phase Monitor  Galvanized Steel Drain Pan       

 

  Field Installed Accessories  1HG0401 - Hail Guard Kit (51.0 lbs)  1RC0434 - Roof Curb - 14" High, Flat, Uninsulated, Full Perimeter (Shipped Knocked Down) (86.0 lbs)  2PE04703725 - Power Exhaust Kit for 06 and 25 Voltages (65.0 lbs)

     

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

Page: 6

Small Sunline Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2) Consolidated Drawing

NOTES: 1. FOR OUTDOOR USE ONLY. 2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. 3. MIN. CLEARANCES TO BE: RIGHT SIDE: 24 [609,6] LEFT SIDE: 24 [609,6] (LESS ECONOMIZER) 36 [914,4] (WITH ECONOMIZER) FRONT: 24 [609,6] (COOLING/ELECTRIC HEAT) 32 [812,8] (GAS HEAT) REAR: 12 [304,8] (LESS ECONOMIZER) 36 [914,4] (WITH ECONOMIZER OR FIXED AIR/MOTORIZED DAMPER) TOP: 72 [1828,8] BOTTOM: 0 [0] 4. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. 5. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 6. SIDE DUCT FLANGES ARE 0.875" [22,2] HIGH. BOTTOM DUCTS DO NOT HAVE FLANGES. 7. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES THE LOWEST NEGATIVE STATIC. 8. DIMENSIONS IN [ ] ARE IN MILLIMETERS OR KILOGRAMS. 9. OPTIONAL COIL GUARD, GAS HEAT, ECONOMIZER HOOD, DISCONNECT SWITCH, CONVENIENCE OUTLET, AND OUTLET/INLET HOOD SHOWN. 10 EXCEPT XN & XP (HEAT PUMP) UNITS.

31.62 [803,3] 7.25 [184,0]

18.26 [463,7]

1.80 [45,8]

27.54 [699,6] REAR

5.51 [140,0]

5.89 [149,6] A

POWER WIRING BOTTOM ENTRY ɸ 2.00 [50,8] 4.00 [101,6] 8.23 [209,2]

CONTROL WIRING BOTTOM ENTRY ɸ 0.88 [22,2] ɸ 1.97 K.O. [50,0] DISCONNECT SWITCH COVER (OPTIONAL)

ECONOMIZER HOOD (OPTIONAL) FILTER ACCESS 27.35 [694,7]

CONVENIENCE OUTLET COVER (OPTIONAL) ɸ 0.88 K.O. [22,2]

18.58 [471,9]

3.78 [96,0] 0.75 [19,1] 19.67 PVC FPT [499,7] COND. DRAIN LEFT VIEW

Unitary Sales Tool v1.5.9.0  

BLOWER ACCESS

4.42 [112,3] 2.55 [64,7]

CENTER OF GRAVITY LOCATION (BASE UNIT) X Y 34.5 [876,3] 18.25 [463,6] 36 [914,4] 18.50 [469,9] 37.5 [952,5] 18.2 [462,3] 33 [838,2] 18.25 [463,6] 31.50 [800,1] 18.50 [469,9] 37 [939,8] 15 [381] 37 [939,8] 15 [381] 40 [1016] 20 [508] 40 [1016] 20 [508] 40 [1016] 20 [508] 38.3 [972,8] 18.75 [476,3] 38.2 [970,3] 18.4 [467,4] 38.6 [980,4] 18 [457,2] 39 [990,6] 20 [508] 39 [990,6] 20 [508] 39 [990,6] 20 [508]

12.26 [311,3]

S U P P L Y

11.50 [292,1] 17.50 [444,5]

111 139 139 114 138 105 118 132 134 135 136 135 132 135 137 138

A [50] [63] [63] [52] [63] [48] [54] [60] [61] [61] [62] [61] [60] [61] [62] [63]

ECONO / O/A

RIGHT SUPPLY

Y D

4 POINT CORNER LOADS (LBS) (BASE UNIT) B 80 [36] 108 [49] 117 [53] 76 [35] 85 [39] 86 [39] 96 [44] 125 [57] 127 [58] 128 [58] 119 [54] 117 [53] 117 [53] 121 [55] 124 [56] 125 [57]

117 154 171 111 122 170 192 155 158 159 165 169 174 151 154 155

C D [53] 162 [73] [70] 198 [90] [78] 204 [93] [50] 167 [76] [55] 196 [89] [77] 208 [94] [87] 234 [106] [70] 164 [74] [72] 167 [76] [72] 168 [76] [75] 190 [86] [77] 195 [88] [79] 197 [89] [69] 168 [76] [70] 171 [78] [70] 172 [78]

B R E T U R N

DIRECTION OF AIRFLOW CENTER OF GRAVITY

6.12 [155,5]

OPERATING WEIGHT (LBS) (BASE UNIT) 470 [213] 598 [271] 632 [287] 468 [212] 541 [245] 569 [258] 640 [290] 575 [261] 585 [265] 590 [268] 610 [277] 616 [279] 620 [281] 575 [261] 585 [265] 590 [268]

U N TONNAGE I T 3 ZE ZE 4 5 ZE 3 ZF ZF 4 ZF 5 ZF 6 ZR 3 ZR 4 5 ZR XN 3 4 XN XN 5 XP 3 XP 4 5 XP

C 6.48 [164,7] GAS SUPPLY BOTTOM ENTRY ɸ 1.50 [38,1] K.O. (0.50 [12,7] NPT AT GAS VALVE VENT AIR OUTLET HOOD 10 COMBUSTION AIR INLET HOOD

11.06 [281,0] 32.09 [815,2] X

CTL BOX ACCESS

BLOWER ACCESS

4.38 [111,1] 31.89 [810,0]

GAS HEAT ACCESS

82.19 [2087,6]

COMP. ACCESS

6.94 [176,2] GAS SUPPLY ENTRY ɸ 1.63 [41,4] 10

RETURN / O/A

3.00 11.50 [76,2] [292,1] 11.50 19.08 [292,1] [484,6]

6.50 [165,1]

4.58 [116,3] 17.50 7.62 [444,5] [193,6] 17.50 31.62 [444,5] [803,2] REAR (PARTIAL VIEW) (RAIN HOOD NOT SHOWN IN THIS VIEW)

32.55 [826,7]

44.88 [1139,8] RIGHT VIEW

COIL GUARD (OPTIONAL)

FRONT VIEW

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Small Sunline

Page: 7

Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2) Typical Application

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Small Sunline

Page: 8

Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2) Typical Field Power and Control Wiring

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

  Page: 9

Small Sunline Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2) Seismic Certification

SPECIAL SEISMIC CERTIFICATION OF NON STRUCTURAL COMPONENTS AND SYSTEMS

CERTIFICATE OF COMPLIANCE Dynamic Cer�fica�on Laboratories has qualified the listed packaged roo�op units as CERTIFIED for seismic applica�ons in accordance with the following codes and standards:

CBC 2010, IBC 2009, ICC ES AC 156 2010, ASCE 7 05 The following model designa�ons are included in this cer�fica�on. A complete list of cer�fied models, op�ons, and installa�on methods are detailed in report number 90300 1108a by Dynamic Cer�fica�on Laboratories, provided by the equipment manufacturer upon request.

Unitary Product Group Packaged Roo�op Units (UPG) Seismic Qualifica�on Tes�ng was conducted in accordance with and in strict adherence to the standards set forth within the American Society of Civil Engineers (ASCE 7) by the independent approval agency, Dynamic Cer�fica�on Laboratories. The above referenced equipment is APPROVED for seismic applica�ons when properly installed and used as intended. The basis of this certifica�on is through tes�ng of the ac�ve and energized components per AC156. This cer�fica�on covers mul�ple UPG brands, including York, Johnson Controls, Coleman, Luxaire, Evcon and Fraser Johnston. The seismic values are obtained from the Maximum Considered Earthquake Short Period Spectral Response Accelera�on, Sds, as determined by the ASCE 7 seismic maps. Various installa�on loca�ons/isola�on configura�ons are covered under this cer�fica�on, limited by the Sds value stated in the following table. A seismic importance factor, Ip, of 1.5 applies to this cer�fica�on to include essen�al facility requirements and life safety applica�ons for post event func�onality. The units are approved for both a rigid and flexible mount configura�on. Maximum Design Sds Values of UPG Packaged Roo�op Units Series Model Tons Sds (g) XP/XA/J0*XP/T0* 036, 048, 060 3, 4, 5 2.5 ZF/ZS/J0*ZF /T0* 036, 048, 060, 072 3, 4, 5, 6 2.5 ZR/ZK/J0*ZR/T0* 036, 048, 060 3, 4, 5 2.5

Fp/Wp 1.88 1.88 1.88

Page 1 of 2 Dynamic Cer�fica�on Laboratories

Unitary Sales Tool v1.5.9.0  

1315 Greg Street, Suite 109, Sparks, NV 89431 – ph: 775 358 5085

Information is subject to change without notice. Check local codes.

www.shaketest.com

Printed 03/21/2016

 

  Page: 10

Small Sunline Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2) Seismic Certification

SPECIAL SEISMIC CERTIFICATION OF NON STRUCTURAL COMPONENTS AND SYSTEMS

CERTIFICATE OF COMPLIANCE

Table of Seismic Design Parameters Fa Ip ap 1.0 1.5 2.5

Site Class D

Rp 6.0

z/h 1.0

Site and Project Requirements It is the responsibility of the Design Professional of Record to: Provide engineering for the anchorage and restraint of the unit Validate Cer�fica�on Design Parameters with actual site condi�ons Provide engineering of all equipment support structures Confirm component configura�on Cer�fica�on Issued by: Dynamic Cer�fica�on Laboratories Document Control Number: 90300 1108a 1 Issue Date: 12/19/11

Dr. Ahmad Itani, SE Dynamic Cer�fica�on Laboratories

Randy Forristall YORK Unitary Engineering Johnson Controls, Incorporated

Page 2 of 2 Dynamic Cer�fica�on Laboratories

Unitary Sales Tool v1.5.9.0  

1315 Greg Street, Suite 109, Sparks, NV 89431 – ph: 775 358 5085

Information is subject to change without notice. Check local codes.

www.shaketest.com

Printed 03/21/2016

 

 

Small Sunline

Page: 11

Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF060S10B2FZZ40001

Quantity:   2  Tag #: RTUs 1,3

System:    ZF060S10B2FZZ40001 (2) 1RC0434 Roof Curb

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

  Page: 12

Predator York Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:  ZF090S18D2D1HAD2A1

Quantity:   1  Tag #: RTU-2

System:    ZF090S18D2D1HAD2A1

No Performance Data Available . . . . . .

Run Performance to view metrics . . . . . .

 

7.5 Ton • York Predator units are manufactured at an ISO 9001 registered facility and each rooftop is completely computer-run tested prior to shipment.

Unit Features • Unit Cabinet Constructed of Powder Painted Steel, Certified At 1000 Hours Salt Spray Test (ASTM B-117 Standards)

• Through-the-Curb and Through-the-Base Utility Connections • Supply can be field converted from vertical to horizontal configuration without

 

• • • • • • • • • • • • • • • •

cutting panels Full perimeter base rails with built in rigging capabilities Hinged Access Panels Standard Cabinet with Composite Drain Pan Reciprocating Compressor Two Stage Cooling Solid Core Liquid Line Filter Driers Microchannel Condenser Coil Standard Evaporator Coil Hot Gas Bypass 180 MBH Input Stainless Steel, Two Stage Gas Heat 3 HP High Static Belt Drive Blower Unit Ships with 2" Pleated Filters (MERV 8) with a Standard Filter Rack that will Accept up to 4" Filters Replacement Filters: 4 - (24" x 16"). Unit accepts 2" or 4" wide filters. Single Point Power Connection Return Air Smoke Detector Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Hoods (Bottom or Horizontal End Return Only) with Economizer Fault Detection & Diagnostic Short Circuit Current: 5kA RMS Symmetrical

• Standard Unit Controller: Simplicity Control Board • Safety Monitoring - Monitors the high and low-pressure switches, the

freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, safety lockouts and re

BAS Controller • Simplicity SE Controller with Discharge Air, Return Air, and Outside Air Sensor

Warranty • One (1) Year Limited Warranty on the Complete Unit • Five (5) Year Warranty - Compressors • Fifteen (15) Year Warranty on Stainless Steel Heat Exchanger

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

Page: 13

Predator York Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:  ZF090S18D2D1HAD2A1

Quantity:   1  Tag #: RTU-2

System:    ZF090S18D2D1HAD2A1

 

Factory Installed Options

ZF090S18D2D1HAD2A1 |  

Single Packaged R-410A Air Conditioner, Standard Product Category:

 

Nominal Cooling Capacity:

ZF

 

  Efficiency  11.2 EER  

090  

7.5 Ton 

 

Two Stage Cooling  

 

Heat Type and Nominal Heat Capacity:

 

Airflow:

D

  3 HP High Static Belt Drive Blower  

 

 

Voltage:

2

  208/230-3-60  

 

S18   180 MBH Input Stainless Steel, Two Stage Gas Heat  

 

Dry Bulb Low Leak Economizer w/Barometric Relief and Economizer / Damper:

D

 

 

 

Power Exhaust and Hoods (Bottom or Horizontal End Return Only) with Economizer Fault Detection & Diagnostic  

   

1

    

Sensor Options:

H

 

Controls:

A

    Simplicity® SE Controller with Discharge Air, Return Air, and Outside Air Sensor  

Refrigeration:

D

 

Additional Options:

2

  Phase Monitor 

 

 

 

Service Options:

Return Air Smoke Detector (Bottom return only) 

Microchannel Condenser Coil 

 

 

Standard Evaporator Coil   2" Pleated Filters (MERV 8) 

 

 

  

 

Hot Gas Bypass  

 

Cabinet Options:

A

  Standard Cabinet with Composite Drain Pan  

 

 

Product Generation:

1

    

 

  Field Installed Accessories  1HG0415 - Hail Guard Kit (50.0 lbs)  1RC0471 - Roof Curb - 14" High, Flat, Uninsulated, Full Perimeter (Shipped Knocked Down) (135.0 lbs)

     

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

Page: 14

Predator York Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF090S18D2D1HAD2A1

Quantity:   1  Tag #: RTU-2

System:    ZF090S18D2D1HAD2A1 Consolidated Drawing

NOTES: 1. FOR OUTDOOR USE ONLY. 2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. 3. MIN. CLEARANCES TO BE: RIGHT SIDE: 12 [305] LEFT SIDE: 36 [915] FRONT: 36 [915] REAR: 36 [915] TOP: 72 [1830] BOTTOM: 0 [0] 4. TO REMOVE THE SLIDE-OUT DRAIN PAIN, A REAR CLEARANCE OF 6.83 60 in (1525 mm) IS REQUIRED. IF SPACE IS UNAVAILABLE, THE DRAIN PAN CAN BE REMOVED THROUGH THE FRONT BY SEPARATING [173] THE CORNER WALL. 24.38 5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES [619] CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. 6. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 32.06 7. SIDE DUCT FLANGES ARE 0.75" HIGH. [814] BOTTOM DUCTS DO NOT HAVE FLANGES. A 8. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES THE LOWEST NEGATIVE STATIC. 9. DIMENSIONS IN [ ] ARE IN MILLIMETERS OR KILOGRAMS. 26.10 10. OPTIONAL COIL GUARDS, POWER EXHAUST, GAS HEAT, [663] ECONOMIZER, DISCONNECT SWITCH, CONVENIENCE OUTLET, (FROM MTG. AND BAROMETRIC RELIEF & FRESH AIR HOODS SHOWN. FLANGE) 11. DELETED 12. 8 TUBE HEAT EXCHANGER IS NOT AVAILABLE FOR 3 & 4 TON UNITS. LEFT DIRECTION OF AIRFLOW CENTER OF GRAVITY 20.39 19.14 [518] 17.14 20.14 [486] 3/4" FPT [435] [512]

32.68 [830]

18.00 [457]

DETAIL A OUTSIDE AIR INTAKE HOOD (OPTIONAL)

25.72 [653]

DISCONNECT SWITCH COVER (OPTIONAL) POWER ENTRY ɸ 2.50 [64] FRESH AIR HOOD/ ECONOMIZER (OPTIONAL) CTL PANEL/ COMPRESSOR ACCESS

CONTROL ENTRY ɸ 0.875 [22] POWER ENTRY ɸ 2.50 [64]

7.85 [199] 6.82 [173]

10.47 ALTERNATE CONDENSATION DRAIN [266]

RIGHT

(LBS) (BASE UNIT) C D 218 [99] 292 [133] 223 [101] 299 [136] 217 [99] 266 [121] 230 [104] 309 [140] 205 [93] 251 [114] 221 [100] 271 [123] 218 [99] 267 [121] 249 [113] 333 [151] 251 [114] 337 [153] 255 [116] 281 [128] 260 [118] 285 [129] 257 [117] 293 [133]

18.25 [464] R E T U R N

16.00 [406]

21.00 [533]

Y

4 POINT CORNER LOADS A B 200 [91] 149 [68] 205 [93] 153 [69] 210 [95] 171 [78] 212 [96] 158 [72] 172 [78] 141 [64] 214 [97] 174 [79] 211 [96] 172 [78] 214 [97] 161 [73] 216 [98] 161 [73] 202 [92] 184 [84] 217 [98] 198 [90] 223[101] 196 [89]

B

S U P 24.00 P [610] L Y

R E T U 27.50 R [699] N

27.75 [705]

SUPPLY

12.06 [306]

C

D 14.47 [368] 18.06 [459]

5.32 [135]

U CENTER OF GRAVITY OPERATING N I WEIGHT(LBS) LOCATION (BASE UNIT) X Y T (BASE UNIT) 6.5 ZF 860 [390] 38 [965] 24 [610] 7.5 880 [399] 38 [965] 24 [610] ZF 5 864 [393] 40 [1016] 26 [660] ZH 6.5 & 7.5 ZH 910 [413] 38 [965] 24 [610] 5 770 [349] 40 [1016] 24 [610] ZJ 4 880 [399] 40 [1016] 26 [660] ZR 5 868 [394] 40 [1016] 26 [660] ZR 6.5 957 [435] 38 [965] 23 [584] ZR 7.5 965 [438] 38 [965] 23 [584] ZR 3 922 [418] 42.4 [1077] 24.7 [627] ZT 4 ZT 960 [436] 42.5 [1080] 25.5 [648] 5 ZT 968 [439] 41.6 [1057] 25.5 [648] TONNAGE

X

16.39 [416] 18.89 [480]

FRONT

BOTTOM GAS 5.16 SUPPLY ENTRY ɸ 2.00 [51] [131] BOTTOM ENTRY: POWER ɸ 2.50 [64] CONTROL 3X ɸ 0.875 [22] TOP VIEW

89.00 [2261] FILTER/ COMPRESSOR ACCESS

27.5 [699]

2.97 [75]

31.69 [805]

REAR (PARTIAL VIEW) (INTAKE HOOD NOT SHOWN IN THIS VIEW) 58.09 [1475]

GAS INLET

BLOWER ACCESS

42.03 [1068]

BAROMETRIC RELIEF HOOD/ POWER EXHAUST(OPTIONAL) CONVENIENCE OUTLET COVER (OPTIONAL) CONVENIENCE OUTLET POWER ENTRY ɸ 0.875 [22] LEFT VIEW Unitary Sales Tool v1.5.9.0  

27.31 [694]

SEE DETAIL A FOR DRAIN LOCATION

21.19 [538] EXHAUST FLUE

11.38 [289]

89.00 [2261] FRONT VIEW (OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEW) Information is subject to change without notice. Check local codes.

59.00 [1499] RIGHT VIEW

COIL GUARD (OPTIONAL)

Printed 03/21/2016

 

 

Predator

Page: 15

York Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF090S18D2D1HAD2A1

Quantity:   1  Tag #: RTU-2

System:    ZF090S18D2D1HAD2A1 Factory Installed Power Exhaust

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Predator

Page: 16

York Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF090S18D2D1HAD2A1

Quantity:   1  Tag #: RTU-2

System:    ZF090S18D2D1HAD2A1 Component Location

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Predator

Page: 17

York Single Package R-410A Air Conditioner Project Name:  55th Lyndale

Unit Model #:    ZF090S18D2D1HAD2A1

Quantity:   1  Tag #: RTU-2

System:    ZF090S18D2D1HAD2A1 1RC0471 Roof Curb

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

  Date 01/05/2016

Project Name 55th Lyndale

Project Number  

SPMN-011816-01

Client / Purchaser  

Guide Specification Summary Page   Product Series

Models and Unit Tags

Small Sunline

ZF060S10B2FZZ40001

Predator

ZF090S18D2D1HAD2A1

Unitary Sales Tool v1.5.9.0  

RTUs 1,3 RTU-2

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Guide Specification for York Sunline GENERAL Units shall be manufactured by Johnson Controls Unitary Products in an ISO 9001 certified facility. York Sunline units are convertible single package units. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit. All non-Scroll compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry a 5year warranty. Aluminized steel and Stainless steel tubular heat exchangers carry a 10-year warranty. DESCRIPTION Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heat, Electric Cooling/Optional Electric Heat, Heat Pump/Optional Electric Heat are designed for outdoor mounted installation. The 3 ton, 4 ton and 5 ton units shall have minimum SEER rating of 13.0 with heat pumps having a 7.7 H.S.P.F. The 6 Ton Cooling only or Cooling with Electric Heat shall have 11.2 EER, 6 Ton Cooling with Gas Heat shall have 11.0 EER. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with Unitary Sales Tool v1.5.9.0  

Page: 19

DOE and AHRI test procedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards. UNIT CABINET Unit cabinet shall be constructed of galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1" or 2" filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection. INDOOR (EVAPORATOR) FAN ASSEMBLY The indoor fan shall be a factory installed direct-drive or belt-drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Guide Specification for York Sunline REFRIGERANT COMPONENTS

  f. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.

Compressors:   a. Shall be internally protected with internal highpressure relief and over temperature protection.   b. Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.   Coils:   a. Evaporator coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.   b. Evaporator coils shall be of the direct expansion, draw-thru design.   c. Condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed or Micro-Channel aluminum tube, aluminum fins.   d. Condenser coils shall be of the direct expansion, draw-thru design.   Refrigerant Circuit and Refrigerant Safety Components shall include:   a. Independent fixed-orifice or thermally operated expansion devices.   b. Filter drier/strainer to eliminate any moisture or foreign matter.   c. Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.

  g. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.   h. Unit control board shall have on-board diagnostics and fault code display.   i. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F.   j. Control board shall monitor each refrigerant safety switch independently.   k. Control board shall retain last 5 fault codes in non volatile memory which will not be lost in the event of a power loss. GAS HEATING SECTION (SINGLE STAGE) Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb without any field modifications. Integrated control boards shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection.   a. Primary and auxiliary high-temperature limit switches.   b. Induced draft motor speed sensor.

  d. The refrigeration system shall provide at least 15°F of sub-cooling at design conditions.

  c. Flame roll out switch.

Unit Controls:

  e. If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

  a. Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-volt transformer side.   b. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.   c. Loss-of-charge/Low-pressure switch.   d. High-pressure switch.   e. Freeze-protection thermostat, evaporator coil.

Unitary Sales Tool v1.5.9.0  

Page: 20

  d. Flame proving controls.

NOTE: All 2 Stage Gas Heat, 60% Capacity 1st Stage, 40% Capacity 2nd Stage. UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of AHRI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Guide Specification for York Sunline ELECTRICAL REQUIREMENTS

  •

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

Page: 21

Roof Curb – 14” high, full perimeter curb with wood nailer (shipped knocked-down). 

STANDARD LIMITED WARRANTIES •

Compressor 5 Years



Heat Exchanger 10 Years



Electric Heat Element 5 Years



Other Parts 1 Year

    OPTIONAL OUTDOOR AIR   •

Economizer – Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. 

ADDITIONAL FACTORY INSTALLED OPTIONS   •

Stainless Steel Heat Exchanger – For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

  •

Phase Monitor – Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition.

  •

Hinged Filter Door Access And Toolless Access Panels

  •

2" Pleated Filters, MERV 7

  •

Return Air Smoke Detector - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

FIELD INSTALLED OPTIONS

Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Page: 22

Guide Specification for York Predator GENERAL Units shall be manufactured by Unitary Products in an ISO 9001 certified facility. York Predator units are convertible single packages with a common footprint cabinet and common roof curb for all 6-1/2 through 121/2 ton models. All units have two compressors with independent R-410A refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged with R-410A, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Units are available in the following configurations: cooling only, cooling with electric heat, cooling with gas heat, reheat only, reheat with electric heat, reheat with gas heat, heat pump and heat pump with electric heat. Electric heaters are available as factory-installed options or field-installed accessories. DESCRIPTION Units shall be factory assembled, single package, (Elec/Elec, Gas/ Elec), designed for outdoor installation. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with factory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and AHRI test procedures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards. UNIT CABINET Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hour salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with up to 1” thick insulation coated on the airside. Either aluminum foil faced or elastometric rubber insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished as standard and be accessible through hinged access door. Fan performance measuring ports shall be provided on the Unitary Sales Tool v1.5.9.0  

outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out design, constructed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate connection shall be a minimum of ¾” I.D. female and be rigid mount connection. OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning. REFRIGERANT COMPONENTS Compressors:   a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit nameplate voltage.   b. Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.   Coils:   a. Evaporator coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.   b. Evaporator coils shall be of the direct expansion, draw-thru design.   c. Condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed or Micro-Channel aluminum tube, aluminum fins. Special Phenolic coating shall be available as a factory option.   d. Condenser coils shall be of the draw-thru design.   Refrigerant Circuit and Refrigerant Safety Components shall include:   a. Independent fixed-orifice or thermally operated expansion devices.   b. Solid core filter drier/strainer to eliminate any moisture or foreign matter.

Information is subject to change without notice. Check local codes.

Printed 03/21/2016

 

 

Page: 23

Guide Specification for York Predator   c. Accessible service gage connections on both suction and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.

  d. All two stage gas units shall have two independent stages of capacity (70% or 75% 1st stage, 100% 2nd stage) 3 through 5 ton and (60% 1st stage, 100% 2nd stage) 6-1/2 through 12-1/2 ton. 

  d. The unit shall have two independent refrigerant circuits, equally split in 50% capacity increments.

UNIT OPERATING CHARACTERISTICS

Unit Controls:   a. Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-volt transformer side.   b. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor:   • Loss-of-charge/Low-pressure switch.   •

High-pressure switch.

  •

Freeze condition sensor on evaporator coil.  If any of these safety devices trip, the LCD screen will display the alarm message.

  c. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.   d. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.   e. Unit control board shall have on-board diagnostics and fault message display.   f. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to a selectable value as low as 0 ºF.

Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only)   ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. STANDARD LIMITED WARRANTIES - Compressor – 5 Years, Heat Exchanger – 10 Years, Stainless Steel Heat Exchanger – 15 Years, Elect. Heat Elem. – 5 Years, Parts – 1 Year. FACTORY  INSTALLED  OPTIONAL  OUTDOOR  AIR (Shall be made available by either/or): ADDITIONAL FACTORY INSTALLED OPTIONS   •

Alternate Indoor Blower Motor – For applications with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow. 

  •

BAS Controls – Include supply air sensor, return air sensor, dirty filter indicator and air proving switch. 

  •

Stainless Steel Heat Exchanger – For applications in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.

  •

Smoke Detector – A smoke detector can be factory mounted and wired in the supply and/or return air compartments. 

  g. Control board shall monitor each refrigerant safety switch independently. GAS HEATING SECTION Heat exchanger and exhaust system shall be constructed of aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection:   a. Primary and auxiliary high-temperature limit switches.   b. Induced draft pressure sensor.

FIELD INSTALLED OPTIONS   •

Roof Curb – 14” high, full perimeter knockdown curb, with hinged design for quick assembly. 

  •

Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. 

  c. Flame proving controls.  Unitary Sales Tool v1.5.9.0  

Information is subject to change without notice. Check local codes.

Printed 03/21/2016