Hazardous Location Fittings & Outlet Boxes

BA37

Threaded Insert Plugs For Outlet Boxes & Hubs Type PLG Use: To close up a taped hole or hub

Trade Size

Catalog Number (inches) Steel/Iron

Material/Finish: 1 ⁄2” - 1” Steel/Zinc Electroplated or Copper-free Aluminum 11⁄4” - 6” Malleable Iron/Zinc Electroplated or Copper-free Aluminum Third Party Certification: UL Listed: E-34997 Suitable for wet locations. UL Listed for hazardous location use as follows: PLG-50R through PLG-100R; PLG-50RA through PLG-100RA: Class I, Div. 1, 2, Groups A, B, C, D Class I, Zone 1, 2, Groups IIA, IIB, IIC Class II, Div. 1, 2, Groups E, F, G Class III PLG-125R through PLG-200R, PLG-125RA through PLG-200RA PLG-250C through PLG-400C: Class I, Div. 1, 2, Groups B, C, D Class I, Zone 1, 2, Groups IIA, IIB + H2 Class II, Div. 1, 2, Groups E, F, G Class III PLG-250CA through PLG-400CA: Class I, Div. 1, 2, Groups C, D Class I, Zone 1, 2, Groups IIA, IIB Class II, Div. 1, 2, Groups E, F, G Class III PLG-500C, PLG-600C: Class I, Div. 1, 2, Group D Class I, Zone 1, 2, Group IIA Class II, Div. 1, 2, Groups E, F, G Class III

Dim. in Inches

Body Thk.

Socket Size

⁄2 ⁄4 1 11⁄4

PLG-50R PLG-75R PLG-100R PLG-125R

PLG-50RA PLG-75RA PLG-100RA PLG-125RA

1

3

1

1

11⁄2 2 21⁄2 3

PLG-150R PLG-200R PLG-250C PLG-300C

PLG-150RA PLG-200RA PLG-250CA PLG-300CA

⁄4 ⁄4 11⁄8 11⁄4

n/a n/a

31⁄2 4 5 6

PLG-350C PLG-400C PLG-500C PLG-600C

PLG-350CA PLG-400CA

11⁄4 11⁄4 13⁄8 11⁄2

n/a n/a n/a n/a

1

3

Features: Threaded (NPT)

Catalog Number Aluminum

⁄2 ⁄2 3 ⁄4 3 ⁄4

⁄8 ⁄2 1 ⁄2 3 ⁄4 ⁄4

3 3

3

1

Type PLG-50R—Type PLG-200R Type PLG-50RA—Type PLG-200RA (Internal Recessed)

Type PLG-250C— Type PLG-600C Type PLG-250CA—Type PLG-400CA (Patented)

CSA Certified: 9795 Applicable Third Party Standards: UL Standard: 886 CSA Standard: C22.2 No. 30 NEC Articles 500-503 & 505

Effective November, 2005 Copyright 2005

800-621-1506 www.o-zgedney.com

BA38

Hazardous Location Fittings & Outlet Boxes

BA38

Reducing Bushings Type RB Flush Type Reducers

Trade Size

(inches)

Steel/ Iron Catalog Number

Aluminum Catalog Number

Dim. in Inches

Body Length

Use: To reduce the trade size of a tapped hole or hub.

∕2 ∕4 1 1

∕8 ∕2 ∕4 1 ∕2

RB-320S RB-321S RB-322S RB-323S

RB-321A RB-322A RB-323A

23

Features: • Tapered threads (NPT) • Smooth internal bushing protects conductors. • Threaded for Rigid Conduit or IMC.

11∕4 - 1∕2 11∕4 - 3∕4 11∕4 - 1

RB-324S RB-325S RB-326S

RB-324A RB-325A RB-326A

13

11∕2 11∕2 11∕2 11∕2 -

11∕4 1 3 ∕4 1 ∕2

RB-327S RB-328S RB-329S RB-330S

RB-327A RB-328A RB-329A RB-330A

13

2 2 2 2 2

11∕2 11∕4 1 3 ∕4 1 ∕2

RB-331 RB-332 RB-333 RB-334 RB-335

RB-331A RB-332A RB-333A RB-334A RB-335A

21∕2 - 2 21∕2 - 11∕2 21∕2 - 1

RB-336 RB-337 RB-339

RB-336A RB-337A RB-339A

1 1 1

3 - 11∕2 3 - 2 3 - 21∕2

RB-340 RB-341 RB-342

RB-340A RB-341A RB-342A

11∕4 11∕4 11∕4

31∕2 - 3 31∕2 - 21∕2

RB-349 RB-350

RB-349A RB-350A

13∕8 13∕8

4 4 4 4

RB-351 RB-355 RB-356 RB-357

RB-351A RB-355A RB-356A RB-357A

11∕2 11∕2 11∕2 11∕2

Material/Finish: RB-320S to RB-330S Steel/Zinc Electroplated RB-331 to RB-357 Malleable Iron/Zinc Electroplated RB-321A to RB-357A Copper-free Aluminum/Natural Finish Third Party Certification: UL Listed: E-34997 RB-321S through RB-330S RB-321A through RB-330A Class I, Div. 1, 2, Groups A, B, C, D Class I, Zone 1, 2, Groups IIA, IIB, IIC Class II, Div. 1, 2, Groups E, F, G Class III RB-331 through RB-357 RB-331A through RB-357A Class I, Div. 1, 2, Groups B, C, D Class I, Zone 1, 2, Groups IIA, IIB + H2 Class II, Div. 1, 2, Groups E, F, G Class III

1 3

-

-

-

3 1 3

2 21∕2 3 31∕2

∕32 ∕32 ∕32

23 23

∕16 ∕16 ∕16

13 13

∕16 ∕16 ∕16 13 ∕16 13

Type RB

13

∕8 ∕8 ∕8 7 ∕8 7 ∕8 7 7 7

CSA Certified: 9795

Applicable Third Party Standards: UL Standard: 886 CSA Standard: C22.2 No. 30 NEC Articles 500-503 & 505

Effective November, 2005 Copyright 2005

800-621-1506 www.o-zgedney.com

BA39

BA39

Hazardous Location Fittings & Outlet Boxes

Reducing Couplings & Male Enlargers Type REC -

Reducing Couplings

Use: To connect two different sizes of conduit together or to replace a coupling and reducer in an installation. Features: Tapered threads (NPT) Materials: REC-0705S through REC-1007S Steel/Zinc Electroplated REC-1207 through REC-5040 Malleable Iron/Zinc Electroplated Third Party Certification: CSA Certified: LR-9795 Class I, Div. 1, 2, Groups A, B, C, D Class II, Div. 1, 2, Groups E, F, G Class III

Trade Size

Dimension in Inches

Catalog Number

Body Length

REC-0705S REC-1005S REC-1007S REC-1207

15⁄8 113⁄16 113⁄16 17⁄8

19⁄16 113⁄16 113⁄16 23⁄16

11⁄4 - 1 11⁄2 - 3⁄4 11⁄2 - 1 11⁄2 - 11⁄4

REC-1210 REC-1507 REC-1510 REC-1512

2 17⁄8 2 2

23⁄16 21⁄2 21⁄2 21⁄2

2 2 2 2

- 3⁄4 - 1 - 11⁄4 - 11⁄2

REC-2007 REC-2010 REC-2012 REC-2015

17⁄8 2 2 2

3 3 3 3

21⁄2 - 11⁄2 3 - 2 4 - 3 5 - 4

REC-2515 REC-3020 REC-4030 REC-5040

21⁄2 29⁄16 33⁄16 43⁄4

39⁄16 41⁄4 53⁄8 613⁄16

(inches) 3 ⁄4 1 1 11⁄4 -

⁄2 ⁄2 3 ⁄4 3 ⁄4 1 1

Max. Dia.

Type REC-0705S—Type REC-1007S

Applicable Third Party Standards: CSA Standard: C22.2 No. 30 NEC Articles 500-503 & 505

Type ME- S -

Type REC-1207—Type REC-5040

Male Enlargers

Use: Enlarges a threaded hub in an enclosure or fitting. Example: A 3⁄4” conduit may connect to a 1⁄2” female hub by using an ME-323S. See illustration below.

Dimension in Inches

Catalog Number ME-323S ME-324S ME-325S

Thread (NPT) Female Male ⁄4 1 11⁄4 3

⁄2 ⁄4 1

1 3

Body Length 19⁄16 13⁄4 115⁄16

Hub Length

Max. Dia

⁄8 ⁄16 13 ⁄16

13⁄16 17⁄16 113⁄16

5

11

Features: • Knurled female hub • Tapered threaded hubs (NPT) for Rigid Conduit and IMC.

Type ME-S

Material/Finish: Steel/Zinc Electroplated Third Party Certification: UL Listed: E-34997 Class I, Div. 1, 2, Groups A, B, C, D Class I, Zone 1, 2, Groups IIA, IIB, IIC Class II, Div. 1, 2, Groups E, F, G Class III Suitable for wet locations

1

3

⁄2”

⁄4”

NPT

NPT

CSA Certified: 9795 3

Applicable Third Party Standards: UL Standards: 514B and 886 CSA Standard: C22.2 No. 30 NEC Articles 500-503 & 505

⁄4” Rigid Conduit

ME-323S

GUAL-50

Suggested Specification: Where male enlargers are required, they shall be of steel construction, UL Listed for use in wet and hazardous locations as defined in NEC Articles 500-503 and 505. The male enlargers shall be O-Z/Gedney Type ME-S. Effective November, 2005 Copyright 2005

800-621-1506 www.o-zgedney.com

BA40

BA40

Hazardous Location Fittings & Outlet Boxes

Pull Box Fittings Existing Conduit Existing Condui t

Reducer Reducer Sleeve Sleeve Length Length

Tapered Tapered Bushing Bushing

Dimensions in Inches

Locknut Locknut

Trade Size

Adapter Adapter Max. Max. Dia. Dia.

Max. Dia.

B

⁄2 ⁄2 1 ⁄2 1 ⁄2

PFV-50-12 PFV-50-18 PFV-50-24 PFV-50-30

33⁄8 33⁄8 33⁄8 33⁄8

23⁄8 23⁄8 23⁄8 23⁄8

43⁄8 43⁄8 43⁄8 43⁄8

21⁄2 21⁄2 21⁄2 21⁄2

12 18 24 30

⁄4 ⁄4 3 ⁄4 3 ⁄4 3 ⁄4

PFV-75-12 PFV-75-18 PFV-75-24 PFV-75-30 PFV-75-36

33⁄8 33⁄8 33⁄8 33⁄8 33⁄8

23⁄8 23⁄8 23⁄8 23⁄8 23⁄8

43⁄8 43⁄8 43⁄8 43⁄8 43⁄8

21⁄2 21⁄2 21⁄2 21⁄2 21⁄2

12 18 24 30 36

1 1 1 1 1

PFV-100-12 PFV-100-18 PFV-100-24 PFV-100-30 PFV-100-36

33⁄8 33⁄8 33⁄8 33⁄8 33⁄8

23⁄8 23⁄8 23⁄8 23⁄8 23⁄8

43⁄8 43⁄8 43⁄8 43⁄8 43⁄8

21⁄2 21⁄2 21⁄2 21⁄2 21⁄2

12 18 24 30 36

11⁄4 11⁄4 11⁄4 11⁄4 11⁄4

PFV-125-18 PFV-125-24 PFV-125-30 PFV-125-36 PFV-126-48

41⁄8 41⁄8 41⁄8 41⁄8 41⁄8

21⁄2 21⁄2 21⁄2 21⁄2 21⁄2

45⁄8 45⁄8 45⁄8 45⁄8 45⁄8

31⁄2 31⁄2 31⁄2 31⁄2 31⁄2

18 24 30 36 48

11⁄2 11⁄2 11⁄2 11⁄2 11⁄2

PFV-150-18 PFV-150-24 PFV-150-30 PFV-150-36 PFV-150-48

45⁄8 45⁄8 45⁄8 45⁄8 45⁄8

25⁄8 25⁄8 25⁄8 25⁄8 25⁄8

45⁄8 45⁄8 45⁄8 45⁄8 45⁄8

31⁄2 31⁄2 31⁄2 31⁄2 31⁄2

18 24 30 36 48

2 2 2 2 2

PFV-200-18 PFV-200-24 PFV-200-30 PFV-200-36 PFV-200-48

51⁄8 51⁄8 51⁄8 51⁄8 51⁄8

23⁄4 23⁄4 23⁄4 23⁄4 23⁄4

5 5 5 5 5

4 4 4 4 4

18 24 30 36 48

21⁄2 21⁄2 21⁄2 21⁄2

PFV-250-24 PFV-250-30 PFV-250-36 PFV-250-48

53⁄4 53⁄4 53⁄4 53⁄4

31⁄8 31⁄8 31⁄8 31⁄8

53⁄8 53⁄8 53⁄8 53⁄8

41⁄2 41⁄2 41⁄2 41⁄2

24 30 36 48

3 3 3 3 3

PFV-300-24 PFV-300-30 PFV-300-36 PFV-300-48 PFV-300-60

63⁄8 63⁄8 63⁄8 63⁄8 63⁄8

33⁄8 33⁄8 33⁄8 33⁄8 33⁄8

53⁄4 53⁄4 53⁄4 53⁄4 53⁄4

5 5 5 5 5

24 30 36 48 60

31⁄2 31⁄2 31⁄2 31⁄2

PFV-350-30 PFV-350-36 PFV-350-48 PFV-350-60

73⁄8 73⁄8 73⁄8 73⁄8

31⁄8 31⁄8 31⁄8 31⁄8

57⁄8 57⁄8 57⁄8 57⁄8

6 6 6 6

30 36 48 60

4 4 4 4

PFV-400-36 PFV-400-48 PFV-400-60 PFV-400-72

83⁄8 83⁄8 83⁄8 83⁄8

33⁄8 33⁄8 33⁄8 33⁄8

61⁄8 61⁄8 61⁄8 61⁄8

7 7 7 7

36 48 60 72

5 5 5

PFV-500-48 PFV-500-60 PFV-500-72

93⁄8 93⁄8 93⁄8

33⁄4 33⁄4 33⁄4

61⁄4 61⁄4 61⁄4

8 8 8

48 60 72

(inches) Existing Condui t Existing Straight Conduit B

C

Type PFV

1 1

“C” plus sleeve length

3 3

Type PFV Use: Used in hazardous locations to provide a convenient pulling point on long conduit runs and meet NEC Section 314.28(A)(1) requirements on length of boxes on straight pulls. Features: • One fitting consists of two hot dip galvanized end units threaded onto a hot dip galvanized oversize sleeve. A minimum engagement of five full threads is provided at all threaded joints. • For Ordinary Location Pull Box Fittings - see catalog section CA. Material/Finish: Malleable or Ductile Iron End Fittings Steel Oversized Sleeve/Hot Dip Galvanized Third Party Certification: UL Listed: E-30513 UL Listed for: Class I, Div. 1, 2, Group D Class I, Zone 1, 2, Group IIA Class II, Div. 1, 2, Groups E, F, G Class III Applicable Third Party Standards: UL Standard: 886 NEC Articles 500-503 & 505 Mil. Spec: Mil-F-28675 Fed. Spec: A-A-50563 Suggested Specification: Type PFV: A hazardous location pull box fitting shall be used in hazardous locations for pulling and access points on long conduit runs. Box length on straight pulls shall meet NEC Section 314.28(A)(1) requirements. A minimum engagement of five full threads is to be provided at all threaded joints. They shall be malleable iron, hot dip galvanized with steel oversize sleeves. Hazardous location pull box fittings shall be O-Z/Gedney Type PFV. Effective November, 2005 Copyright 2005

Oversize Sleeve Sleeve Length C Size Inches

Catalog Number

800-621-1506 www.o-zgedney.com

BA41

Hazardous Location Fittings & Outlet Boxes

BA41

Thread Lubricant Type STL

Catalog Number

Package Weight

Use: For use between any threaded joint to help prevent seizing and galling.

STL-2 STL-8

2 oz tube 8 oz can

Features: • Effective and stable from -40°F to 600°F • Can be used between parts of dissimilar materials • Excellent adhesion qualities • Inhibits corrosion and aids in preventing moisture from entering threaded joints. • Maintains ground continuity • Available in squeeze tube or can with convenient brush in cap.

Type STL-2

Note: UL Listing not applicable.

Type STL-8

Effective November, 2005 Copyright 2005

800-621-1506 www.o-zgedney.com