Cutout Templates
Installation Instructions
4
4500 Series Electric Strike
Inches [mm]
JAMB CUTOUT DIMENSIONS
4500 WITH CYLINDRICAL LOCKSETS
1-1/4” [31.8]
1 2 3 4
4500 Electric Strike Body Keeper Shims & Screws (#4-40 x 1/8” and #4-40 x 3/16”) Centerlined and Non Handed Faceplate for Cylindrical Locksets Offset and Non Handed Faceplate for Mortise Locksets
5 6 7
4-7/8" [123.8]
3-5/8" [92.1]
2-1/4" [57.2]
1
4-1/8" [104.8]
CL Strike
2
4-7/8” [123.8]
3 4
1-1/4" [31.8]
5/8" [15.9]
1-3/4" [44.5]
1” [25.4]
4500 WITH MORTISE LOCKSETS CL Vertical Centerline
Mortise Lockset
#12-24 x 1/2” Mounting Screws 12 & 24 Volt Plug In Connectors Trim Enhancer & Screws
CL Lock
1-1/8" [28.6] 3-5/8” [92.1]
1
Product Components
Strike Prep
CL Vertical Centerline
Cylindrical Lock
HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com
1-1/4" [31.8]
7
SCHLAGE L9000 & YALE 8700 LOCKS ONLY
Strike Prep
CL Vertical Centerline
Mortise Lockset
5
Strike Prep 6
CL Lock
4" [101.6]
4-7/8" [123.8]
3-5/8" [92.1] 8" [203.2]
4-1/8" [104.8]
3/8" [9.5] CL Strike
1-3/4" [44.5]
3053006.002 rev B
4" [101.6]
3-5/8" [92.1]
8" [203.2]
4-7/8" [123.8] 4-1/8" [104.8]
Electrical Specifications
CL Strike
5/8" [15.9]
1-1/4" [31.8]
CL Lock
1-1/4" [31.8]
ELECTRICAL RATINGS FOR SOLENOID
Resistance in Ohms
5/8" [15.9]
1-1/4" [31.8] 1-3/4" [44.5]
1-1/4" [31.8]
© 2011 HES, Inc.
Amps
CONTINUOUS DUTY 12VDC
24VDC
12-16VAC
24VAC
50
200
50
200
.24
.12
.24-.32
.12
Solenoids are rated at +/- 10% indicated value. *10% max duty cycle (2 min. max on time)
ASSA ABLOY, the global leader in door opening solutions
INTERMITTENT DUTY*
MINIMUM WIRE GAUGE REQUIREMENTS
SOLENOID VOLTAGE 12VDC
24VDC
200 feet or less
18 gauge
20 gauge
200 - 300 feet
16 gauge
18 gauge
300 - 400 feet
14 gauge
16 gauge
Installation Directions
2
Installation Diagrams DIAGRAM 2: LATCHBOLT MONITOR
CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
Prepare Frame
1. Select the appropriate Plug In Connector that matches system power and electrically connect as illustrated in Diagram 1. For 12V AC/DC or 16V AC, the pigtail marked “12 VDC” should be used. For 24V AC/DC, the pigtail marked “24 VDC” should be used. 2. If using Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), see Diagram 2 & 3 on page 3 to complete wiring. State of switch is listed for an unpowered strike and LBM in unactuated (door open) position. 3. Verify that the strike is in the correct mode of operation. This unit ships in Fail Secure mode. If you need to convert to Fail Safe see Diagram 4 on page 3. NOTE: FAIL SAFE CONVERSION NEGATES FIRE RATING.
DIAGRAM 3: STRIKE MONITOR LBSM WIRING
LBM WIRING Common
Brown
Common
Orange
Normally Open
Blue
Normally Open
Green
Normally Closed
Yellow
Normally Closed
White
Prepare Strike
3
White Orange Green
Unpowered and in unactuated state
4. Prepare frame using appropriate template for your lockset on page 4. Schlage L9000 & Yale 8700 locksets must use the template labeled “Schlage L9000 & Yale 8700 Locks Only.” All other locksets should use the template labeled “CYLINDRICAL LOCKSET” or “MORTISE LOCKSET.”
Unpowered and in unactuated state
Brown Blue Yellow
DIAGRAM 4: FAIL SAFE CONVERSION* Convert Mode
Fire Door Safety Screw
a. Remove the Fire Door Safety Screw as illustrated. b. Loosen the two #2-56 screws located on the back of the strike as shown above, but do not remove them.
Finish Installing 5. Choose the appropriate faceplate for the strike as illustrated in Diagram 5 on page 3.
a
b
c. Move screws from the bottom of the hole (fail secure position) to the top hole (fail safe position) and re-tighten.
6. Connect wires from the power source to the strike.
Verify d. Verify the strike is now in the Fail Safe operation mode. If the strike still operates as Fail Secure, be sure screws are fully seated in the top position.
7. Install the electric strike unit in jamb cutout, using #12-24 x 1/2” Mounting Screws provided. 8. If horizontal adjustment is needed, see Diagram 6 on page 3.
*USING THE 4500 FOR FAIL SAFE OPERATION NEGATES FIRE RATING
DIAGRAM 5: FACEPLATE OPTIONS
DIAGRAM 6: HORIZONTAL ADJUSTMENT
DIAGRAM 1: 12V to 24V CONVERSION a
b
If horizontal adjustment is needed, 1 or 2 keeper shims can be added as illustrated below.
One Shim If adding a single shim use the #4-40 x 1/8” Keeper Shim Screws.
IF CONNECTOR IS MISSING
VIOLET
BLACK
RED/GREEN
(+ 12 VDC) (-NEG) CONNECT TOGETHER
RED
ELECTRIC STRIKE
ELECTRIC STRIKE
RED
CONNECT TOGETHER
(+ 24 VDC)
VIOLET
CONNECT TOGETHER BLACK RED/GREEN
(-NEG)
a. A Non-Handed offset faceplate is provided for use with mortise locksets. The mortise lock deadlatch should be depressed by the faceplate when the door is closed. b. A Non-Handed center-lined faceplate is provided for use with cylindrical locksets
Both Shims If adding both shims use the #4-40 x 3/16” Keeper Shim Screws.
Installation Directions
2
Installation Diagrams DIAGRAM 2: LATCHBOLT MONITOR
CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
Prepare Frame
1. Select the appropriate Plug In Connector that matches system power and electrically connect as illustrated in Diagram 1. For 12V AC/DC or 16V AC, the pigtail marked “12 VDC” should be used. For 24V AC/DC, the pigtail marked “24 VDC” should be used. 2. If using Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), see Diagram 2 & 3 on page 3 to complete wiring. State of switch is listed for an unpowered strike and LBM in unactuated (door open) position. 3. Verify that the strike is in the correct mode of operation. This unit ships in Fail Secure mode. If you need to convert to Fail Safe see Diagram 4 on page 3. NOTE: FAIL SAFE CONVERSION NEGATES FIRE RATING.
DIAGRAM 3: STRIKE MONITOR LBSM WIRING
LBM WIRING Common
Brown
Common
Orange
Normally Open
Blue
Normally Open
Green
Normally Closed
Yellow
Normally Closed
White
Prepare Strike
3
White Orange Green
Unpowered and in unactuated state
4. Prepare frame using appropriate template for your lockset on page 4. Schlage L9000 & Yale 8700 locksets must use the template labeled “Schlage L9000 & Yale 8700 Locks Only.” All other locksets should use the template labeled “CYLINDRICAL LOCKSET” or “MORTISE LOCKSET.”
Unpowered and in unactuated state
Brown Blue Yellow
DIAGRAM 4: FAIL SAFE CONVERSION* Convert Mode
Fire Door Safety Screw
a. Remove the Fire Door Safety Screw as illustrated. b. Loosen the two #2-56 screws located on the back of the strike as shown above, but do not remove them.
Finish Installing 5. Choose the appropriate faceplate for the strike as illustrated in Diagram 5 on page 3.
a
b
c. Move screws from the bottom of the hole (fail secure position) to the top hole (fail safe position) and re-tighten.
6. Connect wires from the power source to the strike.
Verify d. Verify the strike is now in the Fail Safe operation mode. If the strike still operates as Fail Secure, be sure screws are fully seated in the top position.
7. Install the electric strike unit in jamb cutout, using #12-24 x 1/2” Mounting Screws provided. 8. If horizontal adjustment is needed, see Diagram 6 on page 3.
*USING THE 4500 FOR FAIL SAFE OPERATION NEGATES FIRE RATING
DIAGRAM 5: FACEPLATE OPTIONS
DIAGRAM 6: HORIZONTAL ADJUSTMENT
DIAGRAM 1: 12V to 24V CONVERSION a
b
If horizontal adjustment is needed, 1 or 2 keeper shims can be added as illustrated below.
One Shim If adding a single shim use the #4-40 x 1/8” Keeper Shim Screws.
IF CONNECTOR IS MISSING
VIOLET
BLACK
RED/GREEN
(+ 12 VDC) (-NEG) CONNECT TOGETHER
RED
ELECTRIC STRIKE
ELECTRIC STRIKE
RED
CONNECT TOGETHER
(+ 24 VDC)
VIOLET
CONNECT TOGETHER BLACK RED/GREEN
(-NEG)
a. A Non-Handed offset faceplate is provided for use with mortise locksets. The mortise lock deadlatch should be depressed by the faceplate when the door is closed. b. A Non-Handed center-lined faceplate is provided for use with cylindrical locksets
Both Shims If adding both shims use the #4-40 x 3/16” Keeper Shim Screws.
Cutout Templates
Installation Instructions
4
4500 Series Electric Strike
Inches [mm]
JAMB CUTOUT DIMENSIONS
4500 WITH CYLINDRICAL LOCKSETS
1-1/4” [31.8]
1 2 3 4
4500 Electric Strike Body Keeper Shims & Screws (#4-40 x 1/8” and #4-40 x 3/16”) Centerlined and Non Handed Faceplate for Cylindrical Locksets Offset and Non Handed Faceplate for Mortise Locksets
5 6 7
4-7/8" [123.8]
3-5/8" [92.1]
2-1/4" [57.2]
1
4-1/8" [104.8]
CL Strike
2
4-7/8” [123.8]
3 4
1-1/4" [31.8]
5/8" [15.9]
1-3/4" [44.5]
1” [25.4]
4500 WITH MORTISE LOCKSETS CL Vertical Centerline
Mortise Lockset
#12-24 x 1/2” Mounting Screws 12 & 24 Volt Plug In Connectors Trim Enhancer & Screws
CL Lock
1-1/8" [28.6] 3-5/8” [92.1]
1
Product Components
Strike Prep
CL Vertical Centerline
Cylindrical Lock
HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com
1-1/4" [31.8]
7
SCHLAGE L9000 & YALE 8700 LOCKS ONLY
Strike Prep
CL Vertical Centerline
Mortise Lockset
5
Strike Prep 6
CL Lock
4" [101.6]
4-7/8" [123.8]
3-5/8" [92.1] 8" [203.2]
4-1/8" [104.8]
3/8" [9.5] CL Strike
1-3/4" [44.5]
3053006.002 rev B
4" [101.6]
3-5/8" [92.1]
8" [203.2]
4-7/8" [123.8] 4-1/8" [104.8]
Electrical Specifications
CL Strike
5/8" [15.9]
1-1/4" [31.8]
CL Lock
1-1/4" [31.8]
ELECTRICAL RATINGS FOR SOLENOID
Resistance in Ohms
5/8" [15.9]
1-1/4" [31.8] 1-3/4" [44.5]
1-1/4" [31.8]
© 2011 HES, Inc.
Amps
CONTINUOUS DUTY 12VDC
24VDC
12-16VAC
24VAC
50
200
50
200
.24
.12
.24-.32
.12
Solenoids are rated at +/- 10% indicated value. *10% max duty cycle (2 min. max on time)
ASSA ABLOY, the global leader in door opening solutions
INTERMITTENT DUTY*
MINIMUM WIRE GAUGE REQUIREMENTS
SOLENOID VOLTAGE 12VDC
24VDC
200 feet or less
18 gauge
20 gauge
200 - 300 feet
16 gauge
18 gauge
300 - 400 feet
14 gauge
16 gauge