Cutout Templates

Installation Instructions

4

4500 Series Electric Strike

Inches [mm]

JAMB CUTOUT DIMENSIONS

4500 WITH CYLINDRICAL LOCKSETS

1-1/4” [31.8]

1 2 3 4

4500 Electric Strike Body Keeper Shims & Screws (#4-40 x 1/8” and #4-40 x 3/16”) Centerlined and Non Handed Faceplate for Cylindrical Locksets Offset and Non Handed Faceplate for Mortise Locksets

5 6 7

4-7/8" [123.8]

3-5/8" [92.1]

2-1/4" [57.2]

1

4-1/8" [104.8]

CL Strike

2

4-7/8” [123.8]

3 4

1-1/4" [31.8]

5/8" [15.9]

1-3/4" [44.5]

1” [25.4]

4500 WITH MORTISE LOCKSETS CL Vertical Centerline

Mortise Lockset

#12-24 x 1/2” Mounting Screws 12 & 24 Volt Plug In Connectors Trim Enhancer & Screws

CL Lock

1-1/8" [28.6] 3-5/8” [92.1]

1

Product Components

Strike Prep

CL Vertical Centerline

Cylindrical Lock

HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com

1-1/4" [31.8]

7

SCHLAGE L9000 & YALE 8700 LOCKS ONLY

Strike Prep

CL Vertical Centerline

Mortise Lockset

5

Strike Prep 6

CL Lock

4" [101.6]

4-7/8" [123.8]

3-5/8" [92.1] 8" [203.2]

4-1/8" [104.8]

3/8" [9.5] CL Strike

1-3/4" [44.5]

3053006.002 rev B

4" [101.6]

3-5/8" [92.1]

8" [203.2]

4-7/8" [123.8] 4-1/8" [104.8]

Electrical Specifications

CL Strike

5/8" [15.9]

1-1/4" [31.8]

CL Lock

1-1/4" [31.8]

ELECTRICAL RATINGS FOR SOLENOID

Resistance in Ohms

5/8" [15.9]

1-1/4" [31.8] 1-3/4" [44.5]

1-1/4" [31.8]

© 2011 HES, Inc.

Amps

CONTINUOUS DUTY 12VDC

24VDC

12-16VAC

24VAC

50

200

50

200

.24

.12

.24-.32

.12

Solenoids are rated at +/- 10% indicated value. *10% max duty cycle (2 min. max on time)

ASSA ABLOY, the global leader in door opening solutions

INTERMITTENT DUTY*

MINIMUM WIRE GAUGE REQUIREMENTS

SOLENOID VOLTAGE 12VDC

24VDC

200 feet or less

18 gauge

20 gauge

200 - 300 feet

16 gauge

18 gauge

300 - 400 feet

14 gauge

16 gauge

Installation Directions

2

Installation Diagrams DIAGRAM 2: LATCHBOLT MONITOR

CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the solenoid rating may cause severe damage to the unit and will void the warranty.

Prepare Frame

1. Select the appropriate Plug In Connector that matches system power and electrically connect as illustrated in Diagram 1. For 12V AC/DC or 16V AC, the pigtail marked “12 VDC” should be used. For 24V AC/DC, the pigtail marked “24 VDC” should be used. 2. If using Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), see Diagram 2 & 3 on page 3 to complete wiring. State of switch is listed for an unpowered strike and LBM in unactuated (door open) position. 3. Verify that the strike is in the correct mode of operation. This unit ships in Fail Secure mode. If you need to convert to Fail Safe see Diagram 4 on page 3. NOTE: FAIL SAFE CONVERSION NEGATES FIRE RATING.

DIAGRAM 3: STRIKE MONITOR LBSM WIRING

LBM WIRING Common

Brown

Common

Orange

Normally Open

Blue

Normally Open

Green

Normally Closed

Yellow

Normally Closed

White

Prepare Strike

3

White Orange Green

Unpowered and in unactuated state

4. Prepare frame using appropriate template for your lockset on page 4. Schlage L9000 & Yale 8700 locksets must use the template labeled “Schlage L9000 & Yale 8700 Locks Only.” All other locksets should use the template labeled “CYLINDRICAL LOCKSET” or “MORTISE LOCKSET.”

Unpowered and in unactuated state

Brown Blue Yellow

DIAGRAM 4: FAIL SAFE CONVERSION* Convert Mode

Fire Door Safety Screw

a. Remove the Fire Door Safety Screw as illustrated. b. Loosen the two #2-56 screws located on the back of the strike as shown above, but do not remove them.

Finish Installing 5. Choose the appropriate faceplate for the strike as illustrated in Diagram 5 on page 3.

a

b

c. Move screws from the bottom of the hole (fail secure position) to the top hole (fail safe position) and re-tighten.

6. Connect wires from the power source to the strike.

Verify d. Verify the strike is now in the Fail Safe operation mode. If the strike still operates as Fail Secure, be sure screws are fully seated in the top position.

7. Install the electric strike unit in jamb cutout, using #12-24 x 1/2” Mounting Screws provided. 8. If horizontal adjustment is needed, see Diagram 6 on page 3.

*USING THE 4500 FOR FAIL SAFE OPERATION NEGATES FIRE RATING

DIAGRAM 5: FACEPLATE OPTIONS

DIAGRAM 6: HORIZONTAL ADJUSTMENT

DIAGRAM 1: 12V to 24V CONVERSION a

b

If horizontal adjustment is needed, 1 or 2 keeper shims can be added as illustrated below.

One Shim If adding a single shim use the #4-40 x 1/8” Keeper Shim Screws.

IF CONNECTOR IS MISSING

VIOLET

BLACK

RED/GREEN

(+ 12 VDC) (-NEG) CONNECT TOGETHER

RED

ELECTRIC STRIKE

ELECTRIC STRIKE

RED

CONNECT TOGETHER

(+ 24 VDC)

VIOLET

CONNECT TOGETHER BLACK RED/GREEN

(-NEG)

a. A Non-Handed offset faceplate is provided for use with mortise locksets. The mortise lock deadlatch should be depressed by the faceplate when the door is closed. b. A Non-Handed center-lined faceplate is provided for use with cylindrical locksets

Both Shims If adding both shims use the #4-40 x 3/16” Keeper Shim Screws.

Installation Directions

2

Installation Diagrams DIAGRAM 2: LATCHBOLT MONITOR

CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the solenoid rating may cause severe damage to the unit and will void the warranty.

Prepare Frame

1. Select the appropriate Plug In Connector that matches system power and electrically connect as illustrated in Diagram 1. For 12V AC/DC or 16V AC, the pigtail marked “12 VDC” should be used. For 24V AC/DC, the pigtail marked “24 VDC” should be used. 2. If using Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), see Diagram 2 & 3 on page 3 to complete wiring. State of switch is listed for an unpowered strike and LBM in unactuated (door open) position. 3. Verify that the strike is in the correct mode of operation. This unit ships in Fail Secure mode. If you need to convert to Fail Safe see Diagram 4 on page 3. NOTE: FAIL SAFE CONVERSION NEGATES FIRE RATING.

DIAGRAM 3: STRIKE MONITOR LBSM WIRING

LBM WIRING Common

Brown

Common

Orange

Normally Open

Blue

Normally Open

Green

Normally Closed

Yellow

Normally Closed

White

Prepare Strike

3

White Orange Green

Unpowered and in unactuated state

4. Prepare frame using appropriate template for your lockset on page 4. Schlage L9000 & Yale 8700 locksets must use the template labeled “Schlage L9000 & Yale 8700 Locks Only.” All other locksets should use the template labeled “CYLINDRICAL LOCKSET” or “MORTISE LOCKSET.”

Unpowered and in unactuated state

Brown Blue Yellow

DIAGRAM 4: FAIL SAFE CONVERSION* Convert Mode

Fire Door Safety Screw

a. Remove the Fire Door Safety Screw as illustrated. b. Loosen the two #2-56 screws located on the back of the strike as shown above, but do not remove them.

Finish Installing 5. Choose the appropriate faceplate for the strike as illustrated in Diagram 5 on page 3.

a

b

c. Move screws from the bottom of the hole (fail secure position) to the top hole (fail safe position) and re-tighten.

6. Connect wires from the power source to the strike.

Verify d. Verify the strike is now in the Fail Safe operation mode. If the strike still operates as Fail Secure, be sure screws are fully seated in the top position.

7. Install the electric strike unit in jamb cutout, using #12-24 x 1/2” Mounting Screws provided. 8. If horizontal adjustment is needed, see Diagram 6 on page 3.

*USING THE 4500 FOR FAIL SAFE OPERATION NEGATES FIRE RATING

DIAGRAM 5: FACEPLATE OPTIONS

DIAGRAM 6: HORIZONTAL ADJUSTMENT

DIAGRAM 1: 12V to 24V CONVERSION a

b

If horizontal adjustment is needed, 1 or 2 keeper shims can be added as illustrated below.

One Shim If adding a single shim use the #4-40 x 1/8” Keeper Shim Screws.

IF CONNECTOR IS MISSING

VIOLET

BLACK

RED/GREEN

(+ 12 VDC) (-NEG) CONNECT TOGETHER

RED

ELECTRIC STRIKE

ELECTRIC STRIKE

RED

CONNECT TOGETHER

(+ 24 VDC)

VIOLET

CONNECT TOGETHER BLACK RED/GREEN

(-NEG)

a. A Non-Handed offset faceplate is provided for use with mortise locksets. The mortise lock deadlatch should be depressed by the faceplate when the door is closed. b. A Non-Handed center-lined faceplate is provided for use with cylindrical locksets

Both Shims If adding both shims use the #4-40 x 3/16” Keeper Shim Screws.

Cutout Templates

Installation Instructions

4

4500 Series Electric Strike

Inches [mm]

JAMB CUTOUT DIMENSIONS

4500 WITH CYLINDRICAL LOCKSETS

1-1/4” [31.8]

1 2 3 4

4500 Electric Strike Body Keeper Shims & Screws (#4-40 x 1/8” and #4-40 x 3/16”) Centerlined and Non Handed Faceplate for Cylindrical Locksets Offset and Non Handed Faceplate for Mortise Locksets

5 6 7

4-7/8" [123.8]

3-5/8" [92.1]

2-1/4" [57.2]

1

4-1/8" [104.8]

CL Strike

2

4-7/8” [123.8]

3 4

1-1/4" [31.8]

5/8" [15.9]

1-3/4" [44.5]

1” [25.4]

4500 WITH MORTISE LOCKSETS CL Vertical Centerline

Mortise Lockset

#12-24 x 1/2” Mounting Screws 12 & 24 Volt Plug In Connectors Trim Enhancer & Screws

CL Lock

1-1/8" [28.6] 3-5/8” [92.1]

1

Product Components

Strike Prep

CL Vertical Centerline

Cylindrical Lock

HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com

1-1/4" [31.8]

7

SCHLAGE L9000 & YALE 8700 LOCKS ONLY

Strike Prep

CL Vertical Centerline

Mortise Lockset

5

Strike Prep 6

CL Lock

4" [101.6]

4-7/8" [123.8]

3-5/8" [92.1] 8" [203.2]

4-1/8" [104.8]

3/8" [9.5] CL Strike

1-3/4" [44.5]

3053006.002 rev B

4" [101.6]

3-5/8" [92.1]

8" [203.2]

4-7/8" [123.8] 4-1/8" [104.8]

Electrical Specifications

CL Strike

5/8" [15.9]

1-1/4" [31.8]

CL Lock

1-1/4" [31.8]

ELECTRICAL RATINGS FOR SOLENOID

Resistance in Ohms

5/8" [15.9]

1-1/4" [31.8] 1-3/4" [44.5]

1-1/4" [31.8]

© 2011 HES, Inc.

Amps

CONTINUOUS DUTY 12VDC

24VDC

12-16VAC

24VAC

50

200

50

200

.24

.12

.24-.32

.12

Solenoids are rated at +/- 10% indicated value. *10% max duty cycle (2 min. max on time)

ASSA ABLOY, the global leader in door opening solutions

INTERMITTENT DUTY*

MINIMUM WIRE GAUGE REQUIREMENTS

SOLENOID VOLTAGE 12VDC

24VDC

200 feet or less

18 gauge

20 gauge

200 - 300 feet

16 gauge

18 gauge

300 - 400 feet

14 gauge

16 gauge