5. Chapter 2 General Regulations

Report 43 Downloads 141 Views
io n

Chapter 2 General Regulations

rib ut

2.1 RESERVED 2.2 CAST IRON SOIL PIPE MARKING

rD ist

All cast iron soil pipe and fittings shall be listed and tested to comply with standards referenced in Table 3.1.3 and marked with country of origin and identification of the original manufacturer in addition to any markings required by those referenced standards.

2.3 CHANGES IN DIRECTION OF DRAINAGE PIPING 2.3.1 Uses for Drainage Fittings

Co p

y

No t

Fo

a. Changes in direction of drainage piping shall be made with long radius drainage fittings except where short radius fittings are required or permitted. 1. Short radius fittings are required to connect individual fixture trap arms to vertical drain and vent piping. 2. Short radius fittings may be used in the drain piping for an individual fixture. 3. Short radius fittings shall not be used in drain piping serving two or more fixtures. 4. Short radius fittings shall not be used at the base of stacks. 5. Short radius fittings may be used in vent piping. b. Short radius drainage fittings are those having radius or centerline dimensions that are approximately equal to or less than their nominal pipe size. The radius or centerline dimensions of long radius drainage fittings are greater than their nominal pipe size. c. Long radius drainage fittings shall not be used to connect fixture trap arms to vertical drain and vent piping. Connections to fixture vents shall be above the top weir of the fixture trap. EXCEPTION: Double wyes with 1/8 bends or 45-degree elbows that drain two lavatories into a common drain with a common vent shall be permitted. See Figures 2.3.1-A, 2.3.1-B, 2.3.1-C, and 2.3.1-D

2.3.2 Double Pattern Fittings

nl y

The uses for double pattern drainage fittings shall be the same as for single pattern fittings in Table 2.3.1. EXCEPTION: Double sanitary tees and crosses shall not be used to connect blowout fixtures, back-outlet water closets, back-to-back pressure-assisted water closets, and fixtures or appliances having pumped discharge. See Figure 2.3.2

O

2.3.3 Back-to-Back Back-Outlet Fixtures

Re ad

Stack fittings, including carriers, for back-outlet fixtures installed back-to-back shall be either the wye pattern, incorporate baffles within the drainage fitting, or otherwise be designed to prevent crossflow or mixing of the discharges from the two fixtures prior to the change in direction. See Figure 2.3.3

2.4 FITTINGS AND CONNECTIONS IN DRAINAGE SYSTEMS 2.4.1 Prohibited Fittings No running threads or saddles shall be used in the drainage or vent system. No drainage or vent piping shall be drilled, tapped, burned or welded.

2015 National Standard Plumbing Code - Illustrated

67

io n rib ut

Re ad

O

nl y

Co p

y

No t

Fo

rD ist

1. Horizontal-to-vertical changes in direction are not as critical as other changes because gravity controls the velocity in vertical drops. 2. No-hub cast iron fittings are shown. See Table 2.3.1 for fitting patterns for other drainage pipe materials. 3. Short radius fittings are permitted in piping for individual fixtures. 4. Long radius fittings are not permitted to connect fixture trap arms to vertical drain vent piping because the vent opening at the end of the trap arm will be below the weir of the trap, causing the trap to selfsiphon. Exception: Long radius fittings are permitted to drain two lavatories into a common drain with a common vent per Section 2.3.1 to permit cleaning of the common drain. Self-siphonage is not an issue with the low drain flow rates of lavatories.

68

2015 National Standard Plumbing Code - Illustrated

io n rib ut rD ist Fo No t y Co p nl y O Re ad 2015 National Standard Plumbing Code - Illustrated

69

Table 2.3.1 PERMISSIBLE DRAINAGE FITTINGS FOR CHANGES IN DIRECTION CHANGES IN DIRECTION

PIPE MATERIAL

CAST IRON NO-HUB

HORIZONTAL TO VERTICAL

long sweep short sweep wye combination wye & eighth bend fifth bend (72-deg) sixth bend (60-deg) eighth bend (45-deg) sixteenth bend (22-1/2 deg)

sanitary tee eighth bend & wye (2) combination wye & eighth bend long sweep short sweep quarter bend

eighth bend & wye combination wye & eighth bend long sweep short sweep 3” or larger quarter bend (1) short sweep (1)

drainage tee short turn 90-deg TY long turn 90-deg TY (2) 45-deg elbow or 45-deg Y branch (2) extra long turn 90-deg elbow long turn 90-deg elbow short turn 90-deg elbow

long turn 90-deg TY extra long turn 90-deg elbow long turn 90-deg elbow short turn 90-deg elbow (1) 45-deg elbow & 45-deg Y branch (1)

COPPER

DWV 90-deg long radius elbow 90-deg elbow - long radius DWV long turn T-Y DWV 45-deg Y DWV 90-deg elbow DWV 45-deg elbow

Fo

CAST IRON DRAINAGE (threaded)

extra long turn 90-deg elbow long turn 90-deg elbow long turn 45-deg elbow short turn 22-1/2 deg elbow short turn 11-1/4 deg elbow long turn 90-deg TY short turn 45-deg Y branch short turn 90-deg elbow short turn 60-deg elbow short turn 45-deg elbow

No t

DWV tee DWV 90-deg sanitary tee DWV long turn T-Y (2) 45-deg elbow & DWV 45-deg Y (2) DWV 90-deg long radius elbow 90-deg elbow - long radius

y

DWV

DWV long turn T-Y 45-deg elbow & DWV 45-deg Y DWV 90-deg long radius elbow 90-deg elbow - long radius DWV 90-deg elbow (1)

DWV 90-deg elbow

sanitary tee fixture tee long radius TY (2) 45-deg elbow & DWV 45-deg Y (2) 90-deg long turn elbow 90-deg elbow or 1/4 bend

long radius TY 45-deg elbow and 45-deg wye 90-deg long turn elbow 90-deg elbow or 1/4 bend (1)

tee sanitary tee eighth bend & wye (2) combination wye & eighth bend long sweep 90-deg 1/4 bend

eighth bend & wye (2) combination wye & eighth bend long sweep 90-degree 1/4 bend (1)

Co p

PLASTIC DWV

90-deg long turn elbow long sweep 1/4 bend 60-deg elbow or 1/6 bend 45-deg elbow or 1/8 bend 22-1/2 deg elbow or 1/16 bend long radius TY 45-deg wye

io n

rD ist

quarter bend

VERTICAL TO HORIZONTAL

rib ut

CAST IRON HUB & SPIGOT

HORIZONTAL TO HORIZONTAL

long sweep wye combination wye & eighth bend 15-degree 1/24 bend 22-1/2 degree 1/16 bend 30-degree 1/12 bend 45-degree 1/8 bend

Re ad

O

STAINLESS STEEL PUSH-FIT DWV

nl y

90-deg elbow or quarter bend

90-deg 1/4 bend

Footnotes for Table 2.3.1 (1) Short radius fittings shall not be permitted in horizontal offsets in drainage stacks and at the base of stacks. (2) (2) Long Long radius radius fittings fittings shall shall not not be be used used to to connect connect fixture fixture trap trap arms arms to to vertical vertical drain drain and and vent vent piping. piping. Exception: Long radius fittings are permitted to drain two lavatories into a common drain with a common vent per Section 2.3.1. 70 70

2012 National Standard Plumbing Code - Illustrated 2015 National Standard Plumbing Code - Illustrated

io n rib ut

rD ist

NOTES: 1. Double pattern fittings can be used in horizontal and vertical piping. 2. Long pattern fittings are not permitted to connect fixture trap arms to vertical drain and vent piping because the vent opening at the end of the trap arm will be below the weir of the trap, causing the trap to self-siphon.

O

nl y

Co p

y

No t

Fo

Figure 2.3.2 DOUBLE PATTERN DRAINAGE FITTINGS

Re ad

NOTES: 1. No-hub cast iron fittings are shown. See Table 2.3.1 for fitting patterns for other drainage pipe materials. 2. In Part B, the fixtures must be vented prior to connection to the stack. 3. In Part C, if not battery vented, the fixtures must be individually vented prior to connection to the branch drain.

Figure 2.3.3 PREVENTING CROSSFLOW BETWEEN BACK-TO-BACK BACK-OUTLET FIXTURES

2012 2015 National Standard Plumbing Code - Illustrated

71 71

2.4.2 2.4.2 Heel Heel or or Side-Inlet Side-Inlet Bends Bends

Fo

rD ist

rib ut

io n

A quarter bend bend shall shall not not be beused usedas asaadry dryvent ventwhen whenthe theinlet inletisisplaced placedinina ahorizontal horizontalposition A heel heel or or side-inlet side-inlet quarter position or anyarrangement similar arrangement pipe orproducing fittings producing a similar effect. or any similar of pipe oroffittings a similar effect. EXCEPTION: When the entire fitting is part of a dry vent arrangement systemthe theheel heelororside-inlet side-inletbend bendshall EXCEPTION: When the entire fitting is part of a dry vent arrangement system shall be acceptable. See Figures 2.4.2-A and 2.4.2-B be acceptable. See Figures 2.4.2-A and 2.4.2-B

Re ad

O

nl y

Co p

y

No t

Figure 2.4.2 - A HORIZONTAL HEEL OR SIDE INLET VENT CONNECTION

72 72

Figure 2.4.2 - B VERTICAL HEEL INLET VENT CONNECTION

2012 National Standard Plumbing Code - Illustrated 2015 National Standard Plumbing Code - Illustrated

2.4.3 Obstruction to Flow

io n

a. No fitting, connection, device, or method of installation that obstructs or retards the flow of water, wastes, sewage, or air in the drainage or venting systems in an amount greater than the normal frictional resistance to flow, shall be used unless it is indicated as acceptable in this Code. b. 4x3 closet bends and 4x3 closet flanges shall not be considered as obstructions to flow.

rib ut

Comment #1: This Section does not prohibit double hub fittings for sanitary drain pipe installations since they create no more restriction to flow that would be encountered with a hubless coupling or similar fitting. Comment #2: Failure to ream or deburr drainage piping constitutes an obstruction to flow.

2.4.4 Prohibited Joints

rD ist

Cement mortar joints are prohibited. EXCEPTION: When used for repairs and/or when used for connections to existing lines constructed with such joints.

2.5 HEALTH AND SAFETY

Fo

Where a health or safety hazard is found to exist on a premise, the owner or his agent shall be required to make such corrections as may be necessary to abate such nuisance, and bring the plumbing installation within the provisions of this Code.

2.6.1 Trenching and Bedding

No t

2.6 TRENCHING, BEDDING, TUNNELING AND BACKFILLING

O

nl y

Co p

y

a. Trenching and excavation for the installation of underground piping shall be performed in compliance with occupational safety and health requirements. Trenches shall be of sufficient width to permit proper installation of the pipe. Where shoring is required, additional allowance shall be made in the width of the trench to provide adequate clearance. b. A firm, stable, uniform bedding shall be provided under the pipe for continuous support. Bell holes shall be provided for joints in bell and spigot pipe and for other joints requiring such clearance. Blocking shall not be used to support the pipe. c. The trench bottom may provide the required bedding when adequate soil conditions exist and when excavated to the proper depth and grade. Where trenches are excavated to depths below the bottom of the pipe, bedding shall be added beneath the pipe as required. Such bedding shall be of clean sand, gravel, or similar select material that is compacted sufficiently to provide the support required under 2.6.1.b. d. Where rock is encountered in trenching, it shall be removed to a depth of not less than 6 inches below the bottom of the pipe and bedding shall be added as required under 2.6.1.c. The pipe shall not rest on rock at any point, including joints. Required under Section 2.6.1.c. See Figures 2.6.1-A and 2.6.1-B. Also Section 2.6.2, 2.6.3, and 2.6.4

Re ad

2.6.2 Side-fill

The haunch areas adjacent to the pipe between the bottom of the pipe and its horizontal centerline shall be filled with a clean coarse-grain material such as sand, gravel, or soil. Such side-fill shall be placed by hand, extending to the sides of the trench, and be compacted to provide lateral support for the pipe. See Figures 2.6.1-A and 2.6.1-B

2015 National Standard Plumbing Code - Illustrated

73

io n rib ut rD ist

NOTES: 1. The soil under the pipe must be stable. Unstable bedding may damage the pipe, fittings, or joints when settlement occurs. 2. The side-fill should be shoveled under the pipe to make sure that there are no voids in the side-fill.

nl y

Co p

y

No t

Fo

Figure 2.6.1 - A UNDERGROUND PIPING BEDDED ON SOIL

Re ad

O

NOTES: 1. Unstable bedding may damage the pipe, fittings, or joints when settlement occurs. 2. The side-fill should be shoveled under the pipe to make sure that there are no voids in the side-fill.

74

Figure 2.6.1 - B UNDERGROUND PIPING BEDDED ON SAND OR GRAVEL

2012 2015 National National Standard Standard Plumbing Plumbing Code Code -- Illustrated Illustrated

2.6.3 Initial Backfill

No t

Fo

rD ist

rib ut

io n

a. Backfill material shall be sand, gravel, or loose soil that is free of rocks and debris. Maximum particle size shall be 1-1/2 inches. b. The side-fill adjacent to the pipe shall be backfilled, tamped, and compacted to the top of the pipe. 2.6.3 Initial Backfill c. After the side-fill is backfilled, the trench shall be backfilled in not more than 6-inch layers, each After installation of the side-fill, the trench shall be backfilled to a level not less than 2 feet above the top tamped and compacted, to a level not less than 2 feet above the top of the pipe. of the pipe. Backfill material shall be sand, gravel, or loose soil that is free of rocks and debris. Maximum d. Heavy equipment shall not be used for the initial backfill. particle size shall be 1-1/2 inches. Backfill shall be placed in not more than 6-inch layers, each tamped and See Figure Heavy 2.6.3 compacting equipment shall not be used for the initial backfill. See Figure 2.6.3 compacted.

Co p

y

NOTE: 1. The side-fill adjacent to the pipe must be backfilled and tamped to the top of the pipe. 2. The initial backfill must be placed in 6” tamped layers. The use of heavy compacting equipment is prohibited. 3. The initial backfill material must be sand, gravel, or loose soil from the excavation that is free from rocks and debris. Broken concrete, frozen earth, and other solid materials may damage the pipe from point loads. 4. After the pipe is covered with 2 feet of tamped initial backfill, the final backfill to grade can be compacted with heavy equipment.

nl y

Figure 2.6.3 TYPICAL BACKFILLING PROCEDURE

O

2.6.4 Final Backfill 2.6.4 Final Backfill

The trench shall be backfilled from the top of the compacted initial backfill to finish grade using suitable The trench shall compacting be backfilledequipment from the top compacted initial backfillSee to Figure finish grade material. Heavy mayofbethe used for the final backfill. 2.6.3using suitable material. Heavy compacting equipment may be used for the final backfill. See Figure 2.6.3

Re ad

2.6.5 Tunneling 2.6.5 Tunneling

When pipe is installed in a dug or bored earth tunnel, the space around the pipe between the pipe and the When is installed dug or bored earth tunnel, theconcrete space around the When pipe between the pipe and wall ofpipe the tunnel shall in beacompletely filled with packed or grout. pipe is installed in a the wall of the tunnel shall be filled around with packed concrete or grout. When is installed a jacked-in-place conduit or completely sleeve, the space the pipe between the pipe and pipe the inside of the in conduit or jacked-in-place conduit or sleeve, the space around the pipe between the pipe and the inside of the conduit sleeve shall be sealed in an approved manner in accordance with Section 2.12.d. or sleeve shall be sealed in an approved manner in accordance with Section 2.12.d.

2015 National Standard Plumbing Code - Illustrated

75

2.6.6 Underground Plastic Pipe

rD ist

rib ut

io n

a. Underground plastic pipe shall be installed in accordance with the requirements of Section 2.6. EXCEPTIONS: (1) The maximum particle size in the side-fill and initial backfill shall be not more than 1/2-inch for pipe 6" size and smaller, and 3/4-inch for pipe 8" and larger. (2) For water service piping, refer to ASTM D2774, Standard Practice for Underground Installation of Thermoplastic Pressure Piping. (3) For gravity-flow drainage pipe, refer to ASTM D2321, Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-flow Applications. b. An insulated copper tracer wire or other approved conductor shall be installed adjacent to underground non-metallic water service piping and non-metallic force mains, to facilitate locating the piping. One end shall be brought above ground inside or outside the building wall. The tracer wire for the water service shall originate at the curb valve required in Section 10.12.1. The tracer wire for the force main shall originate at the final point of disposal. The tracer wire shall not be less than 18 AWG insulated. The insulation shall not be yellow in color.

2.6.7 Underground Copper Piping

Fo

Underground copper piping shall be installed in accordance with the requirements of Section 2.6. EXCEPTION: The maximum particle size in the side-fill and initial backfill shall be not more than 1/2-inch for pipe 6" size and smaller, and 3/4-inch for pipe 8" and larger.

2.6.8 Safety Precautions

No t

Rules and regulations pertaining to safety and protection of workers, other persons in the vicinity, and neighboring property shall be adhered to where trenching or similar operations are being conducted.

2.6.9 Supervision

y

Where excavation, bedding or backfilling are performed by persons other than the installer of the underground piping, the pipe installer shall supervise the bedding, side-fill, and initial backfill, and shall be responsible for its conformance to this Code.

Co p

2.6.10 Trenchless Pipe Replacement Systems

nl y

Trenchless replacement of water and sewer piping shall be performed using equipment and procedures recommended by the equipment manufacturer. Where underground piping beneath paved surfaces or concrete floor slabs is replaced by this method, the manufacturer’s recommendations for the specific conditions shall be used. Approved mechanical couplings shall be used to make the connections between new and existing piping.

O

Comment: When piping beneath paving or concrete floors is replaced by the trenchless method, there must be sufficient distance above the pipe to prevent cracking the paving or floor slab when the pipe being replaced bursts.

Re ad

2.7 SAFETY

Any part of a building or premise that is changed, altered, or required to be replaced as a result of the installation, alteration, renovation, or replacement of a plumbing system, or any part thereof, shall be left in a safe, nonhazardous condition.

2.8 INSTALLATION PRACTICES Plumbing systems shall be installed in a manner conforming to this Code and industry installation standards.

76

2015 National Standard Plumbing Code - Illustrated

2.9 PROTECTION OF PIPES 2.9.1 From Breakage

io n

Pipes passing under or through foundation walls shall be protected from breakage.

2.9.2 From Corrosion

rib ut

Pipe subject to corrosion by passing through or under corrosive fill, such as, but not limited to, cinders, concrete, or other corrosive material, shall be protected against external corrosion by protective coating, wrapping, or other means that will resist such corrosion.

rD ist

Comment #1: Soil samples should be taken to assure that the soil will not corrode the pipe. Wrappings and coatings reduce contact corrosion, but cathodic protection may be required where stray electric currents exist.

Comment #2: Job site debris should not be allowed in the backfill for piping trenches. Material such as metal cans, metal studs, and gypsum board may chemically react with some types of pipe.

2.9.3 From Weakened Structure

Fo

Any structural member weakened or impaired by cutting, notching, or otherwise, shall be reinforced, repaired, or replaced, so as to be left in a safe structural condition in accordance with the requirements of the applicable building code.

2.9.4 From Nails, Screws, and Other Fasteners

y

No t

a. Plastic and copper piping run through framing members (wood or metal) to within one inch of the edge of the framing shall be protected by steel nail plates not thinner than 16 gauge. Where such piping penetrates top plates or sole plates of the framing, the nail plate shall extend at least two inches below top plates and two inches above sole plates. b. Where plastic and copper piping runs through metal framing members, it shall be protected from abrasion caused by expansion and contraction of the piping or movement of the framing.

2.10.1 General

Co p

2.10 EXCLUSION OF MATERIALS DETRIMENTAL TO THE SEWAGE SYSTEM

nl y

No material shall be deposited into a building drainage system or sewer that would or could either obstruct, damage, or overload such system; that could interfere with the normal operation of sewage treatment processes; or that could be hazardous to people or property. This provision shall not prohibit the installation of special waste systems when approved by the Authority Having Jurisdiction.

2.10.2 Industrial Wastes

Re ad

O

Waste products from manufacturing or industrial operations shall not be introduced into the public sewer system until it has been determined by the Authority Having Jurisdiction that the introduction thereof will not cause damage to the public sewer system or interfere with the functioning of the sewage treatment plant.

Comment: Where industrial wastes will be created, the facility should provide the following information to the Authority Having Jurisdiction for the sewerage system: (1) the quantity of water and waste material that will be discharged into the sewer system, (2) the industrial processes that create the waste, (3) the composition and concentration of the chemicals in the waste, (4) the water supply demand for the facility, and (5) the intended design of the pre-treatment or neutralizing system for the wastes prior to its discharge into the sewer system.

2015 National Standard Plumbing Code - Illustrated

77

2.11 PIPING MATERIALS EXPOSED WITHIN PLENUMS 2.11 MATERIALS EXPOSED WITHIN PLENUMS

All piping materials exposed within plenums shall comply with the provisions of other applicable Codes. All piping materials exposed within plenums shall comply with the provisions of other applicable Codes.

2.12 SLEEVES 2.12 SLEEVES FOR PIPING

y

No t

Fo

rD ist

rib ut

io n

a. All All piping piping passing passing through through concrete concrete walls, walls, floors, slabs, and masonry walls shall be provided with sleeves for a. protection. protection. EXCEPTION: Sleeves shall required pipes passing through drilled bored holes. Such holes shall EXCEPTION: Sleeves shall notnot be be required forfor pipes passing through drilled or or bored holes. Such holes shall provide 1/2 inch minimum clearance around the pipe and any thermal insulation. provide b. Sleeves shall be sized so there is a minimum of 1/2-inch clearance around the pipe and/or insulation. b. c. Piping Piping through through concrete concrete or or masonry masonry walls walls shall not be subject to any load from building construction. c. d. The annular space between sleeves and pipes shall be filled or tightly caulked with coal tar, asphaltum d. compound, lead, or other material found equally effective and approved compound, approved as as such such by by the theAuthority Authority Having Having Jurisdiction. Jurisdiction. e. All All penetrations penetrations of of construction construction required required to to have have a fire resistance rating shall be protected in accordance with e. the applicable applicable building regulations. the See See Figure Figure 2.12 2.12

Co p

NOTES: 1. The sleeve must be sealed where necessary to prevent the entrance of ground water into the building.

nl y

Figure 2.12 A PIPE SLEEVE THROUGH A FOUNDATION WALL

2.13 OPENINGS FOR PIPING

O

a. Openings for plumbing piping shall be sealed as required to maintain the integrity of the wall, floor, ceiling, 2.13 OPENINGS FOR PIPING

Re ad

or roof that has for been penetrated. a. Openings plumbing piping shall be sealed as required to maintain the integrity of the wall, floor, ceiling, b. Collars or escutcheon plates shall be provided to cover the openings around pipes where the piping penetrates or roof that has been penetrated. walls, floors, or or escutcheon ceilings in finished areas are exposed tothe view. b. Collars plates shall bethat provided to cover openings around pipes where the piping penetrates walls, floors, or ceilings in finished areas that are exposed to view.

2.14 USED MATERIAL OR EQUIPMENT

2.14plumbing USED MATERIAL ORthat EQUIPMENT Used material or equipment does not conform to the standards and regulations set forth in this Code shall be installed in any plumbing system. Usednot plumbing material or equipment that does not conform to the standards and regulations set forth in this Code shall not be installed in any plumbing system. 78

2012 National Standard Plumbing Code - Illustrated

78

2015 National Standard Plumbing Code - Illustrated

2.15 CONDEMNED EQUIPMENT Any plumbing equipment condemned by the Authority Having Jurisdiction because of wear, damage, defects or sanitary hazards, shall not be used for plumbing purposes.

io n

2.16 FREEZING OR OVERHEATING

Re ad

O

nl y

Co p

y

No t

Fo

rD ist

rib ut

a. The plumbing system shall be protected from freezing or overheating. The following conditions shall be met: 1. Exterior water piping shall be installed below recorded frost lines. Minimum earth cover above the top of inches. the pipe shall be 2. Minimum earth cover above the top of exterior building drains and building sewers that connect to public inches. Minimum earth cover above the top of exterior building drains and sewage systems shall be inches. building sewers that connect to individual sewage disposal systems shall be 3. In systems that are used seasonally, water piping shall have provisions to be drained. 4. Piping shall be installed so that the contents will not be heated due to close proximity to any heat source or from direct solar radiation. 5. In areas with seasonal freezing outdoor temperatures, all drain piping and water piping installed in exterior walls, attics, and other areas exposed to outdoor temperatures shall be protected from freezing. In heated spaces, the piping shall be installed on the heated side of the building insulation. See Figure 2.16

2015 National Standard Plumbing Code - Illustrated

79

2.17 2.17 PROTECTING PROTECTING FOOTINGS FOOTINGS

rD ist

rib ut

io n

Trenching parallel to and below the bottom of footings or walls shall not penetrate a 45° plane extending Trenching parallel to and below the bottom of footings or walls shall not penetrate a 45° plane extending outward outward from the bottom corner of the footing or wall, unless the soil type is approved by the Authority Having from the bottom corner of the footing or wall, unless the soil type is approved by the Authority Having Jurisdiction Jurisdiction for a different angle of repose. See Figure 2.17 for a different angle of repose. See Figure 2.17

No t

Fo

NOTES: 1. Check the project design documents to verify that a 45 degree angle of repose is permissible. 2. Consult the project structural engineer if conditions dictate that excavations must be closer than 45 degrees from the bottom edge of footings.

y

Figure 2.17 PROTECTING STRUCTURAL FOOTINGS FROM BEING UNDERMINED

Co p

2.18 CONNECTIONS TO PLUMBING SYSTEMS REQUIRED 2.18 CONNECTIONS TO PLUMBING SYSTEMS REQUIRED Every plumbing fixture, drain, appliance, or appurtenance thereto that is to receive or discharge any liquid waste or sewage shall discharge to the sanitary drainage system of the building in accordance with the requirements of ge any liquid waste this Code. or sewage shall discharge to the sanitary drainage system of the building in accordance with the requirements of

Re ad

O

nl y

this Code.

80 80

2012 2015 National National Standard Standard Plumbing Plumbing Code Code -- Illustrated Illustrated

2.19 CONNECTION TO WATER AND SEWER SYSTEMS 2.19 CONNECTION TO WATER AND SEWER SYSTEMS 2.19.1 Availability of Public Water and Sewer 2.19.1 Availability of Public Water and Sewer

Fo

rD ist

rib ut

io n

The water distribution and drainage systems of any building in which plumbing fixtures are installed shall The water distribution and drainage systems of any building in which plumbing fixtures are installed shall be connected to a public water supply and sewer system respectively if the public water supply and/or public be connected to a public water supply and sewer system respectively if the public water supply and/or public feet of any property line on the premises, or other reasonable distance as determined sewer is within sewer is within ______ feet of any property line on the premises, or other reasonable distance as determined by bythe theAuthority Authority Having Jurisdiction. Figure 2.19.1 Having Jurisdiction. SeeSee Figure 2.19.1

y

No t

NOTES: 1. Refer to the adopting ordinance for this Plumbing Code to determine the distance from which properties must be connected to public water and sewer systems. 2. Connections to public water and sewer systems are more desirable than private systems, from the standpoint of public health and convenience.

Co p

Figure 2.19.1 REQUIRED CONNECTION OF PROPERTIES TO PUBLIC WATER AND SEWER SYSTEMS

2.19.2Private PrivateSystems Systems 2.19.2

O

nl y

Where Whereeither eithera apublic publicwater watersupply supplyororsewer sewersystem, system,ororboth, both,are arenot notavailable, available,aa private private individual individual water water supply supplyororindividual individualsewage sewagedisposal disposalsystem, system,ororboth, both,shall shallbe beprovided, provided,and andthe the water water distribution distribution system and installation anddrainage drainagesystem systemshall shallbe beconnected connectedthereto. thereto.Such Such private private systems systems shall shall meet the standards for installation and and 17.) 17.) anduse useestablished establishedbybythe theHealth HealthDepartment Departmentor orother otheragency agency having having jurisdiction. jurisdiction. (See Chapters 16 and SeeFigure Figure2.19.1. 2.19.1.Also Alsothe thedefinition definitionofof“Private “PrivateSewage SewageDisposal DisposalSystem” System”and and “Private “PrivateWater Water Supply”. Supply”. See

Re ad

Comment: Plumbing in buildings connected to private water or sewage systems must comply with in buildings connected to private Having water orJurisdiction. sewage systems must comply with all allComment: applicablePlumbing requirements of this Code or the Authority applicable requirements of this Code or the Authority Having Jurisdiction.

2.20 WASHROOM & TOILET ROOM REQUIREMENTS 2.20 REQUIREMENTS FOR WASHROOMS, TOILET ROOMS & BATHROOMS 2.20.1 Light and Ventilation 2.20.1 and Ventilation Light Light and ventilation shall be provided as required by other applicable codes. Light and ventilation shall be provided as required by other applicable codes.

2012 National Standard Plumbing Code - Illustrated

2015 National Standard Plumbing Code - Illustrated

81

81

2.20.2 Location of Piping and Fixtures 2.20.2 Location of Piping and Fixtures

Piping, fixtures, or equipment shall not be located in such a manner as to interfere with the normal operation Piping, fixtures, or equipment shall not bes.located in such a manner as to interfere with the normal operation of windows, doors, or other exit opening of windows, doors, or other exit openings.

io n

2.21 PIPING MEASUREMENTS 2.21 PIPING MEASUREMENTS

Except Except where where otherwise otherwise specified specified in in this this Code, Code, all all measurements measurements shall shall be be made made to to the the center center lines lines of of the the pipes. pipes.

rib ut

2.22 2.22 WATER WATER CLOSET CLOSET CONNECTIONS CONNECTIONS

No t

Fo

rD ist

a. Three-inch Three-inch bends bends may may be be used used on on water water closets closets or or similar similar connections connections provided provided aa 4-inch 4-inch by by 3-inch 3-inch flange flange is is a. installed to to receive receive the the closet closet fixture fixture horn. horn. installed b. Four-inch by three-inch closet bends shall be be permitted. permitted. b. Four-inch by three-inch closet bends shall See Figure See Figure 2.22 2.22

y

NOTES: 1. Reducing fixture drains for water closets from 4” to 3” is permissible.

2.23 2.23 DEAD DEAD ENDS ENDS

Co p

Figure 2.22 WATER CLOSET DRAIN CONNECTIONS

Re ad

O

nl y

a. In the installation or removal of any part of a drainage or vent system, dead ends, as defined in Section 1.2, 2.23.1 Drain Piping shall be avoided. EXCEPTION: Where necessary to extend a cleanout so as to be accessible. a. In thefor installation of drain piping, ends shall notends be permitted. b. Rough-ins future fixtures shall not bedead considered dead if the piping is accessible and can be cleared EXCEPTION: Piping to make cleanouts accessible. of any blockages when the future fixtures are installed. See the definition of “Dead End”. See Figure 5.4.5 - B b. Rough-ins for future fixtures shall not be considered dead ends. 2.24 TOILET FACILITIES FOR CONSTRUCTION c. If an existing fixture, appliance, or equipment is removed, anyWORKERS open ends in the drain piping shall be capped or plugged watertight. Suitable toilet facilities shall be provided and maintained in a sanitary condition for the use by workers during construction. Non-sewer 2.23.2 Vent Pipingtype toilet facilities for construction workers shall conform to ANSI Z4.3. In the installation, removal, or disconnecting of any vent piping, any open ends shall be capped or plugged watertight. Dead ends that are not self-draining shall not be permitted.

2.24 TOILET FACILITIES FOR CONSTRUCTION WORKERS Suitable toilet facilities shall be provided and maintained in a sanitary condition for the use by workers during 82 2012 National Standard Plumbing construction. Non-sewer type toilet facilities for construction workers shall conform to ANSI Z4.3.Code - Illustrated 82

2015 National Standard Plumbing Code - Illustrated

2.25 FOOD HANDLING ESTABLISHMENTS AND FOOD HANDLING AREAS WITHIN BUILDINGS 2.25.1 General Area Protection

nl y

Co p

y

No t

Fo

rD ist

rib ut

io n

a. All food and drink, while being stored, prepared, displayed, served, or sold in food handling establishments and food handling areas in buildings shall be protected against contamination from drainage overflow, flooding, backflow, or leakage. EXCEPTION: Seating areas. b. Food or drink shall not be stored, prepared or displayed beneath overhead drain or vent piping unless such pipes are protected against leakage or condensation reaching the food or drink. c. In new or remodeled construction, drain and vent piping shall not be located above food preparation, storage, display, or serving areas where possible. EXCEPTION: Seating areas. d. Where drain and vent piping must be installed above such areas, the amount of piping and the number of pipe joints shall be minimized. e. Where plumbing fixtures are located above such areas, all openings through floors, including those for piping, cleanouts, and other plumbing work shall be provided with sleeves securely bonded to the floor construction and projecting not less than 3/4 inches above the top of the finished floor with the space between the penetration and the sleeve sealed waterproof. See Figure 2.25 - A f. Except for bathtubs or whirlpool baths, plumbing fixtures installed on the floor above such areas shall be the wall-mounted or back-outlet type. g. Floor drains and shower drains installed on the floor above such areas shall be flashed and equipped with integral seepage pans. h. The waste and overflow connections for bathtubs and whirlpool baths installed on the floor above such areas shall be made above the floor and piped through a single sleeved floor opening to the fixture trap below the floor. No floor openings, other than the sleeve for the waste pipe to the fixture trap, and a sleeved opening for a vent pipe, if required, shall be permitted above such areas. Pipes shall be sealed watertight to their sleeves. i. Drain and vent piping above such areas shall be subjected to a standing water test of not less than 25 feet or 10 psig. j. Piping subject to operation at temperatures that may cause condensation on the external surfaces of the pipe shall be thermally insulated to prevent condensation. k. Where drain and vent piping is installed above finished ceilings in such areas, the ceiling panels shall be the removable type or sufficient access panels shall be provided to permit complete inspection of the piping.

O

Comment: The seating areas in restaurants, cafeterias, and other dining areas are not subject to the requirements of Section 2.25.1.

2.25.2 Food Service Equipment and Fixtures

Re ad

a. All food and/or drink service equipment, including sinks, dishwashers, ice machines, brewers, and dispensers, shall be indirectly discharge to the drainage system through an air gap or air break in accordance with Chapter 9. EXCEPTION: If a properly vented floor drain is installed adjacent to a food service fixture that is properly trapped and vented, the food service fixture shall be permitted to connect directly to the drainage system on the sewer side of the floor drain. b. Where multi-compartment sinks are drained indirectly, each compartment shall discharge separately into a sanitary floor sink that is capable of draining all of the compartments simultaneously.

2015 National Standard Plumbing Code - Illustrated

83

2.25.3 Exposed Food Products

io n

Wherever unwrapped or unpacked food products are prepared, displayed, or sold for human consumption, all fixtures, equipment, devices, utensils, tableware, and apparatus involved in the food service process shall be protected against backflow, cross-connection, and flooding from the drainage system by indirect connections to the drainage system through air gaps in accordance with Chapter 9.

2.25.3 Food Equipment Products 2.25.4Exposed Food Display

rib ut

Wherever unwrapped or unpacked aredrink prepared, displayed, or equipment sold for human consumption, Display cases for refrigerated and food frozenproducts food and products and other and appliances that all fixtures, equipment, devices, tableware, and apparatus involved in the food service process produce clear water waste shall utensils, be indirectly connected to the drainage system through an air gap or air break shall be protected against backflow, cross-connection, and flooding from the drainage system by indirect in accordance with Chapter 9. connections to the drainage system through air gaps in accordance with Chapter 9.

2.25.5 Sanitary Floor Sinks 2.25.4 FoodinDisplay Equipment Floor sinks food handling areas shall be of the sanitary design with smooth, corrosion-resistant surfaces

rD ist

that cancases be readily cleaned. and frozen food and drink products and other equipment and appliances that Display for refrigerated a. Where floorshall sinksbeserve as waste receptorstointhefood handing areas,through they shall notgap be located produce clearsanitary water waste indirectly connected drainage system an air or air where subject to foot traffic or other loads on their grates, if provided. break in accordance with Chapter 9. b. Sanitary floor sinks shall comply with ASME A112.6.7 and shall be of the sanitary design with smooth, 2.25.5 Floor Sinkssurfaces that can be readily cleaned. They shall include a dome strainer over the outlet corrosion-resistant opening to in prevent clogging areas the drain sediment bucket to collect Floor sinks food handling shallorbea of the sanitary design with solids. smooth, corrosion-resistant surfaces

nl y

Co p

y

No t

Fo

that can be readily cleaned.

O

NOTES: 1. The 3/4” extended sleeve prevents spillage on the floor above from leaking down into the food handling area and contaminating the food products.

Re ad

Figure 2.25 - A A PIPE PENETRATION OF A FLOOR ABOVE A FOOD HANDLING AREA

2.25.6 Vacuum Condensate Drainage Systems

a. Vacuum condensate drainage systems to lift condensate from refrigerated food and drink display cases shall be designed by the manufacturer specifically for supermarkets and similar applications. Systems shall comply with the requirements of this Code for protection against backflow, cross connections, and contamination of food and drink products. b. Systems shall be installed in accordance with the manufacturer’s requirements for piping material, arrangement of the piping and equipment, pipe sizing, and pipe support. Drain pipe connections to - Illustrated 84 2015 National Standard Plumbing Code display cases shall include swing check valves and isolation valves when recommended by the system manufacturer. c. The waste discharge from vacuum condensate drainage systems shall be connected to the building

io n rib ut rD ist Fo

No t

NOTES: 1. All pipe penetrations through the floor above must have extended pipe sleeves. See Figure 2.25 - A. The number of floor penetrations should be minimized. 2. Floor-outlet water closets are not permitted above a food handling area. 3. Bathtubs and showers must have above-the-floor waste outlets with piping extended to a point where an extended pipe sleeve can be installed. 4. Piping run in a ceiling space above a food handling area must be fully accessible.

Co p

y

Figure 2.25 - B PLUMBING FIXTURES ABOVE A FOOD HANDLING AREA

2.262.25.6 ELEVATOR SUMP PITS Vacuum Condensate Drainage Systems

Re ad

O

nl y

a. Vacuum condensate drainage systems to lift condensate from refrigerated food and drink display Provisions for draining elevator sump pits shall be in accordance with the requirements of the Adopting Agency. cases shall be designed by the manufacturer specifically for supermarkets and similar applications. Systems comply with the requirements of this Code for protection against backflow, cross connections, and 2.27shall IDENTIFICATION OF SYSTEM PIPING contamination of food and drink products. shall be installed with the manufacturer’s b. Systems for piping material, of a. Where plumbing system piping in is accordance identified, the labeling shall complyrequirements with the applicable requirements arrangement of the piping and equipment, pipe sizing, and pipe support. Drain pipe connections to display ASME A13.1 or its equivalent. cases shall include swing check valves and isolation valves when recommended by the system manufacturer. b. Piping for non-potable water used for typical potable water applications shall be identified in accordance c. The10.21. waste discharge from vacuum condensate drainage systems shall be connected to the building with Section gravity drainage system through an air gap or air break. The gravity drainage system shall be sized for the waste MULTIPURPOSE discharge rate from the vacuum system. 2.28maximum NFPA 13D RESIDENTIAL FIRE SPRINKLER SYSTEMS Where approved by the Authority Having Jurisdiction, NFPA 13D multipurpose residential fire sprinkler systems that provide both domestic cold water distribution and fire sprinkler protection for one- and two-family dwellings with a combination piping system shall comply with Section 10.20.

2.29 RADON GAS SYSTEMS Radon systems and their components shall be designed to comply with the laws, ordinances, codes, and regulations of relevant jurisdictional authorities, including applicable mechanical, electrical, building, plumbing, energy, and fire prevention codes.Code - Illustrated 2015 National Standard Plumbing 85 2012 National Standard Plumbing Code - Illustrated

85

2.26 REQUIREMENTS FOR ELEVATORS 2.26.1 General

rib ut

io n

a. The plumbing requirements for elevator shafts, pits, and equipment rooms shall be in accordance with the applicable elevator code. b. Piping shall not be installed in elevator machine rooms that is prohibited by the applicable elevator code. c. Foundation drains and other sources of ground water shall not be connected to elevator pits. d. Where elevators have Phase II firefighter override, drainage shall be provided for their elevator pit.

2.26.2 Where Elevator Pit Drainage is Provided

No t

Fo

rD ist

a. Drainage from elevator pit drains or pumps shall discharge to an approved location. Such drainage shall not be connected to storm drain piping. b. Where the drainage discharge is outdoors, the location shall be approved by the Authority Having Jurisdiction and be marked “ELEVATOR PIT DISCHARGE”. c. An indoor discharge from elevator pit drains or pumps shall extend from the pit to an indirect waste receptor or be connected to gravity drain piping indirectly through an air gap or air break. The point of discharge shall be marked “ELEVATOR PIT DISCHARGE”. d. The controls for sump pumps serving hydraulic elevators shall include automatic oil sensing with pump cutoff or there shall be oil separation for pump operation. e. Sump pits for drains or pumps shall have a removable or operable grate-type cover that is secured and level with the elevator pit floor. f. The discharge piping from elevator sump pumps shall include a check valve and a manual quarter-turn shutoff valve with visual indication of its full open and full closed positions from within the elevator pit. g. Where elevators have Phase II firefighter override, the design flow capacity of the required drains or pumps shall be not less than 3000 gph (50 gpm) per elevator. Pumps for hydraulic elevators shall have oil separation for pump operation.

y

2.27 IDENTIFICATION OF SYSTEM PIPING

Co p

a. Where plumbing system piping is identified, the labeling shall comply with the applicable requirements of ASME A13.1 or its equivalent. b. Piping for non-potable water used for typical potable water applications shall be identified in accordance with Section 10.21.

2.28 NFPA 13D MULTIPURPOSE RESIDENTIAL FIRE SPRINKLER SYSTEMS

nl y

Where approved by the Authority Having Jurisdiction, NFPA 13D multipurpose residential fire sprinkler systems that provide both domestic cold water distribution and fire sprinkler protection for one- and two-family dwellings with a combination piping system shall comply with Section 10.20.

O

2.29 RADON GAS SYSTEMS

Re ad

Radon systems and their components shall be designed to comply with the laws, ordinances, codes, and regulations of relevant jurisdictional authorities, including applicable mechanical, electrical, building, plumbing, energy, and fire prevention codes.

2.30 SWIMMING POOLS, WADING POOLS, SPAS, AND HOT TUBS a. The water supply shall be protected from backflow by a fixed air gap above the overflow level of the pool, spa, or hot tub, or by an approved backflow preventer. Where the water supply connection is below the overflow level, an ASSE 1013 reduced pressure principle backflow preventer shall be provided. b. The drainage from swimming pools and wading pools shall be indirect through an air gap in accordance with Section 9.1.11.

86

2015 National Standard Plumbing Code - Illustrated