Product Installation Document
1 Overview These switching power supplies/distribution units convert 115 VAC input into 6 VDC, 12 VDC, or 24 VDC @ 2.5 A or 4.0 A of continuous supply current and distribute it using individually fused or PTC outputs. These general-purpose power supplies have a wide range of applications for access control, security and CCTV systems that require additional power. For convenient installation, they come completely assembled with a steel enclosure, transformer, and connecting hardware.
2 Product Contents All hardware is mounted in steel enclosure (see dimensions below) and includes a HT28100 transformer and a single power supply board. Product
Power Supply Board
Distribution Board
Quantity
HPS3
HPD4
1
HPV3DC4ULCB
HPS3
HPD4CB
1
HPV5DC8UL
HPS5
HPD8
1
HPV5DC8ULCB
HPS5
HPD8CB
1
HPV5DC16UL
HPS5
HPD8
2
HPV5DC16ULCB
HPS5
HPD8CB
2
HPV3DC4UL
3 Features •
Designed for quick installation.
•
Power ON/OFF switch.
•
Filtered and electronically regulated output.
•
Individually protected fused or PTC outputs.
•
Diagnostic LEDs for quick troubleshooting.
•
Transformer has built-in thermal protection.
•
Vented enclosure with hinged door and five convenient knockouts.
•
AC line cord and terminal block fuse protection included.
•
Unit maintains camera synchronization.
4 Specifications •
UL-listed to UL-2044 Commercial CCTV Equipment.
•
Maximum temperature range: 32° F to 120° F (0° C to 49° C); indoor use only.
•
Enclosure dimensions: 10" H x 11.5" W x 4.875" D (cm: 25.4 H x 29.21 W x 12.38 D).
•
Input: 115V, 60 Hz, 1.0 A.
•
Output voltage: switch selectable 6/12/24 VDC.
•
Output current: see “Voltage Output Table/ Maximum Total Output Current” on page 2.
4.1 Voltage Output Table/ Maximum Total Output Current Main output voltage is switch selectable. Note the maximum output current at each output voltage. Switch selector is located on HPS3 and HPS5 power supply board. See Figure 1 below Product HPV3DC4UL
6 VDC
12 VDC
24 VDC
2.5 A
2.5 A
2.5 A
HPV3DC4ULCB
2.5 A
2.5 A
2.5 A
HPV5DC8UL
4.0 A
4.0 A
2.5 A
HPV5DC8ULCB
4.0 A
4.0 A
2.5 A
HPV5DC16UL
4.0 A
4.0 A
2.5 A
HPV5DC16ULCB
4.0 A
4.0 A
2.5 A
DC LED (red)
DC LED (red)
TB1
TB1
DC+
DC+
DC-
DC-
AC
AC
AC
AC
AC LED (green)
AC LED (green)
HPS3
HPS5
2
SW 1.2
1
SW 1.1
ON Configuration (Shown in 12 V position) SW 1 (Slide right to turn on)
SW 2 (Slide right to turn on)
24 VDC
Off
On
12 VDC
Off
Off
6 VDC
On
Off
Output
Figure 1 Voltage Selection Diagrams
2
HPV3DC4UL(CB), HPV5DC8UL(CB), HPV5DC16UL(CB) Product Installation Document — P/N 53446:B2 6/18/13
4.2 LED Diagnostic Table HPS3/HPS5 AC Power (Green LED)
HPS3/HPS5 DC Power (Red LED)
HPD4/HPD8 Output Power (Green LEDs)
Status
ON
ON
ON (All)
OFF
OFF
OFF (All)
Normal operation. Loss of AC/AC main fuse blown.
ON
OFF
OFF (All)
No DC output. Overload present.
ON
ON
OFF (One or more)
Blown fuse(s) on HPD4/8.
4.3 Fuse Replacement Table !
CAUTION:RISK OF EQUIPMENT DAMAGE! TO REDUCE THE RISK OF FIRE, REPLACE ONLY WITH FUSES OF THE SAME TYPE AND RATING.
Fuse
Rating
AC Mains Terminal Block
2.0 A, 250 V, 5 x 20mm cartridge.
HPD Main Secondary Fuse (F9)
5.0 A, 32 V, standard automotive (tan).
HPD-4 Outputs (F1-F4)
3.0 A, 32 V, standard automotive (violet)
HPD-8 Outputs (F1-F8)
3.0 A, 32 V, standard automotive (violet)
5 Installation Instructions 1.
Unpack product. Do not discard packaging material until installation is complete.
2.
Pre-drill holes where enclosure is to be mounted. Choose a vertical surface strong enough to support the full weight of the assembly. Select a mounting location in an area without excessive moisture; for indoor installation only.
3.
Secure enclosure to the desired location using the appropriate sized fasteners.
4.
Configure the power supply using DIP switches to select output voltage required (refer to Figure 1).
5.
Disconnect power to the branch circuit to which the product will be connected.
6.
Place SW1 on the distribution board/boards (HPD4/HPD8) in the off position.
7.
Connect incoming AC power (115 V, 60 Hz): – Hot (black) to terminal marked “L”. – Neutral (white) to terminal marked “N”. – Ground to terminal marked “G”.
8.
Use the knockout in bottom of cabinet for 115 VAC wiring. Route the 115 VAC wiring at least 1/4" from (low voltage) wiring.
9.
Keep a 1/4" (0.635 cm) separation between power-limited wiring and non-power-limited wiring. Use separate knockouts for power limited wiring.
10. Connect CCTV cameras (or other external loads) to appropriate terminals: Connect circuit #1 to terminals marked “1+” and “–”. Connect circuit #2 to terminals marked “2+” and “–”. Continue to connect the remaining circuits, carefully observing polarity. Terminals marked with “–” are of the same polarity. 11. Power the branch circuit and slide SW1 to the ON position. All LEDs should illuminate. 12. To avoid potential damage, verify that out put voltage and load current does not exceed output limitations. 13. Upon completion of wiring, secure cabinet door with screws supplied, to prevent access by unauthorized person.
HPV3DC4UL(CB), HPV5DC8UL(CB), HPV5DC16UL(CB) Product Installation Document — P/N 53446:B2 6/18/13
3
HPV3DC4UL
DC OUTPUTS
KNOCKOUT FOR LOW-VOLTAGE FIELD WIRING
HPD4
CKT #1 COM CKT #2 COM CKT #3 COM CKT #4
4
COM
INPUT POWER TERMINALS (115 VAC, 60 Hz)
HPS3
Connect power input wires or included power cord here.
NEUTRAL
HOT 1 2 ON
EARTH GND
53471bd.wmf
F U S E
TRANSFORMER Input: 115 VAC, 60 Hz Output: 28 VAC @ 3.6 A
KNOCKOUT FOR 115 VAC WIRING
HPV3DC4ULCB
DC OUTPUTS
KNOCKOUT FOR LOW-VOLTAGE FIELD WIRING
HPD4CB
CKT #1 COM CKT #2 COM
A MINIMUM OF 1/4” SHALL BE MAINTAINED BETWEEN THE FIELD WIRING AND THE INTERNAL FACTORY WIRING.
CKT #3 COM CKT #4
4
COM
INPUT POWER TERMINALS (115 VAC, 60 Hz)
HPS3
Connect power input wires or included power cord here.
NEUTRAL
HOT 1 2 ON
EARTH GND
53485bd.wmf
F U S E
TRANSFORMER Input: 115 VAC, 60 Hz Output: 28 VAC @ 3.6 A
KNOCKOUT FOR 115 VAC WIRING
4
HPV3DC4UL(CB), HPV5DC8UL(CB), HPV5DC16UL(CB) Product Installation Document — P/N 53446:B2 6/18/13
HPV5DC8UL KNOCKOUTS FOR LOW-VOLTAGE FIELD WIRING
DC OUTPUTS
CKT #1
COM
COM
CKT #8
CKT #2
COM
COM
CKT #7
CKT #3
COM
COM
CKT #6 COM
COM
CKT #5
4
CKT #4
A MINIMUM OF 1/4” SHALL BE MAINTAINED BETWEEN THE FIELD WIRING AND THE INTERNAL FACTORY WIRING.
INPUT POWER TERMINALS (115 VAC, 60 Hz)
HPD8
HPS5
Connect power input wires or included power cord here.
NEUTRAL
HOT 1 2 ON
EARTH GND
53474bd.wmf
F U S E
TRANSFORMER Input: 115 VAC, 60 Hz Output: 28 VAC @ 3.6 A
KNOCKOUT FOR 115 VAC WIRING
HPV5DC8ULCB
DC OUTPUTS
KNOCKOUTS FOR LOW-VOLTAGE FIELD WIRING
CKT #1
COM
COM
CKT # 8
CKT #2
COM
COM
CKT #7
CKT #3
COM
COM
CKT # 6 COM
COM
CKT #5
4
CKT #4
HPD8CB
INPUT POWER TERMINALS (115 VAC, 60 Hz)
HPS5
Connect power input wires or included power cord here.
NEUTRAL
HOT 1 2 ON
EARTH GND
53488bd.wmf
F U S E
TRANSFORMER Input: 115 VAC, 60 Hz Output: 28 VAC @ 3.6 A
KNOCKOUT FOR 115 VAC WIRING
HPV3DC4UL(CB), HPV5DC8UL(CB), HPV5DC16UL(CB) Product Installation Document — P/N 53446:B2 6/18/13
5
53473bd.wmf
HPV5DC16UL
53487bd.wmf
HPV5DC16ULCB
!
WARNING:TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS APPLIANCE TO RAIN OR MOISTURE. RISK OF ELECTRICAL SHOCK AND/OR EQUIPMENT DAMAGE, DISCONNECT POWER BEORE SERVICING THIS APPLIANCE. • FOR CONTINUOUS PROTECTION AGAINST HAZARD, REPLACE FUSES WITH ONLY EXACT TYPE AND RATING. • MAINTAIN A 1/4" OF SEPARATION BETWEEN THE AC MAINS AND ALL LOW VOLTAGE WIRING. • A READILY ACCESSIBLE SWITCHED CIRCUIT BREAKER MUST BE AVAILABLE TO DISCONNECT MAIN POWER AS REQUIRED. • THIS UNIT CONTAINS NO USER-SERVICEABLE PARTS, INSTALLATION AND SERVICING SHOULD ONLY BE MADE BY QUALIFIED PERSONELL. • INSTALL IN ACCORDANCE WITH WITH ALL LOCAL REGULATIONS AND NATIONAL ELECTRIC CODE.
For additional information: • Visit our website at http://www.honeywellpower.com • Contact Technical Support at (877) HPP-POWR • E-mail us at
[email protected] 6