AL-1812 Installation Instructions

Report 3 Downloads 19 Views
AL-1812 Relay Card

Installation Instructions

1043366C • August 2006 Copyright © 2006, GE Security Inc.

Introduction This is the GE AL-1812 Relay Card Installation Instructions. The relay card provides low current inputs for open collector outputs, such as the AL-1191/Al-1193 Smart Card Readers. The relay cards come in groups of four with the following hardware: • Eight clip-in standoffs • Four plastic standoffs • Eight mounting screws • Eight jumpers CAUTION:

Figure 3 shows a single card mounted in the AL-1685 housing. Figure 3. Single-card mounting

AL-1685 housing

AL-1812 relay card

You must be free of static electricity before handling circuit boards. Wear a grounding strap or touch a bare metal surface to discharge static electricity.

Installation To install the relay card, do the following: 1. Separate the cards into singles or doubles as needed by snapping the cards apart at the score lines (Figure 1).

Figure 4 shows a double card mounted in the AL-1685 housing. Figure 4. Double-card mounting

Figure 1. Separating the relay cards AL-1685 housing

AL-1812 relay cards

Score lines

2.

Mount the cards in AL-1685 metal housings using the appropriate hardware. Figure 2 shows the relay card mounting holes. 3.

Figure 2. Mounting holes

Relay 2 jumper Relay 1 jumper

Mounting holes

Mounting hole

Slide relay 1 and relay 2 contact-programming jumpers (Figure 2) over the pins for the required programming setting (Figure 5). Set dry relay contact. Jumper removed or placed on center pin only Set +12 V on relay comm. Jumper on center pin and plus pin. Set 0 V on relay comm. Jumper on center pin and minus pin.

Figure 5. Jumper settings

Set dry relay contact

Set +12 V on relay comm

Set 0 V on relay comm

+

-

+

-

+

-

2

AL-1812 Relay Card Installation Instructions

Wiring Figure 6 shows a typical relay card wiring diagram. Figure 6. Typical wiring diagram Typical wiring using system bus or AUX power Door strike

AL-119X reader

Typical wiring using an external power supply Green (DO) System bus

White (D1)

AL-1812 relay card

Black (0V) Red (+12)

NC1 0V

Egress (RTE)

External power supply

Violet

Trigger input Trigger input +

RLY 1

+

+TR

NC2 NO2 +

-

C2

Specifications Supply voltage Current consumption Standby All relays active Dimensions Operating temperature Humidity

To system bus 0 V

NO1 C1

RLY 2

-

-

-TR

+12V

+

9 to 14 VDC 75 mA max. 1 A at 0 to 30 VDC 3.1 x 2.0 in. (80 x 52 mm) 32 to 122°F (0 to 50°C) 95% noncondensing

Technical support Toll-free: 888.GESECURity (888.437.3287 in the US, including Alaska and Hawaii; Puerto Rico; Canada). Outside the toll-free area: Contact your local dealer. www.gesecurity.com

Door strike