AO55 Blind Analog Transmitter Quick Start Guide

Components AO55 Wall Mount Unit

AO55 Meter Mount Unit

Recommended Tools • Hex wrench (5/32” or 4 mm)—for opening the cover

• Small flat head screw driver—for adjusting frequency and connecting wiring

Setting Frequency Loosen the screws and then remove the upper portion of the housing. 4

90 1

7 8

7 8

7 8

45 6

45 6

7 8

.

2 3

90 1

2 3

90 1

4

2 3

90 1

2 3

2. Locate the K-factor of the flow sensor (found on the meter or fitting, or in the instruction manual, depending on meter model). The K-factor is the number of pulses the flow sensor produces per gallon of flow.

5

45 6

1

45 6

1. Decide what flow rate should represent the top of the scale. This is ordinarily the maximum expected flow, or a value just above it, in gallons per minute.

Frequency

AO55

3. Calculate frequency, using this formula: Sensor

4-20 mA

Power

K-Factor x Top Flow (GPM) = Frequency 60 For example: 54.50 x 170 = 154.42 60 4. Round to one decimal place and enter the frequency using the four rotary Frequency switches. Note the decimal point between the third and fourth switches. 253.872.0284

Page 1 of 2

seametrics.com

AO55 Blind Analog Transmitter Quick Start Guide

Connections The only connections required on a meter mounted AO55 are the positive and negative 4-20 mA loop connections. If wall mounted, the sensor must also be connected, since it is remote from the transmitter.

Sensor Connections

4-20 mA Connections

7 8

7 8

45 6

45 6

7 8

45 6

45 6

7 8

90 1

2 3

90 1

2 3

90 1

2 3

90 1

2 3

Wiring AO55 to a Mechanical Sensor

Frequency

AO55 Power +

S

Black -

4-20 mA

White

Sensor

Red

24-36 Vdc Power Supply (may be included in control unit) + Red Black + Black

4-20 mA Device (e.g. Pump, PLC, Chart Recorder) Mechanical Sensor

7 8

7 8

45 6

45 6

7 8

45 6

45 6

7 8

2 3

Power

S

4-20 mA

Black Green White

90 1

AO55

+ 24 Vdc Red Sensor

Forward + Output _

2 3

+

90 1

Frequency

Magmeter Terminal Block

Power _

90 1

2 3

90 1

2 3

Wiring AO55 to an EX Magmeter

24-36 Vdc Power Supply (may be included in control unit) + Red Black + Black

4-20 mA Device (e.g. Pump, PLC, Chart Recorder)

For detailed information, including averaging time and calibration, please see the AO55 Instructions booklet, available on our web site at: seametrics.com/downloads. Seametrics • 19026 72nd Avenue South • Kent, Washington 98032 • USA (P) 253.872.0284 • (F) 253.872.0285 • 1.800.975.8153 • seametrics.com