Acct # ___________ Inv # ____________ BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT 33055 OR-FILE NO. _________________

NEW INSTALLATION

(FROM NOTIFICATION LETTER)

FIRM NAME : ADMIRAL CONDOS SEATTLE

ADDRESS: 2331 42ND AVE SW

ZIP: 98116

PARTY CONTACTED: Kari Sprecher

883-4955 PHONE NO. (425) _______________

REDUCED PRESSURE BACKFLOW ASSEMBLY AIRGAP (used in lieu of backflow assembly) DOUBLE CHECK VALVE ASSEMBLY PRESSURE VACUUM BREAKER ASSEMBLY

TITLE Management

MAKE OF ASSEMBLY Febco Model 850 Serial No H250812 CROSS-CONNECTION PROTECTED (EX: FIRE SYSTEM, BOILER ETC.) Irragation _________________ garden under large planter LOCATION OF ASSEMBLY Roof ______________________________ Reduced Pressure Assemblies Double Check Assemblies 1st Check 2nd Check Initial Test Repairs And Materials Used Test After Repairs

Closed tight……....

DC-closed tight ■ Leaked………..….. RPpsid



Relief Valve Opened at psid

Leaked…………....

2.4

Size 1_________

Pressure Vacuum Breaker Air Inlet Check Valve Opened at psid psid Did not Open………....

Leaked ……..…

2.0

DC-closed tight….. RPpsid

Closed tight……....

Opened at psid

Opened at psid

AirGap Inspected APPROVED

psid

FAILED

Remarks: ______________________________________________ NOTE: This Assembly failed its performance test. It must be repaired, retested, and a complete test report sent to the Seattle Public Utilities within 30 days. Ostrander Initial Test Performed By: Matt ____________

Calibration Date:

10/2/14 ________

RETURN REPORT TO: SEATTLE PUBLIC UTILITIES CSB-INSPECTION SERVICES 700 5TH AVE, SUITE 4900 P.O. BOX 34018 SEATTLE, WA 98124-4018 PHONE 206-684-3536 FAX 206-684-7585

Cert. No.:

Gauge #:

B3902 ___

10071347 ___________

Date:

05/28/2015 12:00pm PDT

845 Model: Midwest _________________

INSPECTED/TESTED BY:

Matt Ostrander

REPAIRED BY FINAL TEST BY

COMPANY PERFORMING TEST: AAA Fire & Safety, Inc 3013 3rd Ave N Seattle, Wa 98109 PH: 206-284-1721 FAX 206-284-2176

5/28/15 DATE: ________

DATE: _____________ DATE: ____________

Acct # ___________ Inv # ____________ BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT 22147 OR-FILE NO. _________________

NEW INSTALLATION

(FROM NOTIFICATION LETTER)

FIRM NAME : ADMIRAL CONDOS SEATTLE

ADDRESS: 2331 42ND AVE SW

ZIP: 98116

PARTY CONTACTED: Kari Sprecher

883-4955 PHONE NO. (425) _______________

REDUCED PRESSURE BACKFLOW ASSEMBLY AIRGAP (used in lieu of backflow assembly) DOUBLE CHECK VALVE ASSEMBLY PRESSURE VACUUM BREAKER ASSEMBLY

TITLE Management

MAKE OF ASSEMBLY Ames Model 2000SS Serial No 120993 CROSS-CONNECTION PROTECTED (EX: FIRE SYSTEM, BOILER ETC.) Fire _________________ room LOCATION OF ASSEMBLY Riser ______________________________ Reduced Pressure Assemblies Double Check Assemblies 1st Check 2nd Check Initial Test Repairs And Materials Used Test After Repairs

Closed tight……....

DC-closed tight ■ Leaked………..….. RPpsid



Relief Valve Opened at psid

Leaked…………....

4.0

Size 4"_________

Pressure Vacuum Breaker Air Inlet Check Valve Opened at psid psid Did not Open………....

Leaked ……..…

3.1

DC-closed tight….. RPpsid

Closed tight……....

Opened at psid

Opened at psid

AirGap Inspected APPROVED

psid

FAILED

Remarks: ______________________________________________ NOTE: This Assembly failed its performance test. It must be repaired, retested, and a complete test report sent to the Seattle Public Utilities within 30 days. Ostrander Initial Test Performed By: Matt ____________

Calibration Date:

10/2/14 ________

RETURN REPORT TO: SEATTLE PUBLIC UTILITIES CSB-INSPECTION SERVICES 700 5TH AVE, SUITE 4900 P.O. BOX 34018 SEATTLE, WA 98124-4018 PHONE 206-684-3536 FAX 206-684-7585

Cert. No.:

Gauge #:

B3902 ___

10071347 ___________

Date:

05/28/2015 12:00pm PDT

845 Model: Midwest _________________

INSPECTED/TESTED BY:

Matt Ostrander

REPAIRED BY FINAL TEST BY

COMPANY PERFORMING TEST: AAA Fire & Safety, Inc 3013 3rd Ave N Seattle, Wa 98109 PH: 206-284-1721 FAX 206-284-2176

5/28/15 DATE: ________

DATE: _____________ DATE: ____________

Acct # ___________ Inv # ____________ BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT 18055 OR-FILE NO. _________________

NEW INSTALLATION

(FROM NOTIFICATION LETTER)

FIRM NAME : ADMIRAL CONDOS SEATTLE

ADDRESS: 2331 42ND AVE SW

ZIP: 98116

PARTY CONTACTED: Kari Sprecher

883-4955 PHONE NO. (425) _______________

REDUCED PRESSURE BACKFLOW ASSEMBLY AIRGAP (used in lieu of backflow assembly) DOUBLE CHECK VALVE ASSEMBLY PRESSURE VACUUM BREAKER ASSEMBLY

TITLE Management

MAKE OF ASSEMBLY Wilkins Model 950 Serial No A16298 CROSS-CONNECTION PROTECTED (EX: FIRE SYSTEM, BOILER ETC.) Domestic _________________ room LOCATION OF ASSEMBLY Riser ______________________________ Reduced Pressure Assemblies Double Check Assemblies 1st Check 2nd Check Initial Test Repairs And Materials Used Test After Repairs

Closed tight……....

DC-closed tight ■ Leaked………..….. RPpsid



Relief Valve Opened at psid

Leaked…………....

2.8

Size 3"_________

Pressure Vacuum Breaker Air Inlet Check Valve Opened at psid psid Did not Open………....

Leaked ……..…

3.1

DC-closed tight….. RPpsid

Closed tight……....

Opened at psid

Opened at psid

AirGap Inspected APPROVED

psid

FAILED

Remarks: ______________________________________________ NOTE: This Assembly failed its performance test. It must be repaired, retested, and a complete test report sent to the Seattle Public Utilities within 30 days. Ostrander Initial Test Performed By: Matt ____________

Calibration Date:

10/2/14 ________

RETURN REPORT TO: SEATTLE PUBLIC UTILITIES CSB-INSPECTION SERVICES 700 5TH AVE, SUITE 4900 P.O. BOX 34018 SEATTLE, WA 98124-4018 PHONE 206-684-3536 FAX 206-684-7585

Cert. No.:

Gauge #:

B3902 ___

10071347 ___________

Date:

05/28/2015 12:00pm PDT

846 Model: Midwest _________________

INSPECTED/TESTED BY:

Matt 0strander

REPAIRED BY FINAL TEST BY

COMPANY PERFORMING TEST: AAA Fire & Safety, Inc 3013 3rd Ave N Seattle, Wa 98109 PH: 206-284-1721 FAX 206-284-2176

5/28/15 DATE: ________

DATE: _____________ DATE: ____________

Acct # ___________ Inv # ____________ BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT 18056 OR-FILE NO. _________________

NEW INSTALLATION

(FROM NOTIFICATION LETTER)

FIRM NAME : ADMIRAL CONDOS SEATTLE

ADDRESS: 2331 42ND AVE SW

ZIP: 98116

PARTY CONTACTED: Kari Sprecher

883-4955 PHONE NO. (425) _______________

REDUCED PRESSURE BACKFLOW ASSEMBLY AIRGAP (used in lieu of backflow assembly) DOUBLE CHECK VALVE ASSEMBLY PRESSURE VACUUM BREAKER ASSEMBLY

TITLE Management

MAKE OF ASSEMBLY Febco Model 850 Serial No HC38770 CROSS-CONNECTION PROTECTED (EX: FIRE SYSTEM, BOILER ETC.) Irrigation _________________ room LOCATION OF ASSEMBLY Riser ______________________________ Reduced Pressure Assemblies Double Check Assemblies 1st Check 2nd Check Initial Test Repairs And Materials Used Test After Repairs

Closed tight……....

DC-closed tight ■ Leaked………..….. RPpsid



Relief Valve Opened at psid

Leaked…………....

2.1

Size 3/4" _________

Pressure Vacuum Breaker Air Inlet Check Valve Opened at psid psid Did not Open………....

Leaked ……..…

1.7

DC-closed tight….. RPpsid

Closed tight……....

Opened at psid

Opened at psid

AirGap Inspected APPROVED

psid

FAILED

Remarks: ______________________________________________ NOTE: This Assembly failed its performance test. It must be repaired, retested, and a complete test report sent to the Seattle Public Utilities within 30 days. Ostrander Initial Test Performed By: Matt ____________

Calibration Date:

10/2/14 ________

RETURN REPORT TO: SEATTLE PUBLIC UTILITIES CSB-INSPECTION SERVICES 700 5TH AVE, SUITE 4900 P.O. BOX 34018 SEATTLE, WA 98124-4018 PHONE 206-684-3536 FAX 206-684-7585

Cert. No.:

Gauge #:

B3902 ___

10071347 ___________

Date:

05/28/2015 12:00pm PDT

845 Model: Midwest _________________

INSPECTED/TESTED BY:

Midwest 845

REPAIRED BY FINAL TEST BY

COMPANY PERFORMING TEST: AAA Fire & Safety, Inc 3013 3rd Ave N Seattle, Wa 98109 PH: 206-284-1721 FAX 206-284-2176

5/28/15 DATE: ________

DATE: _____________ DATE: ____________