S3S - Three-Stage Boiler Control Overview The S3S is a Three-Stage Boiler Control which can stage up to three boilers using PID logic for better control of the system temperature. The S3S will enable just enough stages to maintain either a fixed or an outdoor reset set point. The S3S has multiple uses including: Staging three Triangle Tube Boilers to maintain the desired set point for either heating or domestic applications. Staging between multiple sources of heat such as Solar, Geothermal Systems and a Triangle Tube Boiler.
Features •
Stage 3 Triangle Tube Boilers The S3S can be configured to stage up to three Triangle Tube Boilers to maintain the desired system set point.
•
Fixed Lead Stage or Automatic Rotation The S3S can be configured to always start with the same stage or automatically rotate the lead stage to equalize runtimes.
•
Stage 2 Triangle Tube Boilers with a System Pump The S3S can also be configured to stage up to two Triangle Tube Boilers and operate the System Pump.
•
External Enable The S3S can be remotely enabled from an external device or controller.
•
System Pump Run-On The S3S can be configured to provide the System Pump with an additional Run-On time to disburse heat from the boilers.
•
Sensor Fault Operation The S3S provides the option of switching on or off all stages if a sensor fault should occur.
•
Fixed Set Point or Outdoor Reset The S3S can stage up to three boilers to maintain either a fixed set point or operate using the outdoor reset function. The outdoor reset function utilizes fixed reset curves as well as providing the option for custom user defined heating curves.
•
Digital Display Large 2 x 16 character display provides status information as well as easy parameter adjustments in plain English.
•
English or Metric Units The S3S can be configured to operate using either English or Metric units.
•
Mounting Options The S3S can be mounted on a standard 4” x 4” electrical box or can be panel mounted using the included plastic wiring enclosure.
•
Outdoor Cutoff The optional Outdoor Cutoff function can disable the system when the outdoor temperature rises and heat is no longer required.
Part #
Item Description
PSCON14
S3S Three-Stage Boiler Control (Includes System and Outdoor Temperature Sensors)
S3S Specifications Voltage Input: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120VAC 60 Hz (2 Black wires) / 24 VAC 60 Hz (24VAC Terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .(Only One Power Source) Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 VA Max Operating Temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . .20ºF (-7ºC )to 120ºF (49ºC) Operating Humidity: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20% to 80% Dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4”W x 4”H x 2 1/2” Weight: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 pound Outputs: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 S.P.S.T (Yellow = Output A) (Blue = OutputB), (White = Output C.) Output Relay Ratings: . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Amp inductive(Maximum of 1/8 HP), 6 Amp resistive at 120 VAC 60 Hz Control Modes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Outdoor Reset, Set Point Output Modes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Boiler + 1-Pump, 1 Boiler+2-Pump, 1-Lo/Hi+1-Pump, 2 Boilers+1-Pump, 3 Boilers Lead Rotation : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Manual or Time (1Hr to 999 Hr) Purge Delay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.0 to 10.0 minutes Reaction Time: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 to 10 minutes Minimum Runtime: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 to 60 minutes Reset Ratios: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Standard ranging from 8:1 to 1:4 (Outdoor: System), and one Custom Offset: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-40ºF (-22ºC) to 40ºF (+22ºC) Minimum Target: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70ºF (21ºC) to 170ºF (77ºC) Maximum Target: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90ºF (32ºC) to 240ºF (116ºC) Set Point: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-10ºF (-23ºC) to 230ºF (110ºC) Pump Run-On: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 to 60 minutes DHW Priority Timer Options: . . . . . . . . . . . . . . . . . . . . . . . .No Priority, Priority from 1 to 120 minutes Setback: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0ºF (0ºC) to 80ºF (44ºC) Boost: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Yes, No Sensor Fault Operating Options: . . . . . . . . . . . . . . . . . . . . .Output ON or Output OFF Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Back Lite Alphanumeric (2 rows x 16 char. each) LEDs: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 representing the Output Relays Buttons: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 (Set, Up, Down) Prestige Boilers SYSTEM = TARGET =
147 °F 150 °F
OUTPUT A OUTPUT B OUTPUT C
Outdoor Sensor
S3S Application:
SET
prestige
prestige
prestige
The S3S monitors the header temperature and stages the Prestige Solo Boilers as required to maintain set point.
S3S Sensor
Freeway Center - 1 Triangle Lane Blackwood, NJ 08012 Tel: (856) 228 8881- Fax: (856) 228 3584 E-mail:
[email protected] - http://www.triangletube.com 2010-12 S3S Controller
Date 4/20/10