High Speed Fuses
Ferrule Fuses
Table of Contents
Basic Catalog Number FWA FWX FWH FWC FWP FWK FWJ FWL/FWS
Volts 150 250 500 600 690V/700 750 1000 1250/1500/2000
Amp Range 5-60 1-50 0.25-30 6-32 1-100 5-60 20-30 2-30
Accessories
Fuse Holders
Page 224-225 226-227 228-231 232-233 234-237 238-239 240-241 242 241
Ferrule Fuse Ranges
Amps 5-60 1-50 0.25-30 6-32 20-100 1-50 5-60 20-30 20-30 8-15 2-6
AC X X X X X X X X X X X
DC X X X X — X X X (800Vdc) X (1000Vdc) X (1000Vdc) X (1000Vdc)
Bussmann offers a full line of ferrule style (cylindrical clip-mounted) fuses, designed and tested to meet standards and requirements in various locations around the world. Their unique design and construction provide: • Superior cycling capability • Low energy let-through (I2t) Ferrule fuses provide an excellent solution for small UPS, small ac drives and other low power applications where space is at a premium.
Voltage Rating
All Bussmann ferrule fuses — except 690V — have been tested at their rated voltage. The 690V ferrule fuse has been tested to the IEC 60269 standard, which requires clearing at the rated voltage +5%. Accessories
Ferrule fuses may be mounted in fuseclips, fuse holders, fuse blocks or fused switches. A variety of products are available. Please consult Bussmann Application Engineering to discuss your requirement.
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
223
High Speed Fuses
Volts 150 250 500 600 700 (22 x 58mm) 700 (14 x 51mm) 750 1000 1250 1500 2000
General Information
High Speed Fuses
Ferrule — FWA 150V: 5-60A FWA 5-30A (10 x 38mm) 35-60A (21 X 51mm)
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.
Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 150Vac/dc Amps: — 5-60A IR: — 100kA Sym. Agency Information: CE, UL Recognition JFHR2.E91958 Electrical Characteristics Total Clearing I t 2
The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2
1.5 1.0
0.3 0.2
0.15
2)
22
Dimensions A B 1.5 (38.1) 0.375 (9.5) 2.0 (50.8) 0.625 (15.9)
A
70
102
1) 5-30A Range 2) 35-60A Range
Eg
150
C 0.406 (10.3) 0.811 (20.6)
C
B
100
1.0 Kp 0.8
100
150
0.6 0.5 0.4 0.3 0.2 0.1
30 40 50
60
70
Ib
80 90 100%
Electrical Characteristics I2t (A2 Sec) Catalog Numbers FWA-5A10F FWA-10A10F FWA-15A10F FWA-20A10F FWA-25A10F FWA-30A10F FWA-35A21F FWA-40A21F FWA-45A21F FWA-50A21F FWA-60A21F
Size 10 x 38mm (13⁄32” x 11⁄2”) 21 x 51mm (13⁄16” x 2”)
Rated Current RMS-Amps 5 10 15 20 25 30 35 40 45 50 60
• Watts loss provided at rated current. • See accessories on page 243.
• • • •
• • • •
Pre-arc 1.6 3.6 14 33 58 100 75 100 130 170 250
Clearing at 150V 8 16 55 130 220 400 800 1000 1300 1600 2400
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
Data Sheet: 720003
224
50
Eg
Catalog Numbers
Dimensions - in (mm)
Amp Range 5-30 35-60
200
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
1)
0.5
300
Power Losses
K
UL
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts Loss 1 2.7 3.3 3.8 4.9 4.9 4.5 5.1 6 7.3 8.0
High Speed Fuses
Ferrule — FWA 150V: 5-60A FWA 5-30A: 150V (10 x 38mm)
FWA 35-60A: 150V (21 x 51mm)
Time-Current Curve
103
Virtual Pre-Arcing Time In Seconds
102
Time-Current Curve 104 6 4
6 4 2
2
6 4
103 6 4
2
2
6 4
102 6 4 Virtual Pre-Arcing Time In Seconds
104
2 101
FWA-5A10F FWA-10A10F FWA-15A10F FWA-20A10F FWA-25A10F FWA-30A10F
6 4 2
100
6 4 2
10–1
10–2
10–3
2 100
6 4 2
2
2
6 4
10–2 6 4
2
2
6 4
10–3 6 4 2
2 2
4
6
8
101
2
4
6
8
102
2
4
6
8
Prospective Current In Amps RMS
10–4
103
2
101
4
6
8
2
102
104
4
4
2
Peak Let-Through Current
FWA-30A10F FWA-25A10F FWA-20A10F FWA-15A10F
6 4 2
FWA-12A10F FWA-10A10F FWA-5A10F
102
4
10
3
6 4 2
102
4
2
101
103
6
6
101
8
FWA-60A21F FWA-50A21F FWA-45A21F FWA-40A21F FWA-35A21F
6
6
2
6
Peak Let-Through Curve
104
103
4
Prospective Current In Amps RMS
High Speed Fuses
Peak Let-Through Curve
Peak Let-Through Current
2 101 6 4
10–1 6 4
6 4
10–4
FWA-35A21F FWA-40A21F FWA-45A21F FWA-50A21F FWA-60A21F
2 2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
Data Sheet: 35785317
2
4
6
105
2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785305
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
225
High Speed Fuses
Ferrule — FWX 250V (UL): 1-50A FWX (14 x 51mm)
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 250Vac/dc Amps: — 1-50A IR: — 200kA RMS Sym. — 50kA @ 250Vdc Agency Information: CE, UL Recognition JFHR2.E91958 1-50A & CSA Component Acceptance file Class 1422-30, 1422-90 (53787) 5-30A Electrical Characteristics Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
1.4 1.2
Arc Voltage
1.5 1.0 0.5 0.3 0.2
0.15
2)
125
200
250
14.3 (0.563")
15.5 (0.610")
400
1)
300 200
50
1.0 Kp 0.8
Eg
300
Catalog Number FWX-1A14F FWX-2A14F FWX-3A14F FWX-4A14F FWX-5A14F FWX-10A14F FWX-15A14F FWX-20A14F FWX-25A14F FWX-30A14F FWX-50A14F
150
200
Eg
250
0.6 0.5 0.4 0.3 0.2 0.1
30 40 50
60
70
Ib
80 90 100%
Size
14 x 51mm (9⁄16” x 2”)
Electrical Characteristics Rated I2t (A2Sec) Current Clearing RMS-Amps Pre-arc at 250V 1 — — 2 — — 3 — — 4 — — 5 1.6 13 10 3.6 24 15 14 83 20 33 200 25 58 300 30 100 500 50 200 1800
Watts Loss — — — — 1.3 3.4 3.8 4.6 5.3 5.9 5.7
• Watts loss provided at rated current. • (250Vdc/Interrupting rating 50kA) UL Recognition & CSA Component Acceptance on 5 through 30A only. Consult Bussmann for additional ratings. • See accessories on page 243.
• • • •
• • • •
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
Data Sheet: 720006
226
100
2)
Catalog Numbers
Dimensions - mm (in) 50.8 (2.000")
600 500
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
1)
75
800
Power Losses
K
UL
103
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
High Speed Fuses
Ferrule — FWX 250V (UL): 1-50A FWX 1-30A: 250V (14 x 51mm) Time-Current Curve
Prospective Current In Amps RMS
Peak Let-Through Curve High Speed Fuses
Prospective Current In Amps RMS
Data Sheet: 35785302
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
227
High Speed Fuses
Ferrule — FWH 500V: 0.25-30A FWH (6 x 32mm)
Catalog Numbers
Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 500Vac (0.25-6.3A) 500Vdc (2-5A) Amps: — 0.25-30A IR: — 50kA at ≥ 20% pf (0.25-20A) — 20kA at ≥ 20% pf (25-30A) Agency Information: CE, UL Recognition JFHR2.E91958 0.25-30A, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) 0.25-7A Opening Times Amp Ratings 0.25-7 10-30
150% > 30 min < 30 min
200% < 30 min < 30 min
Dimensions - mm (inches) 31.8 (1.25")
300% ≤ 10 sec ≤ 10 sec
6.4 (0.25")
Catalog Size Numbers FWH-.250A6F FWH-.500A6F FWH-001A6F FWH-002A6F FWH-3.15A6F FWH-005A6F FWH-6.30A6F 6 x 32mm FWH-007A6F (1⁄4” x 11⁄4”) FWH-010A6F FWH-12.5A6F FWH-015A6F FWH-016A6F FWH-020A6F FWH-025A6F FWH-030A6F
Rated Current RMS-Amps 0.25* 0.5* 1* 2* 3.15* 5* 6.3* 7* 10** 12.5** 15** 16** 20** 25** 30**
*300% minimum opening current at rated voltage. **200% minimum opening current at rated voltage. • Consult Bussmann for DC ratings. • See accessories on page 243.
• • • •
• • • •
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
3.2 (0.125")
Data Sheet: 720038
228
Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 500V 0.01 0.05 0.05 0.25 0.4 2 1.3 3.5 3.1 7.7 15 40 36 90 50 125 9.9 139 20 60 44 146 48 177 75 259 126 345 145 430
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts Loss 2.7 1.2 1.7 3.2 2.9 2.1 2.3 2.5 2.86 3.53 3.08 4.48 4.26 — —
High Speed Fuses
Ferrule — FWH 500V: 0.25-30A FWH 10-30A: 500V (6 x 32mm)
FWH 0.25-7A: 500V (6 x 32mm)
Time-Current Curve
Time-Current Curve 104
6 4
FWH-002A6F
FWH-3.15A6F
2 10
FWH-005A6F
3
FWH-6.30A6F FWH-007A6F
6 4 2
102
Virtual Pre-Arcing Time In Seconds
6 4 2
101 6 4 2 100 6 4 2 10–1
6 FWH-.250A6F 4 FWH-.500A6F FWH-001A6F 2
10–2 4x10–3
.2
.4
.6
.8
100
2
4
6
8
101
2
4
6
8
102
2
Prospective Current In Amps RMS
High Speed Fuses
Data Sheet: 35785256
Data Sheet: 50955
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
229
High Speed Fuses
Ferrule — FWH 500V: 1-30A FWH (14 x 51mm)
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Specifications Description: Ferrule style high speed fuses. Dimensions: See Dimensions illustration. Ratings: Volts: — 500Vac Amps: — 1-30A IR: — 200kA RMS Sym. — 50kA @500Vdc Agency Information: CE, UL Recognition 1- 30A & CSA Component Acceptance file Class 1422-30, (53787) on: 5 - 30A.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Electrical Characteristics Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
1.5 1.0
K
Catalog Numbers
0.5 0.3 0.2
0.15 100
Dimensions - mm (inches) 50.8 (2.000")
15.5 (0.610")
250
400
14.3 (0.563")
Eg
500
Catalog Numbers Size FWH-1A14F 14 x 51mm 9 FWH-2A14F ( ⁄16” x 2”) FWH-3A14F FWH-4A14F FWH-5A14F FWH-6A14F FWH-10A14F FWH-12A14F FWH-15A14F FWH-20A14F FWH-25A14F FWH-30A14F
2.0 1.2
103
800 600 500 400
300 100
1.0 Kp 0.8
200
300
• • • •
500
0.4 0.3 0.2 0.1
30 40 50
60
70
Features and Benefits Excellent cycling capability and dc performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Ib
80 90 100%
Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 500V 1 — — 2 — — 3 — — 4 — — 5 1.6 6.4 6 1.6 6.4 10 3.6 13 12 — — 15 10 40 20 26 96 25 49 191 30 58 232
• Watts loss provided at rated current. • See accessories on page 243.
• • • •
400
Eg
0.6 0.5
Data Sheet: 720008
230
UL
1.6
Watts Loss — — 2.3 — 1.5 1.5 4 — 5.5 6 7 9
High Speed Fuses
Ferrule — FWH 500V: 1-30A FWH 1-30A: 500V (14 x 51mm) Time-Current Curve 104 6 4 2 103 6 4 2
Virtual Pre-Arcing Time In Seconds
102 6 4
FWH-5A14F FWH-10A14F FWH-15A14F FWH-20A14F FWH-25A14F FWH-30A14F
2 101 6 4 2 100 6 4 2 10–1 6 4 2 10–2 6 4 2 10–3 6 4 2 2
4
6
8
101
2
4
6
8
2
102
4
6
8
High Speed Fuses
10–4
103
Prospective Current In Amps RMS
Peak Let-Through Curve 104
6 4 2
Peak Let-Through Current
10
FWH-30A14F FWH-25A14F
3
6 4 2
FWH-20A14F FWH-15A14F FWH-10A14F FWH-5A14F
102
6 4 2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785298
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
231
High Speed Fuses
Ferrule — FWC 600V: 6-32A voltage, Eg, (rms).
FWC (10 x 38mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 600Vac/700Vdc (6-25A) 600Vac (30-32A) Amps: — 6-32A IR: — 200kA RMS Sym. — 50kA @ 700Vdc (6-25A) Agency Information: CE, UL Recognition JFHR8.E91958 6-32A. & CSA Component Acceptance file Class 1422-30, (53787) on (6-32A) Electrical Characteristics Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working
1.5 1.0
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%. Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
K
0.5 0.3 0.2
0.15 100
Dimensions - mm (in) 38.1 (1.500")
1.6
250
400
Eg
500
600
Catalog Numbers Size FWC-6A10F FWC-8A10F FWC-10A10F FWC-12A10F 10 x 38mm FWC-16A10F (13⁄32” x 11⁄2”) FWC-20A10F FWC-25A10F FWC-30A10F FWC-32A10F
1.2
103
800 600 500 400 300 200
1.0 Kp 0.8
Eg 300
500
400
600
0.6 0.5 0.4 0.3 0.2 0.1
30 40 50
60
70
Ib
80 90 100%
Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 600V 6 4 30 8 6 50 10 9 70 12 15 120 16 25 150 20 34 260 25 60 390 30 95 600 32 95 600
• Watts loss provided at rated current. • See accessories on page 243.
• • • •
• • • •
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
Data Sheet: 720011
232
UL
Catalog Numbers
10.3 (0.406")
9.5 (0.375")
2.0
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts Loss 1.5 2.0 2.5 3.0 3.5 4.8 6.0 7.5 7.5
High Speed Fuses
Ferrule — FWC 600V: 6-32A FWC 6-32A: 600V (10 x 38mm) Time-Current Curve 104
6 4 2
103
FWC-6A10F FWC-8A10F FWC-10A10F FWC-12A10F FWC-16A10F FWC-20A10F FWC-25A10F FWC-30A10F & FWC-32A10F
6 4 2
102
6 4
Virtual Pre-Arcing Time In Seconds
2 10
1
6 4 2
100
6 4 2
10–1
6 4 2
10–2
6 4 2
10–3
6 4 2 2
101
4
6
8 102
2
4
6
Prospective Current In Amps RMS
High Speed Fuses
10–4
8 103
Peak Let-Through Curve 104
6
FWC-30A10F & FWC-32A10F FWC-25A10F FWC-20A10F FWC-16A10F
4 2
Peak Let-Through Current
10
3
6 4 2
FWC-12A10F FWC-10A10F FWC-8A10F FWC-6A10F
102
6 4 2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
4
6
105
2
Data Sheet: 35785306
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
233
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 1-50A, Striker Optional FWP (14 x 51mm)
Arc Voltage
Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustrations. Ratings: Volts: — 690Vac (IEC) — 700Vac (UL) FWP with — 800Vdc (5-50A) striker option. Amps: — 1-50A IR: — 200kA RMS Sym. — 50kA @800Vdc Agency Information: CE, UL Recognition JFHR2.E91958, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) for versions without indicator only. Designed and tested to IEC 60269: Part 4. Electrical Characteristics Total Clearing I2t
1.4 1.2 1.0 0.9 0.8 0.7 0.6
The total clearing I2t at rated voltage and at power factor of 15% are given in 0.5 the electrical 1) characteristics. For other 0.4 2) voltages, the clearing I2t is 0.3 found by multiplying by 200 correction factor, K, given as a function of applied working voltage, Eg, (rms).
1.4 1.2 103 9 8 7 6
Power Losses
3
Catalog Numbers
300
400
500
1) 5-30A Range 2) 32-50A Range
600
Eg
700
Without Striker 50.8 (2.000")
14.3 (0.563")
15.5 (0.610")
With Striker
5 (0.197")
Size
51 (2.00") 13 (0.511")
• • • •
4 200
1.0 Kp 0.8
300
400
500
600
Eg
700
0.6 0.5 0.4 0.3 0.2
Ib
0.1
30 40 50 60 70 80 90 100% Electrical Characteristics Rated I2t (A2 Sec) Current Minimum Clearing At Watts RMS-Amps Melting Rated Voltage Loss
14 x 51mm (9⁄16" x 2")
14 x 51mm (9⁄16” x 2”)
*Striker range is 600Vdc only • Watts loss provided at rated current. • See accessories on page 243.
59 (2.323") 14.3 (0.563")
Catalog Numbers Without Striker FWP-1A14F FWP-2A14F FWP-2.5A14F FWP-3A14F FWP-4A14F FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F With Striker* FWP-10A14FI FWP-15A14FI FWP-20A14FI FWP-25A14FI FWP-30A14FI FWP-32A14FI FWP-40A14FI FWP-50A14FI
UL
5
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
K
Dimensions - mm (in)
234
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.
1 2 2.5 3 4 5 10 15 20 25 30 32 40 50
10 15 20 25 30 32 40 50
— — — — — 1.6 3.6 8.6 26.0 46.5 58 68 84 200
3.6 8.6 26.0 46.5 58 68 84 200
— — — — — 11.0 38.5 70 230 375 485 600 750 1800 38.5 70 230 375 485 600 750 1800
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Data Sheet: 720025
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
— — — — — 1.5 4 5.5 6 7 9 7.6 8 9
4 5.5 6 7 9 7.6 8 9
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 1-50A, Striker Optional Without Striker FWP 5-50A: 660V/700V (14 x 51mm) Time-Current Curve 104
6 4 2
103
6 4 2
Virtual Pre-Arcing Time In Seconds
102
FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F
6 4 2
101
6 4 2
100
10–1
6 4
FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F
2 6 4 2
10–2
6 4 2
10–3
6 4 2
10–4
2
4
6
8
2
101
4
6
8
2
102
4
6
8
103
High Speed Fuses
Prospective Current In Amps RMS
Peak Let-Through Curve 104
FWP-50A14F FWP-40A14F FWP-32A14F FWP-30A14F FWP-25A14F
6 4 2
Peak Let-Through Current
103
6 4 2
FWP-20A14F FWP-15A14F FWP-10A14F FWP-5A14F
102
6 4 2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785307
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
235
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional FWP (22 x 58mm)
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.
Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustration. Ratings: Volts: — 690Vac (IEC) — 700Vac (UL) FWP with — 500Vac striker option. — 500Vdc (20-100A) Amps: — 20-100A IR: — 200kA RMS Sym. — 50kA @ 500Vdc Agency Information: CE, UL Recognition JFHR2.E91958, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) Electrical Characteristics Total Clearing I2t
The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2
1.4 1.2 1.0 0.9 0.8 0.7 0.6
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
K
0.5 0.4
0.3 200
300
58.0 (2.283")
400
500
22.2 (0.875")
600
Eg
700
Catalog Numbers Without Striker FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F With Striker FWP-20A22FI FWP-25A22FI FWP-32A22FI FWP-40A22FI FWP-50A22FI FWP-63A22FI FWP-80A22FI FWP-100A22FI
Size 22 x 58mm (7⁄8" x 29⁄32")
22 x 58mm (7⁄8" x 29⁄32")
*IEC/UL Voltage rating 690/700 15.0 (0.591")
With Striker
66 (2.598") 58 (2.283") 5 (0.197")
22.2 (0.874")
UL
5 4
3
200
1.0 Kp 0.8
400
500
600
700
0.6 0.5
0.4
0.3 0.2 0.1
30 40 50
16 (0.630"
• • • •
• • • •
Rated Current RMS-Amps 20 25 32 40 50 63 80 100*
20 25 32 40 50 63 80 100*
60
70
Ib
80 90 100%
Electrical Characteristics I2t (A2 Sec) Minimum Clearing At Melting Rated Voltage
Watts Loss
19.0 34.0 53.5 68 135 280 600 1100
5 6 8 9 9.5 11 13.5 16
19.0 34.0 53.5 68 135 280 600 1100
260 410 605 750 1600 3080 6600 12500
260 410 605 750 1600 3080 6600 12500
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
Data Sheet: 720026
236
300
Eg
Catalog Numbers
Dimensions - mm (in)
Without Striker
1.4 1.2 103 9 8 7 6
Arc Voltage
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
5 6 8 9 9.5 11 13.5 16
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional Without Striker FWP 20-100A: 660V/700V (22 x 58mm) Time-Current Curve 104
6 4 2
103
6 4 2
102
FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F
6 4 2
Virtual Pre-Arcing Time In Seconds
101 6 4 2 10
0
6 4
FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F
2 10–1 6 4 2 10–2
6 4 2
10–3
6 4 2 2
101
4
6
8
2
102
4
6
8
High Speed Fuses
10–4
103
Prospective Current In Amps RMS
Peak Let-Through Curve 104
FWP-100A22F FWP-80A22F
6
FWP-63A22F
Peak Let-Through Current
4
FWP-50A22F
2 103 6
FWP-40A22F FWP-32A22F
4
FWP-25A22F FWP-20A22F
2 102
102
2
4
6
103
2
4
6
104
2
Prospective Short-Circuit Current Symmetrical RMS
4
6
105
2
Data Sheet: 35785291
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
237
High Speed Fuses
Ferrule — FWK 750V: 5-60A • • • •
FWK 5-30A (20 x 127mm 35-60A (25 x 146mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: — 750Vac — 750Vdc (Time constant = 10-15mS) Amps: — 5-60A IR: — 45kA RMS Sym. Agency Information: CE
• • • •
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
Catalog Numbers Catalog Numbers FWK-5A20F FWK-8A20F FWK-10A20F FWK-15A20F FWK-20A20F FWK-25A20F FWK-30A20F FWK-35A25F FWK-40A25F FWK-50A25F FWK-60A25F
Size 20 x 127mm (13⁄16” x 5”) 25 x 146mm (1” x 53⁄4”)
Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 750Vdc 5 8.5 16 8 50 100 10 95 200 15 100 240 20 125 315 25 400 1100 30 800 2600 35 1300 4300 40 1600 5300 50 3100 12000 60 5900 24000
Recommended fuseholders for 20x127, -2, -3 Recommended fuseclips for 20x127, 1A1837 Recommended fuseclips for 25x146, A3354705
Dimensions - mm (in) Fig. 1: 5-30A 127.0 (5.000")
20.5 (0.807")
16.0 (0.630")
Fig. 2: 35-60A 146.05 (5.75")
25.4 (1")
20.64 (0.813")
Data Sheet: 720039
238
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
High Speed Fuses
Ferrule — FWK 750V: 5-60A FWK 750V: 5-30A (20 x 127mm) 35-60A (25 x 146mm) Time-Current Curve 104 6 4 FWK-15A20F
2
FWK-20A20F
103
FWK-25A20F
6
FWK-30A20F
4
FWK-40A25F FWK-50A25F
2
FWK-60A25F
102 Virtual Pre-Arcing Time In Seconds
6 4 2 101 6 4 2 100 6 4
FWK-5A20F FWK-8A20F
2 10
FWK-10A20F
±1
6 4 2 10
±2
4x10
±3
2
4
6
8
101
2
4
6
8
102
2
4
6
8
103
Prospective Current In Amps RMS
High Speed Fuses
Data Sheet: 720028
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
239
High Speed Fuses
Ferrule — FWJ 1000V: 20-30A FWJ (14 x 67mm)
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.
Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 1000Vac/800Vdc Amps: — 20-30A IR: — 25kA RMS Sym. — 20kA @ 800Vdc Agency Information: CE, UL Recognized JFHR2.E91958 Electrical Characteristics Total Clearing I2t
1.5
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
1.0
0.15 200
500
800
Dimensions - mm (in) 66.7 (2.626")
14.5 (0.571")
15.9 (0.625")
Fuseclips: • Catalog Number: 5591 (see data sheet 2132)
800 400
200
1.0 Kp 0.8
1000 1400 1800
0.6 0.5 0.4 0.3 0.2 0.1
30 40 50
60
70
Ib
80 90 100%
Catalog Numbers FWJ-20A14F FWJ-25A14F FWJ-30A14F
Size 14 x 67mm 9 ( ⁄16” x 25⁄8”)
• Watts loss provided at rated current. • See accessories on page 243.
• • • •
• • • •
Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 1000V 25 220 33 350 52 450
Rated Current RMS-Amps 20 25 30
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters
Data Sheet: 35785031
240
600
Eg
Catalog Numbers
Eg
1000
1200
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
0.5
UL
1600
Power Losses
K
0.3 0.2
2000
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts Loss 9 11 14
High Speed Fuses
Ferrule — FWJ 1000V: 20-30A FWJ 20-30A: 1000V (14 x 67mm) Time-Current Curve 104
6 4 2
103
6 4 2
102
6 4
Virtual Pre-Arcing Time In Seconds
2 101
6 4
FWJ-20A14F FWJ-25A14F FWJ-30A14F
2 100
6 4 2
10–1
6 4 2
10–2
6 4 2
10–3
6 4
101
2
4
6
8 102
2
4
6
High Speed Fuses
2 10–4
8 103
Prospective Current In Amps RMS
Peak Let-Through Curve 104
6
4
FWJ-30A14F FWJ-25A14F FWJ-20A14F
2
Peak Let-Through Current
103
6
4
2
102
6
4
2 101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785315
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
241
High Speed Fuses
Ferrule — FWS/FWL 1000Vdc: 2-30A • • • •
FWS 2-15A (20 x 127mm) FWL 20-30A (20 x 127mm) Specifications Description: Ferrule style full range fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 1200Vac (FWL 20-30A) — 1400Vac (FWS 8-15A) — 2100Vac (FWS 2-6A) — 1000Vdc (FWL/FWS 2-30) Amps: — 2-30A IR: — 45kA RMS Sym. — 30kA @ 1000Vdc Agency Information: CE, IEC 60077
• • • • • •
Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks
Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters Traction aux circuits Capacitor protection
FWL/FWS 2-30A: 1000Vdc 2-30A (20 x 127mm) Time-Current Curve
Catalog Numbers Catalog Numbers FWS-2A20F FWS-6A20F FWS-8A20F FWS-10A20F FWS-12A20F FWS-15A20F FWL-20A20F FWL-25A20F FWL-30A20F
Size 20 x 127mm (13⁄16” x 5”) 20 x 127mm (13⁄16” x 5”)
Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 1000Vdc 2 0.8 2.4 6 27 81 8 64 192 10 118 277 12 170 380 15 209 500 20 675 1550 25 1200 2760 30 1850 4300
• ADD “I” to catalog number for indicating version. • Enclosed finger-safe fuse holder – CH127 • See accessories on page 243. • Watts loss provided at rated current.
Dimensions - mm (in) 127.0 (5.000")
Watts Loss 4.4 6.7 7.6 3.0 3.4 5.0 5.9 6.5 7.5
20.5 (0.807")
16.0 (0.630")
Indicating Version – Dimensions - mm (in) 8.0 (0.315") 127.0 (5.000")
20.5 (0.807")
2.0
16.0 (0.630")
Data Sheet: 720040
242
2.0 (0.079")
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
High Speed Fuses
Ferrule Fuse Accessories Fuse Blocks
Fuse Holders Specifications Catalog Symbol: CH Series Description: DIN-Rail mount fuse holders Agency Information: UL File E14853, Guide IZLT Listed, IZLT2 Recognized CSA: File 47235, CHPV and CHM - Class 6225-30, CHCC - Class 6225-01 Ratings: 600V/30A (UL) 690V/32A (IEC) Features and Benefits • Finger-safe design - No exposed contacts • DIN-Rail mount (35mm) - Fits standard mounting rails • Optional open fuse indication lights tells fuse status at a glance • Handle/fusepuller easily installs and removes fuses • Available in single and multi-pole configurations • Wire ready lugs and spade terminal connections save installation time • CE marking • Available up to 1000Vdc • PLC device available for remote monitoring
Specifications Catalog Symbol: J70100, J70032 Description: Fuse blocks for 22x58mm & 14x51mm fuses. Ratings: Volts: — 700Vac/dc Amps: — 32-100A Withstand: — 200kA RMS Sym. Agency Information: CE, UL Recognized, Guide IZLT2, File E14853 Flammability Rating: UL 94V0 Catalog Numbers Catalog Numbers
Fuse Size
J70032-2CR
14x51
J70100-2CR
22x58 22x58
J70032-1CR J70032-3CR J70100-1CR J70100-3CR
32
Poles
100
1
Amps 32 32
100 100
1 2 3 2 3
Max Wire Size #2 #2 #2 #2 #2
Terminations Box Lug w/ Box Clip Lug w/ Retaining Retaining Clip
#2
Typical Applications • Switchboard panel, control consoles, small motors, transformers, and similar applications
High Speed Fuses
Recommended Cooper Bussmann Fuse Types Class CC North American Class CC Fuses - LP-CC, FNQ-R, KTK-R 10 x 38 North American Midget Fuses - FNQ, KTK, AGU, BAF, BAN, FNM, FWA, FWC, & PV 14 x 51 FWX, FWH, FWP & NON 22 x 58 FWP
See pages 274-280 for CH Series fuse holder information.
Data Sheet: 2053
Data Sheet: 1211
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
243
High speed fuses
Faster lead-time. Better protection. More energy efficient.
244