Bussmann Full Line Catalog # 1007 - Section 6 High Speed Fuses ...

Report 3 Downloads 125 Views
High Speed Fuses

Ferrule Fuses

Table of Contents

Basic Catalog Number FWA FWX FWH FWC FWP FWK FWJ FWL/FWS

Volts 150 250 500 600 690V/700 750 1000 1250/1500/2000

Amp Range 5-60 1-50 0.25-30 6-32 1-100 5-60 20-30 2-30

Accessories

Fuse Holders

Page 224-225 226-227 228-231 232-233 234-237 238-239 240-241 242 241

Ferrule Fuse Ranges

Amps 5-60 1-50 0.25-30 6-32 20-100 1-50 5-60 20-30 20-30 8-15 2-6

AC X X X X X X X X X X X

DC X X X X — X X X (800Vdc) X (1000Vdc) X (1000Vdc) X (1000Vdc)

Bussmann offers a full line of ferrule style (cylindrical clip-mounted) fuses, designed and tested to meet standards and requirements in various locations around the world. Their unique design and construction provide: • Superior cycling capability • Low energy let-through (I2t) Ferrule fuses provide an excellent solution for small UPS, small ac drives and other low power applications where space is at a premium.

Voltage Rating

All Bussmann ferrule fuses — except 690V — have been tested at their rated voltage. The 690V ferrule fuse has been tested to the IEC 60269 standard, which requires clearing at the rated voltage +5%. Accessories

Ferrule fuses may be mounted in fuseclips, fuse holders, fuse blocks or fused switches. A variety of products are available. Please consult Bussmann Application Engineering to discuss your requirement.

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

223

High Speed Fuses

Volts 150 250 500 600 700 (22 x 58mm) 700 (14 x 51mm) 750 1000 1250 1500 2000

General Information

High Speed Fuses

Ferrule — FWA 150V: 5-60A FWA 5-30A (10 x 38mm) 35-60A (21 X 51mm)

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.

Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 150Vac/dc Amps: — 5-60A IR: — 100kA Sym. Agency Information: CE, UL Recognition JFHR2.E91958 Electrical Characteristics Total Clearing I t 2

The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2

1.5 1.0

0.3 0.2

0.15

2)

22

Dimensions A B 1.5 (38.1) 0.375 (9.5) 2.0 (50.8) 0.625 (15.9)

A

70

102

1) 5-30A Range 2) 35-60A Range

Eg

150

C 0.406 (10.3) 0.811 (20.6)

C

B

100

1.0 Kp 0.8

100

150

0.6 0.5 0.4 0.3 0.2 0.1

30 40 50

60

70

Ib

80 90 100%

Electrical Characteristics I2t (A2 Sec) Catalog Numbers FWA-5A10F FWA-10A10F FWA-15A10F FWA-20A10F FWA-25A10F FWA-30A10F FWA-35A21F FWA-40A21F FWA-45A21F FWA-50A21F FWA-60A21F

Size 10 x 38mm (13⁄32” x 11⁄2”) 21 x 51mm (13⁄16” x 2”)

Rated Current RMS-Amps 5 10 15 20 25 30 35 40 45 50 60

• Watts loss provided at rated current. • See accessories on page 243.

• • • •

• • • •

Pre-arc 1.6 3.6 14 33 58 100 75 100 130 170 250

Clearing at 150V 8 16 55 130 220 400 800 1000 1300 1600 2400

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

Data Sheet: 720003

224

50

Eg

Catalog Numbers

Dimensions - in (mm)

Amp Range 5-30 35-60

200

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

1)

0.5

300

Power Losses

K

UL

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Watts Loss 1 2.7 3.3 3.8 4.9 4.9 4.5 5.1 6 7.3 8.0

High Speed Fuses

Ferrule — FWA 150V: 5-60A FWA 5-30A: 150V (10 x 38mm)

FWA 35-60A: 150V (21 x 51mm)

Time-Current Curve

103

Virtual Pre-Arcing Time In Seconds

102

Time-Current Curve 104 6 4

6 4 2

2

6 4

103 6 4

2

2

6 4

102 6 4 Virtual Pre-Arcing Time In Seconds

104

2 101

FWA-5A10F FWA-10A10F FWA-15A10F FWA-20A10F FWA-25A10F FWA-30A10F

6 4 2

100

6 4 2

10–1

10–2

10–3

2 100

6 4 2

2

2

6 4

10–2 6 4

2

2

6 4

10–3 6 4 2

2 2

4

6

8

101

2

4

6

8

102

2

4

6

8

Prospective Current In Amps RMS

10–4

103

2

101

4

6

8

2

102

104

4

4

2

Peak Let-Through Current

FWA-30A10F FWA-25A10F FWA-20A10F FWA-15A10F

6 4 2

FWA-12A10F FWA-10A10F FWA-5A10F

102

4

10

3

6 4 2

102

4

2

101

103

6

6

101

8

FWA-60A21F FWA-50A21F FWA-45A21F FWA-40A21F FWA-35A21F

6

6

2

6

Peak Let-Through Curve

104

103

4

Prospective Current In Amps RMS

High Speed Fuses

Peak Let-Through Curve

Peak Let-Through Current

2 101 6 4

10–1 6 4

6 4

10–4

FWA-35A21F FWA-40A21F FWA-45A21F FWA-50A21F FWA-60A21F

2 2

4

6

102

2

4

6

103

2

4

6

104

Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785317

2

4

6

105

2

101

101

2

4

6

102

2

4

6

103

2

4

6

104

Prospective Short-Circuit Current Symmetrical RMS

2

4

6

105

2

Data Sheet: 35785305

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

225

High Speed Fuses

Ferrule — FWX 250V (UL): 1-50A FWX (14 x 51mm)

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 250Vac/dc Amps: — 1-50A IR: — 200kA RMS Sym. — 50kA @ 250Vdc Agency Information: CE, UL Recognition JFHR2.E91958 1-50A & CSA Component Acceptance file Class 1422-30, 1422-90 (53787) 5-30A Electrical Characteristics Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

1.4 1.2

Arc Voltage

1.5 1.0 0.5 0.3 0.2

0.15

2)

125

200

250

14.3 (0.563")

15.5 (0.610")

400

1)

300 200

50

1.0 Kp 0.8

Eg

300

Catalog Number FWX-1A14F FWX-2A14F FWX-3A14F FWX-4A14F FWX-5A14F FWX-10A14F FWX-15A14F FWX-20A14F FWX-25A14F FWX-30A14F FWX-50A14F

150

200

Eg

250

0.6 0.5 0.4 0.3 0.2 0.1

30 40 50

60

70

Ib

80 90 100%

Size

14 x 51mm (9⁄16” x 2”)

Electrical Characteristics Rated I2t (A2Sec) Current Clearing RMS-Amps Pre-arc at 250V 1 — — 2 — — 3 — — 4 — — 5 1.6 13 10 3.6 24 15 14 83 20 33 200 25 58 300 30 100 500 50 200 1800

Watts Loss — — — — 1.3 3.4 3.8 4.6 5.3 5.9 5.7

• Watts loss provided at rated current. • (250Vdc/Interrupting rating 50kA) UL Recognition & CSA Component Acceptance on 5 through 30A only. Consult Bussmann for additional ratings. • See accessories on page 243.

• • • •

• • • •

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

Data Sheet: 720006

226

100

2)

Catalog Numbers

Dimensions - mm (in) 50.8 (2.000")

600 500

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

1)

75

800

Power Losses

K

UL

103

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

High Speed Fuses

Ferrule — FWX 250V (UL): 1-50A FWX 1-30A: 250V (14 x 51mm) Time-Current Curve

Prospective Current In Amps RMS

Peak Let-Through Curve High Speed Fuses

Prospective Current In Amps RMS

Data Sheet: 35785302

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

227

High Speed Fuses

Ferrule — FWH 500V: 0.25-30A FWH (6 x 32mm)

Catalog Numbers

Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 500Vac (0.25-6.3A) 500Vdc (2-5A) Amps: — 0.25-30A IR: — 50kA at ≥ 20% pf (0.25-20A) — 20kA at ≥ 20% pf (25-30A) Agency Information: CE, UL Recognition JFHR2.E91958 0.25-30A, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) 0.25-7A Opening Times Amp Ratings 0.25-7 10-30

150% > 30 min < 30 min

200% < 30 min < 30 min

Dimensions - mm (inches) 31.8 (1.25")

300% ≤ 10 sec ≤ 10 sec

6.4 (0.25")

Catalog Size Numbers FWH-.250A6F FWH-.500A6F FWH-001A6F FWH-002A6F FWH-3.15A6F FWH-005A6F FWH-6.30A6F 6 x 32mm FWH-007A6F (1⁄4” x 11⁄4”) FWH-010A6F FWH-12.5A6F FWH-015A6F FWH-016A6F FWH-020A6F FWH-025A6F FWH-030A6F

Rated Current RMS-Amps 0.25* 0.5* 1* 2* 3.15* 5* 6.3* 7* 10** 12.5** 15** 16** 20** 25** 30**

*300% minimum opening current at rated voltage. **200% minimum opening current at rated voltage. • Consult Bussmann for DC ratings. • See accessories on page 243.

• • • •

• • • •

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

3.2 (0.125")

Data Sheet: 720038

228

Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 500V 0.01 0.05 0.05 0.25 0.4 2 1.3 3.5 3.1 7.7 15 40 36 90 50 125 9.9 139 20 60 44 146 48 177 75 259 126 345 145 430

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Watts Loss 2.7 1.2 1.7 3.2 2.9 2.1 2.3 2.5 2.86 3.53 3.08 4.48 4.26 — —

High Speed Fuses

Ferrule — FWH 500V: 0.25-30A FWH 10-30A: 500V (6 x 32mm)

FWH 0.25-7A: 500V (6 x 32mm)

Time-Current Curve

Time-Current Curve 104

6 4

FWH-002A6F

FWH-3.15A6F

2 10

FWH-005A6F

3

FWH-6.30A6F FWH-007A6F

6 4 2

102

Virtual Pre-Arcing Time In Seconds

6 4 2

101 6 4 2 100 6 4 2 10–1

6 FWH-.250A6F 4 FWH-.500A6F FWH-001A6F 2

10–2 4x10–3

.2

.4

.6

.8

100

2

4

6

8

101

2

4

6

8

102

2

Prospective Current In Amps RMS

High Speed Fuses

Data Sheet: 35785256

Data Sheet: 50955

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

229

High Speed Fuses

Ferrule — FWH 500V: 1-30A FWH (14 x 51mm)

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Specifications Description: Ferrule style high speed fuses. Dimensions: See Dimensions illustration. Ratings: Volts: — 500Vac Amps: — 1-30A IR: — 200kA RMS Sym. — 50kA @500Vdc Agency Information: CE, UL Recognition 1- 30A & CSA Component Acceptance file Class 1422-30, (53787) on: 5 - 30A.

Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

Electrical Characteristics Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

1.5 1.0

K

Catalog Numbers

0.5 0.3 0.2

0.15 100

Dimensions - mm (inches) 50.8 (2.000")

15.5 (0.610")

250

400

14.3 (0.563")

Eg

500

Catalog Numbers Size FWH-1A14F 14 x 51mm 9 FWH-2A14F ( ⁄16” x 2”) FWH-3A14F FWH-4A14F FWH-5A14F FWH-6A14F FWH-10A14F FWH-12A14F FWH-15A14F FWH-20A14F FWH-25A14F FWH-30A14F

2.0 1.2

103

800 600 500 400

300 100

1.0 Kp 0.8

200

300

• • • •

500

0.4 0.3 0.2 0.1

30 40 50

60

70

Features and Benefits Excellent cycling capability and dc performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Ib

80 90 100%

Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 500V 1 — — 2 — — 3 — — 4 — — 5 1.6 6.4 6 1.6 6.4 10 3.6 13 12 — — 15 10 40 20 26 96 25 49 191 30 58 232

• Watts loss provided at rated current. • See accessories on page 243.

• • • •

400

Eg

0.6 0.5

Data Sheet: 720008

230

UL

1.6

Watts Loss — — 2.3 — 1.5 1.5 4 — 5.5 6 7 9

High Speed Fuses

Ferrule — FWH 500V: 1-30A FWH 1-30A: 500V (14 x 51mm) Time-Current Curve 104 6 4 2 103 6 4 2

Virtual Pre-Arcing Time In Seconds

102 6 4

FWH-5A14F FWH-10A14F FWH-15A14F FWH-20A14F FWH-25A14F FWH-30A14F

2 101 6 4 2 100 6 4 2 10–1 6 4 2 10–2 6 4 2 10–3 6 4 2 2

4

6

8

101

2

4

6

8

2

102

4

6

8

High Speed Fuses

10–4

103

Prospective Current In Amps RMS

Peak Let-Through Curve 104

6 4 2

Peak Let-Through Current

10

FWH-30A14F FWH-25A14F

3

6 4 2

FWH-20A14F FWH-15A14F FWH-10A14F FWH-5A14F

102

6 4 2

101

101

2

4

6

102

2

4

6

103

2

4

6

104

Prospective Short-Circuit Current Symmetrical RMS

2

4

6

105

2

Data Sheet: 35785298

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

231

High Speed Fuses

Ferrule — FWC 600V: 6-32A voltage, Eg, (rms).

FWC (10 x 38mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 600Vac/700Vdc (6-25A) 600Vac (30-32A) Amps: — 6-32A IR: — 200kA RMS Sym. — 50kA @ 700Vdc (6-25A) Agency Information: CE, UL Recognition JFHR8.E91958 6-32A. & CSA Component Acceptance file Class 1422-30, (53787) on (6-32A) Electrical Characteristics Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working

1.5 1.0

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%. Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

K

0.5 0.3 0.2

0.15 100

Dimensions - mm (in) 38.1 (1.500")

1.6

250

400

Eg

500

600

Catalog Numbers Size FWC-6A10F FWC-8A10F FWC-10A10F FWC-12A10F 10 x 38mm FWC-16A10F (13⁄32” x 11⁄2”) FWC-20A10F FWC-25A10F FWC-30A10F FWC-32A10F

1.2

103

800 600 500 400 300 200

1.0 Kp 0.8

Eg 300

500

400

600

0.6 0.5 0.4 0.3 0.2 0.1

30 40 50

60

70

Ib

80 90 100%

Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 600V 6 4 30 8 6 50 10 9 70 12 15 120 16 25 150 20 34 260 25 60 390 30 95 600 32 95 600

• Watts loss provided at rated current. • See accessories on page 243.

• • • •

• • • •

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

Data Sheet: 720011

232

UL

Catalog Numbers

10.3 (0.406")

9.5 (0.375")

2.0

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Watts Loss 1.5 2.0 2.5 3.0 3.5 4.8 6.0 7.5 7.5

High Speed Fuses

Ferrule — FWC 600V: 6-32A FWC 6-32A: 600V (10 x 38mm) Time-Current Curve 104

6 4 2

103

FWC-6A10F FWC-8A10F FWC-10A10F FWC-12A10F FWC-16A10F FWC-20A10F FWC-25A10F FWC-30A10F & FWC-32A10F

6 4 2

102

6 4

Virtual Pre-Arcing Time In Seconds

2 10

1

6 4 2

100

6 4 2

10–1

6 4 2

10–2

6 4 2

10–3

6 4 2 2

101

4

6

8 102

2

4

6

Prospective Current In Amps RMS

High Speed Fuses

10–4

8 103

Peak Let-Through Curve 104

6

FWC-30A10F & FWC-32A10F FWC-25A10F FWC-20A10F FWC-16A10F

4 2

Peak Let-Through Current

10

3

6 4 2

FWC-12A10F FWC-10A10F FWC-8A10F FWC-6A10F

102

6 4 2

101

101

2

4

6

102

2

4

6

103

2

4

6

104

Prospective Short-Circuit Current Symmetrical RMS

4

6

105

2

Data Sheet: 35785306

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

233

High Speed Fuses

Ferrule — FWP 690V/700V (IEC/UL): 1-50A, Striker Optional FWP (14 x 51mm)

Arc Voltage

Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustrations. Ratings: Volts: — 690Vac (IEC) — 700Vac (UL) FWP with — 800Vdc (5-50A) striker option. Amps: — 1-50A IR: — 200kA RMS Sym. — 50kA @800Vdc Agency Information: CE, UL Recognition JFHR2.E91958, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) for versions without indicator only. Designed and tested to IEC 60269: Part 4. Electrical Characteristics Total Clearing I2t

1.4 1.2 1.0 0.9 0.8 0.7 0.6

The total clearing I2t at rated voltage and at power factor of 15% are given in 0.5 the electrical 1) characteristics. For other 0.4 2) voltages, the clearing I2t is 0.3 found by multiplying by 200 correction factor, K, given as a function of applied working voltage, Eg, (rms).

1.4 1.2 103 9 8 7 6

Power Losses

3

Catalog Numbers

300

400

500

1) 5-30A Range 2) 32-50A Range

600

Eg

700

Without Striker 50.8 (2.000")

14.3 (0.563")

15.5 (0.610")

With Striker

5 (0.197")

Size

51 (2.00") 13 (0.511")

• • • •

4 200

1.0 Kp 0.8

300

400

500

600

Eg

700

0.6 0.5 0.4 0.3 0.2

Ib

0.1

30 40 50 60 70 80 90 100% Electrical Characteristics Rated I2t (A2 Sec) Current Minimum Clearing At Watts RMS-Amps Melting Rated Voltage Loss

14 x 51mm (9⁄16" x 2")

14 x 51mm (9⁄16” x 2”)

*Striker range is 600Vdc only • Watts loss provided at rated current. • See accessories on page 243.

59 (2.323") 14.3 (0.563")

Catalog Numbers Without Striker FWP-1A14F FWP-2A14F FWP-2.5A14F FWP-3A14F FWP-4A14F FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F With Striker* FWP-10A14FI FWP-15A14FI FWP-20A14FI FWP-25A14FI FWP-30A14FI FWP-32A14FI FWP-40A14FI FWP-50A14FI

UL

5

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

K

Dimensions - mm (in)

234

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.

1 2 2.5 3 4 5 10 15 20 25 30 32 40 50

10 15 20 25 30 32 40 50

— — — — — 1.6 3.6 8.6 26.0 46.5 58 68 84 200

3.6 8.6 26.0 46.5 58 68 84 200

— — — — — 11.0 38.5 70 230 375 485 600 750 1800 38.5 70 230 375 485 600 750 1800

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Data Sheet: 720025

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

— — — — — 1.5 4 5.5 6 7 9 7.6 8 9

4 5.5 6 7 9 7.6 8 9

High Speed Fuses

Ferrule — FWP 690V/700V (IEC/UL): 1-50A, Striker Optional Without Striker FWP 5-50A: 660V/700V (14 x 51mm) Time-Current Curve 104

6 4 2

103

6 4 2

Virtual Pre-Arcing Time In Seconds

102

FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F

6 4 2

101

6 4 2

100

10–1

6 4

FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F

2 6 4 2

10–2

6 4 2

10–3

6 4 2

10–4

2

4

6

8

2

101

4

6

8

2

102

4

6

8

103

High Speed Fuses

Prospective Current In Amps RMS

Peak Let-Through Curve 104

FWP-50A14F FWP-40A14F FWP-32A14F FWP-30A14F FWP-25A14F

6 4 2

Peak Let-Through Current

103

6 4 2

FWP-20A14F FWP-15A14F FWP-10A14F FWP-5A14F

102

6 4 2

101

101

2

4

6

102

2

4

6

103

2

4

6

104

Prospective Short-Circuit Current Symmetrical RMS

2

4

6

105

2

Data Sheet: 35785307

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

235

High Speed Fuses

Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional FWP (22 x 58mm)

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.

Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustration. Ratings: Volts: — 690Vac (IEC) — 700Vac (UL) FWP with — 500Vac striker option. — 500Vdc (20-100A) Amps: — 20-100A IR: — 200kA RMS Sym. — 50kA @ 500Vdc Agency Information: CE, UL Recognition JFHR2.E91958, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) Electrical Characteristics Total Clearing I2t

The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2

1.4 1.2 1.0 0.9 0.8 0.7 0.6

Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

K

0.5 0.4

0.3 200

300

58.0 (2.283")

400

500

22.2 (0.875")

600

Eg

700

Catalog Numbers Without Striker FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F With Striker FWP-20A22FI FWP-25A22FI FWP-32A22FI FWP-40A22FI FWP-50A22FI FWP-63A22FI FWP-80A22FI FWP-100A22FI

Size 22 x 58mm (7⁄8" x 29⁄32")

22 x 58mm (7⁄8" x 29⁄32")

*IEC/UL Voltage rating 690/700 15.0 (0.591")

With Striker

66 (2.598") 58 (2.283") 5 (0.197")

22.2 (0.874")

UL

5 4

3

200

1.0 Kp 0.8

400

500

600

700

0.6 0.5

0.4

0.3 0.2 0.1

30 40 50

16 (0.630"

• • • •

• • • •

Rated Current RMS-Amps 20 25 32 40 50 63 80 100*

20 25 32 40 50 63 80 100*

60

70

Ib

80 90 100%

Electrical Characteristics I2t (A2 Sec) Minimum Clearing At Melting Rated Voltage

Watts Loss

19.0 34.0 53.5 68 135 280 600 1100

5 6 8 9 9.5 11 13.5 16

19.0 34.0 53.5 68 135 280 600 1100

260 410 605 750 1600 3080 6600 12500

260 410 605 750 1600 3080 6600 12500

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

Data Sheet: 720026

236

300

Eg

Catalog Numbers

Dimensions - mm (in)

Without Striker

1.4 1.2 103 9 8 7 6

Arc Voltage

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

5 6 8 9 9.5 11 13.5 16

High Speed Fuses

Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional Without Striker FWP 20-100A: 660V/700V (22 x 58mm) Time-Current Curve 104

6 4 2

103

6 4 2

102

FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F

6 4 2

Virtual Pre-Arcing Time In Seconds

101 6 4 2 10

0

6 4

FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F

2 10–1 6 4 2 10–2

6 4 2

10–3

6 4 2 2

101

4

6

8

2

102

4

6

8

High Speed Fuses

10–4

103

Prospective Current In Amps RMS

Peak Let-Through Curve 104

FWP-100A22F FWP-80A22F

6

FWP-63A22F

Peak Let-Through Current

4

FWP-50A22F

2 103 6

FWP-40A22F FWP-32A22F

4

FWP-25A22F FWP-20A22F

2 102

102

2

4

6

103

2

4

6

104

2

Prospective Short-Circuit Current Symmetrical RMS

4

6

105

2

Data Sheet: 35785291

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

237

High Speed Fuses

Ferrule — FWK 750V: 5-60A • • • •

FWK 5-30A (20 x 127mm 35-60A (25 x 146mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: — 750Vac — 750Vdc (Time constant = 10-15mS) Amps: — 5-60A IR: — 45kA RMS Sym. Agency Information: CE

• • • •

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

Catalog Numbers Catalog Numbers FWK-5A20F FWK-8A20F FWK-10A20F FWK-15A20F FWK-20A20F FWK-25A20F FWK-30A20F FWK-35A25F FWK-40A25F FWK-50A25F FWK-60A25F

Size 20 x 127mm (13⁄16” x 5”) 25 x 146mm (1” x 53⁄4”)

Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 750Vdc 5 8.5 16 8 50 100 10 95 200 15 100 240 20 125 315 25 400 1100 30 800 2600 35 1300 4300 40 1600 5300 50 3100 12000 60 5900 24000

Recommended fuseholders for 20x127, -2, -3 Recommended fuseclips for 20x127, 1A1837 Recommended fuseclips for 25x146, A3354705

Dimensions - mm (in) Fig. 1: 5-30A 127.0 (5.000")

20.5 (0.807")

16.0 (0.630")

Fig. 2: 35-60A 146.05 (5.75")

25.4 (1")

20.64 (0.813")

Data Sheet: 720039

238

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

High Speed Fuses

Ferrule — FWK 750V: 5-60A FWK 750V: 5-30A (20 x 127mm) 35-60A (25 x 146mm) Time-Current Curve 104 6 4 FWK-15A20F

2

FWK-20A20F

103

FWK-25A20F

6

FWK-30A20F

4

FWK-40A25F FWK-50A25F

2

FWK-60A25F

102 Virtual Pre-Arcing Time In Seconds

6 4 2 101 6 4 2 100 6 4

FWK-5A20F FWK-8A20F

2 10

FWK-10A20F

±1

6 4 2 10

±2

4x10

±3

2

4

6

8

101

2

4

6

8

102

2

4

6

8

103

Prospective Current In Amps RMS

High Speed Fuses

Data Sheet: 720028

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

239

High Speed Fuses

Ferrule — FWJ 1000V: 20-30A FWJ (14 x 67mm)

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%.

Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 1000Vac/800Vdc Amps: — 20-30A IR: — 25kA RMS Sym. — 20kA @ 800Vdc Agency Information: CE, UL Recognized JFHR2.E91958 Electrical Characteristics Total Clearing I2t

1.5

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

1.0

0.15 200

500

800

Dimensions - mm (in) 66.7 (2.626")

14.5 (0.571")

15.9 (0.625")

Fuseclips: • Catalog Number: 5591 (see data sheet 2132)

800 400

200

1.0 Kp 0.8

1000 1400 1800

0.6 0.5 0.4 0.3 0.2 0.1

30 40 50

60

70

Ib

80 90 100%

Catalog Numbers FWJ-20A14F FWJ-25A14F FWJ-30A14F

Size 14 x 67mm 9 ( ⁄16” x 25⁄8”)

• Watts loss provided at rated current. • See accessories on page 243.

• • • •

• • • •

Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 1000V 25 220 33 350 52 450

Rated Current RMS-Amps 20 25 30

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters

Data Sheet: 35785031

240

600

Eg

Catalog Numbers

Eg

1000

1200

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

0.5

UL

1600

Power Losses

K

0.3 0.2

2000

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Watts Loss 9 11 14

High Speed Fuses

Ferrule — FWJ 1000V: 20-30A FWJ 20-30A: 1000V (14 x 67mm) Time-Current Curve 104

6 4 2

103

6 4 2

102

6 4

Virtual Pre-Arcing Time In Seconds

2 101

6 4

FWJ-20A14F FWJ-25A14F FWJ-30A14F

2 100

6 4 2

10–1

6 4 2

10–2

6 4 2

10–3

6 4

101

2

4

6

8 102

2

4

6

High Speed Fuses

2 10–4

8 103

Prospective Current In Amps RMS

Peak Let-Through Curve 104

6

4

FWJ-30A14F FWJ-25A14F FWJ-20A14F

2

Peak Let-Through Current

103

6

4

2

102

6

4

2 101

101

2

4

6

102

2

4

6

103

2

4

6

104

Prospective Short-Circuit Current Symmetrical RMS

2

4

6

105

2

Data Sheet: 35785315

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

241

High Speed Fuses

Ferrule — FWS/FWL 1000Vdc: 2-30A • • • •

FWS 2-15A (20 x 127mm) FWL 20-30A (20 x 127mm) Specifications Description: Ferrule style full range fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 1200Vac (FWL 20-30A) — 1400Vac (FWS 8-15A) — 2100Vac (FWS 2-6A) — 1000Vdc (FWL/FWS 2-30) Amps: — 2-30A IR: — 45kA RMS Sym. — 30kA @ 1000Vdc Agency Information: CE, IEC 60077

• • • • • •

Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks

Typical Applications DC Common bus DC Drives Power converters/rectifiers Reduced voltage starters Traction aux circuits Capacitor protection

FWL/FWS 2-30A: 1000Vdc 2-30A (20 x 127mm) Time-Current Curve

Catalog Numbers Catalog Numbers FWS-2A20F FWS-6A20F FWS-8A20F FWS-10A20F FWS-12A20F FWS-15A20F FWL-20A20F FWL-25A20F FWL-30A20F

Size 20 x 127mm (13⁄16” x 5”) 20 x 127mm (13⁄16” x 5”)

Electrical Characteristics Rated I2t (A2 Sec) Current Clearing RMS-Amps Pre-arc at 1000Vdc 2 0.8 2.4 6 27 81 8 64 192 10 118 277 12 170 380 15 209 500 20 675 1550 25 1200 2760 30 1850 4300

• ADD “I” to catalog number for indicating version. • Enclosed finger-safe fuse holder – CH127 • See accessories on page 243. • Watts loss provided at rated current.

Dimensions - mm (in) 127.0 (5.000")

Watts Loss 4.4 6.7 7.6 3.0 3.4 5.0 5.9 6.5 7.5

20.5 (0.807")

16.0 (0.630")

Indicating Version – Dimensions - mm (in) 8.0 (0.315") 127.0 (5.000")

20.5 (0.807")

2.0

16.0 (0.630")

Data Sheet: 720040

242

2.0 (0.079")

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

High Speed Fuses

Ferrule Fuse Accessories Fuse Blocks

Fuse Holders Specifications Catalog Symbol: CH Series Description: DIN-Rail mount fuse holders Agency Information: UL File E14853, Guide IZLT Listed, IZLT2 Recognized CSA: File 47235, CHPV and CHM - Class 6225-30, CHCC - Class 6225-01 Ratings: 600V/30A (UL) 690V/32A (IEC) Features and Benefits • Finger-safe design - No exposed contacts • DIN-Rail mount (35mm) - Fits standard mounting rails • Optional open fuse indication lights tells fuse status at a glance • Handle/fusepuller easily installs and removes fuses • Available in single and multi-pole configurations • Wire ready lugs and spade terminal connections save installation time • CE marking • Available up to 1000Vdc • PLC device available for remote monitoring

Specifications Catalog Symbol: J70100, J70032 Description: Fuse blocks for 22x58mm & 14x51mm fuses. Ratings: Volts: — 700Vac/dc Amps: — 32-100A Withstand: — 200kA RMS Sym. Agency Information: CE, UL Recognized, Guide IZLT2, File E14853 Flammability Rating: UL 94V0 Catalog Numbers Catalog Numbers

Fuse Size

J70032-2CR

14x51

J70100-2CR

22x58 22x58

J70032-1CR J70032-3CR J70100-1CR J70100-3CR

32

Poles

100

1

Amps 32 32

100 100

1 2 3 2 3

Max Wire Size #2 #2 #2 #2 #2

Terminations Box Lug w/ Box Clip Lug w/ Retaining Retaining Clip

#2

Typical Applications • Switchboard panel, control consoles, small motors, transformers, and similar applications

High Speed Fuses

Recommended Cooper Bussmann Fuse Types Class CC North American Class CC Fuses - LP-CC, FNQ-R, KTK-R 10 x 38 North American Midget Fuses - FNQ, KTK, AGU, BAF, BAN, FNM, FWA, FWC, & PV 14 x 51 FWX, FWH, FWP & NON 22 x 58 FWP

See pages 274-280 for CH Series fuse holder information.

Data Sheet: 2053

Data Sheet: 1211

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

243

High speed fuses

Faster lead-time. Better protection. More energy efficient.

244