OCCUPANCY SENSOR FOR ON/OFF CONTROL TIMED OVERRIDE FROM TIMECLOCK.
S
1 GAS SOLENOID VALVE TO COOKING APPLIANCES AND ANSUL SYSTEM NORMALLY CLOSED
1
EXHAUST FAN CONTROL
ANALOG INPUT ANALOG OUTPUT
BDD C
BACKDRAFT DAMPER CONTROLLER
CC CD CHR CHS COND CSEN DI DO DP DPT EA EP
COOLING COIL CONTROL DAMPER CHILLED WATER RETURN CHILLED WATER SUPPLY CONDENSATE OVERFLOW CURRENT SENSOR DIGITAL INPUT DIGITAL OUTPUT DIFFERENTIAL PRESSURE SWITCH DIFFERENTIAL PRESSURE TRANSMITTER EXHAUST AIR ELECTRICAL-PNEUMATIC TRANSDUCER /SWITCH
FCU FAP FS F FT FR HT HC HH HWR HWS IR
FAN COIL UNIT FIRE ALARM PANEL FLOW SWITCH FILTER ASSEMBLY FLOW TRANSDUCER FREEZESTAT HUMIDITY TRANSMITTER HEATING COIL HIGH LIMIT HUMIDITY SWITCH HOT WATER RETURN HOT WATER SUPPLY INTERLOCK RELAY
M MIN OA PC PE
MOTORIZED CONTROL MINIMUM OUTSIDE AIR PREHEAT COIL PNEUMATIC ELECTRIC SWITCH
PT RA RF
PRESSURE TRANSMITTER RETURN AIR RETURN FAN
S SA SD SF SPT SR
SPACE TEMPERATURE SENSOR SUPPLY AIR SMOKE DETECTOR (BY ELECTRICAL) SUPPLY FAN STATIC PRESSURE TRANSMITTER SWITCHING RELAY
T TT TTA
THERMOSTAT TEMPERATURE TRANSMITTER TEMPERATURE TRANSMITTER W/AVERAGING BULB VALVE VARIABLE FREQUENCY DRIVE VELOCITY SENSOR WET BULB TEMPERATURE TRANSMITTER
V VFD VS WBT
ARCHITECT OF RECORD
NO SCALE silhouette design architecture
S
1
SEQUENCE OF OPERATION GENERAL NOTES:
FIRE ALARM FROM EMCS BI
566 W. Adams Street Suite 500 Chicago, Illinois 60661 312.258.0025 www.silhouettedesignarchitecture.com
GENERAL: SA
START/STOP S
HOOD SWITCH VIA TEMPERATURE SENSOR FURNISHED BY FOOD SERVICE CONTRACTOR (INSTALLED BY DIV 26). TEMPERATURE SENSOR WITHIN HOOD SHALL ENERGIZE ROOFTOP UNIT AND EXHAUST FAN UPON DETECTION OF HEAT IN CONFORMANCE WITH IFGC 505.
3
A.
M
B.
T
1 C. D.
SPACE TEMPERATURE
MUA-1 SHALL BE PROVIDED WITH FACTORY SUPPLIED PACKED CONTROLS. FACTORY CONTROLS SHALL OPERATE INDEPENDENTLY OF BASE BUILDING BMS, UNLESS OTHERWISE INDICATED. MUA-1 CONTROLS SHALL BE PROVIDED WITH FACTORY SET SEQUENCES AND OPERATIONS TO MAINTAIN SPACE TEMPERATURE, PRESSURE AND OPERATE IN THE MODES AS STATED BELOW. MUA-1 TO SHUT DOWN UPON FREEZESTAT ALARM. CHILLED WATER COIL TO HAVE MANUAL RESET FOR LOW TEMP LIMIT OF 38 °F.
NORMAL OPERATION (NO COOKING CONDITION): VAV BOX CONTROL SEQUENCE A.
OCCUPIED MODE : UPON A RISE IN SPACE TEMPERATURE, THE UNIT SHALL MODULATE TO PROVIDE UP TO ITS MAXIMUM CFM TO MAINTAIN SPACE SETPOINT. UPON A DECREASE IN SPACE TEMPERATURE, THE UNIT SHALL MODULATE DOWN TO ITS MINIMUM COOLING CFM TO MAINTAIN SPACE SETPOINT. UPON A FURTHER DECREASE IN SPACE TEMPERATURE, THE UNIT SHALL MODULATE DOWN TO IT'S FIXED HEATING MINIMUM CFM.
POLLUTION CONTROL UNIT CONTROL NO SCALE
B.
THE HOOD EXHAUST FAN IS OFF. THE OUTDOOR AIR MECHANICAL DAMPER SHALL BE CLOSED. VAV-1 SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE. EF-2 SHALL RUN CONTINUOUSLY.
CHICK-FIL-A
ASSOCIATED MUA-1
AI
COOKING OPERATION (HOOD ON): UNOCCUPIED MODE : UNIT'S VOLUME DAMPER SHALL BE FULLY CLOSED. TEMPERATURE SETBACK TO 65°F/85°F FOR COOLING/HEATING SETBACK.
A.
EXHAUST FAN EF-1 SHALL BE INTERLOCKED TO OPERATE VIA TEMPERATURE SENSOR WITHIN HOOD. FROM AN AUXILIARY CONTACT, MUA-1 OUTSIDE AIR DAMPER SHALL OPEN TO FIXED POSITION. VAV-1 SHALL BE CONTROLLED BY THE SPACE TEMPERATURE SENSOR. 1. OCCUPIED COOLING: MUA-1 SHALL RUN CONTINUOUSLY, THE HEATING COIL SHALL BE LOCKED OUT, AND COOLING COIL CONTROL VALVE SHALL MODULATE THE LEAVING AIR TEMP TO MAINTAIN DUCT OUTLET TEMPERATURE SETPOINT OF 75F (ADJUSTABLE). 2. OCCUPIED HEATING: MUA-1 SHALL RUN CONTINUOUSLY, COOLING WILL BE LOCKED OUT, HEATING COIL VALVE SHALL MODULATE THE LEAVING AIR TEMPERATURE TO MAINTAIN DUCT OUTLET TEMPERATURE SETPOINT OF 65F (ADJUSTABLE). B. EF-2 SHALL RUN CONTINUOUSLY.
FIRE MODE : UNIT SHALL SHUT DOWN UPON RECEIVING A GENERAL ALARM FROM BUILDING FIRE ALARM SYSTEM.
2
VAV BOX CONTROL NO SCALE
FIRE MODE: A. B. C. D. E.
DIA PROJECT NO: CFAB1501 CONCOURSE B CENTRAL CORE DENVER INTERNATIONAL AIRPORT 8900 PENA BLVD DENVER, CO 80249-6363
GREASE FILTERS
MUA-1 SHALL DE-ENERGIZE UPON ACTIVATION OF SPACE FIRE ALARM FROM ANSUL FIRE SUPPRESSION SYSTEM OR DUCT DETECTOR. EF-1 AND EF-2 SHALL CONTINUE TO RUN. GAS SOLENOID VALVE SERVING THE SPACE SHALL CLOSE. CHILLED AND HEATING HOT WATER VALVES SHALL CLOSE. VAV-1 AND VAV-2 SHALL DE-ENERGIZE UPON ACTIVATION OF SPACE FIRE ALARM.
1 NOTE: THIS CONTROL DIAGRAM IS INTEGRAL WITH FACTORY PACKAGED CONTROLS, AND DOES NOT COMMUNICATE WITH THE BASE BUILDING BMS, UNLESS OTHERWISE NOTED.
BUILDING FIRE MODE:
1
DISCHARGE AIR TEMPERATURE
DISCHARGE AIR TEMPERATURE
AI
AI
A. VAV-1 AND VAV-2 SHALL DE-ENERGIZE UPON ACTIVATION OF BUILDING FIRE ALARM SIGNAL. B. EF-1, EF-2, AND MUA-1 SHALL CONTINUE OPERATION OF CURRENT MODE.
SMOKE DETECTOR
1
AI
A.
FILTER FILTER CHW
HHW OA
SA C
DATE CKD
90% SUBMITTAL
12/11/15
100% SUBMITTAL
01/18/16
ANSUL FIRE PROTECTION SYSTEM:
T
FR
ISSUE RECORD NO. BY PURPOSE
B.
C
ANSUL FIRE PROTECTION SYSTEM, BY OTHER DIVISION, SHALL SEND A SIGNAL THROUGH THE FIRE PROTECTION SYSTEM TO SHUT DOWN RTU SUPPLY FAN. EXHAUST FANS TO BREAK STANDARD OPERATING INTERLOCK WITH RTU AND CONTINUE IN EXHAUST MODE. ALARM SIGNAL FROM FROM ANSUL PANEL SHALL BE COPIED AT THE BMS. UPON ACTIVATION OF THE ANSUL FIRE PROTECTION SYSTEM, POWER SHALL BE CUT OFF TO THE GAS SOLENOID VALVE (CLOSED). ADVISORY SIGNAL TO BE SENT TO DIA FIRE ALARM PANEL.
UNOCCUPIED MODE:
S/S TI
TI
TI
TI
AO
BO
SUPPLY FAN START / STOP
OUTSIDE AIR DAMPER
A. B. C. D.
THE HOOD EXHAUST SYSTEM IS OFF. MUA-1 IS OFF. VAV-1 UNIT SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE. EF-2 SHALL DE-ENERGIZE.