IN
Commercial Specification Grade Dual Tech Occupancy Sensor FEATURES • California Title 24 compliant. • Self-adjusting Auto Off delay of 10 minutes to 30 minutes. • Dual technology Ultrasonic & Passive Infrared (PIR) sensing eliminates false activations or deactivations for additional energy savings. • Self-adapting sensors with Instinct Technology drastically simplify and reduce a contractor’s installation and adjustment time period. • Sensors will automatically reset time delay to a 10-minute default when left at the installer setting.
• Microprocessor-based airflow tolerant technology features patented rate of change technology, making these sensors ideal for spaces with increased airflow due to higher occupancy levels. • Exclusive Energy-Saver mode for 2-level lighting environments. • BAS compatible. • Manual ON/OFF feature when wired to a normally open momentary pushbutton switch. • Complete no-gap coverage; NEMA WD7 Guide robotic method utilized to verify coverage patterns. • Paintable off-white ABS molded housing.
INSTINCT
6.5" (154mm) 3.75" (100mm)
AHOMC-DT-0701-R
Wire Leads – Ceiling Mount Frequency
Coverage Area
Description
Catalog No.
32 kHz
300-700 sq. ft. (27.87-65.03 sq. m)
180º One Way Dual Tech Occ. Sensor, Isolated Relay
■ AHOMC-DT-0701-R
Coverage Areas
AHOMC-DT-0701-R 300-700 sq. ft. Max. mounting height: 12 ft.
TESTING & CODE COMPLIANCE
MATERIAL CHARACTERISTICS
• Listed to UL 508 • California Title 24 Energy Code compliant
• Environmental: Flammability meets UL94 requirements; V0 rated • Temperature Rating: 15ºC to 26ºC (60ºF to 80ºF) www.cooperwiringdevices.com
TM
1.46" (37mm)
IN
Occupancy Sensor Specification & Performance Data
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Ceiling Mount Occupancy Sensor with InstinctTM Technology
Dual Technology 10-30 V/DC
Application The Dual Tech sensor’s combination of Ultrasonic and Passive Infrared technologies with Instinct Technology offers the most complete sensing equipment available today. This pairing helps eliminate false activations or deactivations for additional energy savings. The OMC-DT sensors are also equipped with Instinct Technology which provides a revolutionary adaptive and airflow tolerant technology, making them ideal for spaces which have increased airflow due to higher occupant levels. Dual Tech sensors with Instinct Technology drastically simplify and reduce a contractor’s installation and adjustment time period. These self-adapting, dual technology sensors truly offer some of the most advanced technology available. These sensors are ideal for offices, conference rooms, storage areas, common areas, hallways and other indoor office spaces. Device Type
Ceiling Mount Occupancy Sensor, AHOMC-DT Series
Wiring Type
Pre-stripped wire leads
Specifications: Environmental
Testing & Code Compliance
ptional Switch for Manual ON/OFF apability. Use 3A 4VDC Momentary Wall Switch.
• Listed to UL 508 • California Title 24 Energy Code compliant
Warranty
5-year limited warranty
Flammability
Meets UL 94 requirements; V0 rated
Temperature Rating m-Energy Saver Option/Dual Level Operation
Switchpack Wiring Diagram
Optional Switch for Manual ON/OFF Capability. Use 3A 24VDC Momentary Wall Switch.
15ºC to 26ºC (60°F to 80°F)
Humidity Rating
Relative humidity less than 95%, non-condensing
Operating Areas
For indoor ceiling use only
Specifications: Materials
Specifications: Operation
Specifications: Mechanical
Specifications: Electrical
Power Requirements 10-30 VDC from switchpack Maximum Current Per Sensor
25mA
Output
Open collector output to switch up to 10 switchpacks
Isolated Form C Relay
Available in -R models; ratings: 1A, 30 VDC/VAC
Available Frequencies
32 kHz
Detection Technology
Passive Infrared and Ultrasonic
Mounting