Certificate
UK G83/1
The results of tests performed according to reference standard UK G83/1 are summarized in this certificate. Power-One Italy S.p.a. declares that the units set for UK G83/1 operations are characterized by the following features: · The internal specification and parameters are set to be compliant with UK G83/1 engineering requirements. · All units have identical internal parameters setting. · These parameters cannot be changed without the usage of password protected tool. SSEG DETAILS (Small-Scale Embedded Generator) SSEG Type Reference: SSEG Model Reference:
PHOTO-VOLTAIC GRID TIED INVERTER PVI-6000-TL-OUTD PVI-6000-TL-OUTD-S PVI-6000-TL-OUTD-W PVI-5000-TL-OUTD PVI-5000-TL-OUTD-S PVI-5000-TL-OUTD-W
Maximum export capability (SSEG rating less parasitic load)
6200 W (PVI-6000-TL-OUTD and derived models) 5050 W (PVI-5000-TL-OUTD and derived models)
Nominal Output AC Power
6000 W (PVI-6000-TL-OUTD and derived models) 5000 W (PVI-5000-TL-OUTD and derived models)
MANUFACTURER AND TEST HOUSE DETAILS Name: Address:
Telephone number: Fax number: E-mail address
Power-one Italy S.p.A. - R.& D. Department Via S. Giorgio 642, 52028 Terranuova Bracciolini Arezzo - Italy +39-055-91951 +39-055-9195248
[email protected] TEST RESULTS SUMMARY Power Quality: · Harmonic Current Emission as per EN-61000-3-12 · Voltage Fluctuation and Flickers as per EN-61000-3-3 · DC Injection as per UK G83/1 · Power Factor as per UK G83/1 Protection: · Under/Over Frequency Tests · Under/Over Voltage Tests · Reconnection Times · Loss of Main – (Anti-Islanding) Tests as per UK G83/1 Power-One Italy S.p.a. Terranuova Bracciolini,
September 16, 2013 Robert White (Director Safety & Environmental Compliance)
File: PVI-6000(5000)-TL-OUTD_Certificate_UK G83_Rev_16-Sep-2013.doc
www.power-one.com
This document and the contents herein are property of Power-One. It shall not be changed, or altered in any way. PowerOne Italy Via S. Giorgio, 642 52028 Terranuova Bracciolini Arezzo – Italy Phone +39 05591951 Fax +39 0559195248
Page 1 of 5
TEST RESULTS DETAILS – TYPE VERIFICATION TEST SHEET POWER QUALITY HARMONICS CURRENT EMISSIONS PVI-6000-TL-OUTD, Harmonics Current Emission as per EN-61000-3-12 Value of short circuit power SSC=0.198 MVA @ RSCE=33 Harmonic 2rd [%A] 3rd [%A] 4rd [%A] 5rd [%A] Limit 8.000 21.6000 4.000 10.700 Result L1 0.058 0.2062 0.052 0.099 Harmonic 9rd [%A] 10rd [%A] 11rd [%A] 12rd [%A] Limit 3.800 1.600 3.100 1.333 Result L1 0.039 0.029 0.040 0.021
6rd [%A] 2.667 0.038 13rd [%A] 2.000 0.031
7rd [%A] 7.200 0.058 THD [%A] 13.000 0.405
8rd [%A] 2.000 0.018 PWHD [%A] 22.000 0.861
PVI-5000-TL-OUTD, Harmonics Current Emission as per EN-61000-3-12 Value of short circuit power SSC=0.165 MVA @ RSCE=33 Harmonic 2rd [%A] 3rd [%A] 4rd [%A] 5rd [%A] Limit 8.000 21.6000 4.000 10.700 Result L1 0.032 0.2100 0.058 0.114 Harmonic 9rd [%A] 10rd [%A] 11rd [%A] 12rd [%A] Limit 3.800 1.600 3.100 1.333 Result L1 0.026 0.024 0.034 0.014
6rd [%A] 2.667 0.061 13rd [%A] 2.000 0.034
7rd [%A] 7.200 0.051 THD [%A] 13.000 0.464
8rd [%A] 2.000 0.040 PWHD [%A] 22.000 1.106
DC INJECTION PERFORMACES PVI-6000-TL-OUTD, DC injection as per UK G83/1 Limit 0.02 [Adc] tested at three power levels Test Level [%Pout] Test value L1 [Adc]
10% 0.006
50% 0.012
100% 0.019
PVI-5000-TL-OUTD, DC injection as per UK G83/1 Limit 0.02 [Adc] tested at three power levels Test Level [%Pout] Test value L1 [Adc]
10% 0.011
50% 0.015
100% 0.015
POWER FACTOR PERFORMANCES PVI-6000-TL-OUTD, Power Factor as per UK G83/1 0.95 lag -0.95 (over than 20% of Power) lead at three voltage levels and three power levels Test Level [Vac] 218.2 230.0 Test value [10% Pout] 0.995 0.996 Test value [50% Pout] 0.999 0.999 Test value [100% Pout] 0.998 0.999
256.4 0.997 0.998 0.997
PVI-5000-TL-OUTD, Power Factor as per UK G83/1 0.95 lag -0.95 (over than 20% of Power) lead at three voltage levels and three power levels Test Level [Vac] 218.2 230.0 Test value [10% Pout] 0.947 0.925 Test value [50% Pout] 0.996 0.995 Test value [100% Pout] 0.999 0.998
256.4 0.947 0.993 0.998
File: PVI-6000(5000)-TL-OUTD_Certificate_UK G83_Rev_16-Sep-2013.doc
www.power-one.com
This document and the contents herein are property of Power-One. It shall not be changed, or altered in any way. PowerOne Italy Via S. Giorgio, 642 52028 Terranuova Bracciolini Arezzo – Italy Phone +39 05591951 Fax +39 0559195248
Page 2 of 5
VOLTAGE FLUCTUATION AND FLICKERS PVI-6000-TL-OUTD, Voltage Fluctuation and Flickers as per EN-61000-3-3 Voltage Pst [%] Pit [%] D(t)>3% Disturbance Limit 1.000 0.650 0.500 Test value 0.253 0.25 0.1 PVI-5000-TL-OUTD, Voltage Fluctuation and Flickers as per EN-61000-3-3 Voltage Pst [%] Pit [%] D(t)>3% Disturbance Limit 1.000 0.650 0.500 Test value 0.253 0.25 0.1
dc [%]
dmax [%]
3.300 0.1
4.000 1.05
dc [%]
dmax [%]
3.300 0.1
4.000 1.05
POWER LIMITATIONS PVI-6000-TL-OUTD, Power limitations of input and output Pin CH1 Pin CH2 Iin CH1 Iin CH2 P Q [W] [W] [Adc] [Adc] [W] [var] Limit 4200 4200 20.00 20.00 6200 6670 Test value 4335 4247 20.1 20.1 6278 -
S [VA] 6670 -
Id [Aac] 30.00 30.50
Iq [Aac] 30.30 -
I [Aac] 30.30 30.50
PVI-5000-TL-OUTD, Power limitations of input and output Pin CH1 Pin CH2 Iin CH1 Iin CH2 [W] [W] [Adc] [Adc] Limit 4200 4200 20.00 20.00 Test value 4335 4245 20.1 20.1
S [VA] 5560 -
Id [Aac] 27.00 27.5
Iq [Aac] 27.30 -
I [Aac] 27.30 27.5
P [W] 5050 5123
File: PVI-6000(5000)-TL-OUTD_Certificate_UK G83_Rev_16-Sep-2013.doc
Q [var] 5560 -
www.power-one.com
This document and the contents herein are property of Power-One. It shall not be changed, or altered in any way. PowerOne Italy Via S. Giorgio, 642 52028 Terranuova Bracciolini Arezzo – Italy Phone +39 05591951 Fax +39 0559195248
Page 3 of 5
PROTECTION -PVI-6000-TL-OUTD- -PVI-5000-TL-OUTDUNDER FREQUENCY TESTS UK G83 Limit Settings Frequency [Hz] Time [s] Frequency [Hz] 47.00 0.50 47.05
Time [s] 0.42
Results Frequency [Hz] Time [s] 47.05 0.39
OVER FREQUENCY TESTS UK G83 Limit Settings Frequency [Hz] Time [s] Frequency [Hz] 50.50 0.50 50.45
Time [s] 0.42
Results Frequency [Hz] Time [s] 50.50 0.36
Vϕ-n nom = 230.0 Vac Under Voltage < L1-N
UNDER VOLTAGE TESTS UK G83 Limit Settings Voltage [Vac] Voltage [Vac] Time [s] 207.0 213.9 1.50
Time [s] 1.30
Results Voltage [Vac] Time [s] 214.3 1.35
Vϕ-n nom = 230.0 Vac Over Voltage > L1-N
OVER VOLTAGE TESTS UK G83 Limit Settings Voltage [Vac] Voltage [Vac] Time [s] 264.5 261.7 1.50
Time [s] 1.30
Results Voltage [Vac] Time [s] 262 1.36
Fnom=50.00 Hz Under Frequency
Frequency max [Hz] Frequency min [Hz] Voltage max [Vac] Voltage min [Vac]
Minimum Value Limit [s] Actual setting [s] Recorded value [s]
Method used Output power Level UK G83/1 Limit [s] Trip value [s]
BEFORE CONNECTION UK G83 Limit 50.50 47.00 264.5 207.0
Settings 50.45 47.05 261.7 213.9
RECONNECTION TIMES After U/O Voltage After U/O Frequency 180 180 180 180 185 189
Results 50.43 47.05 261.1 215
After Loss of Main 180 180 185
After any other fault 60 60 70
LOSS OF MAIN TESTS Rate of change of frequency and active power variation 10% 55% 100% 5 5 5 0.305 0.577 0.585
File: PVI-6000(5000)-TL-OUTD_Certificate_UK G83_Rev_16-Sep-2013.doc
www.power-one.com
This document and the contents herein are property of Power-One. It shall not be changed, or altered in any way. PowerOne Italy Via S. Giorgio, 642 52028 Terranuova Bracciolini Arezzo – Italy Phone +39 05591951 Fax +39 0559195248
Page 4 of 5
SSEG Short Circuit Current Contribution Test RMS Value over 1 Period (Cycle) Peak Current
35.7 473.3
[Aac] [A]
SELF MONITORING – SOLID STATE SWITCHING Not applicable because electro-mechanical relays are used ACCURACY Voltage reading accuracy [%] Frequency reading accuracy [%] Current reading accuracy [%] Power reading accuracy [%] Time reading accuracy [s]
= +/- 1 = +/- 0.05 = +/-2 = +/-2 = +/-0.08
−END OF DOCUMENT−
File: PVI-6000(5000)-TL-OUTD_Certificate_UK G83_Rev_16-Sep-2013.doc
www.power-one.com
This document and the contents herein are property of Power-One. It shall not be changed, or altered in any way. PowerOne Italy Via S. Giorgio, 642 52028 Terranuova Bracciolini Arezzo – Italy Phone +39 05591951 Fax +39 0559195248
Page 5 of 5