Class RK5 Fuses Bussmann - Dual Element, Time Delay Dual Element, Time-Delay Fuse -- 10 seconds (minimum) at 500% rated amps, Current-Limiting *ECSR replaces DLSR Volts: 600Vac (or less), 200Vdc Amps: 1-600A IR: 200kA RMS Sym Agency Information: CE, Std. 248-12, Class RK5, UL Listed, Guide JDDZ, File E162363, CSA Certified, HRCI-R C22.2 No. 248.12, Class 1422-02, File 53787 Typical Applications: • AC power distribution system mains, feeders, and branch circuits Industrial Control • Protection of motors and motor branch circuits • Protection of transformers and other inductive loads • All general-purpose applications including lighting, heating and othernon-inductive loads Features: • True dual-element construction allows sizing of 125% FLA for motor backup protection. • Superior overload and cycling capabilities. • Current limiting provides component short-circuit protection.
Description 600V Dual Element Time Delay 5A 600V Dual Element Time Delay 10A 600V Dual Element Time Delay 15A 600V Dual Element Time Delay 20A 600V Dual Element Time Delay 25A 600V Dual Element Time Delay 30A 600V Dual Element Time Delay 35A 600V Dual Element Time Delay 40A 600V Dual Element Time Delay 45A 600V Dual Element Time Delay 50A 600V Dual Element Time Delay 60A 600V Dual Element Time Delay 70A 600V Dual Element Time Delay 80A 600V Dual Element Time Delay 90A 600V Dual Element Time Delay 100A 600V Dual Element Time Delay 125A 600V Dual Element Time Delay 150A 600V Dual Element Time Delay 200A