OVERVIEW The CMRB 9 2P Series occupancy sensor mounts directly to the end of a fluorescent fixture and utilizes the industry’s leading Passive Infrared (PIR) technology to provide excellent coverage for rooms without obstructions. The sensor is line powered and can switch loads directly without the need for a power pack. With two line power switching relays, A/B switching or control of multiple loads can be handled by one device. Mounting heights of 8 to 15 ft (2.44 to 4.57 m) provide 10 to 20 ft (3.05 to 6.10 m) radial coverage. When mounting above 15 ft (4.57 m) the CMRB 6 2P Series sensor is a better option; and when mounting below 8 ft (2.44 m) or for greater radial coverage the CMRB 10 2P Series sensor should be considered. Additionally, for areas with obstructions the CMRB PDT 9 2P should be used. FEATURES • 100% Digital PIR Detection, Excellent RF Immunity • Two Self-Contained Relay, No Power Pack Needed • No Minimum Load Requirements • Interchangeable Hot & Load Wires, Impossible to Wire Backwards • Push-Button Programmable • Adjustable Time Delays • No Field Calibration or Sensitivity Adjustments Required • Convenient Test Mode • 100 hr Lamp Burn-in Timer
CMRB 9 2P
Standard Range 360° Sensor
SPECIFICATIONS Size: 3.63” H x 3.63” W x 1.50” D (9.22 cm x 9.22 cm x 3.81 cm)
Warranty Five-year limited warranty. Complete warranty terms located at: www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx Note: Actual performance may differ as a result of end-user environment and application. Specifications subject to change without notice. C
ORDERING INFORMATION CMRB 9 2P Series CMRB 9 2P
Example: CMRB 9 2P DZ LT Photocell
Standard Range 360° Sensor
US LISTED
[blank] None P Inhibit Photocell DZ Dual Zone Photocell
9 STANDARD RANGE 360º LENS • Best choice for small motion (e.g. hand movements) detection • Viewing angle of 56º in a 360º conical shaped pattern • Provides 12 ft (3.66 m) radial coverage when mounted to standard 9 ft (2.74 m) ceiling • 8 to 15 ft (2.44 to 4.57 m) mounting heights provide 10 to 20 ft (3.05 to 6.10 m) radial coverage
TOP VIEW
SIDE VIEW 0 ft
9
3.7
12
1.8
6
0m
0 ft
1.8
6
3.7
12
0m
2.7 3.7
1.8
0m
1.8
3.7
12
6
0 ft
6
12
WIRING (DO NOT WIRE HOT) STANDARD WIRING BLACK* - Line Input 1 BLACK* - Load Output 1 BLUE** - Line Input 2 BLUE** - Load Output 2 WHITE - Neutral
} }
*BLACK wires can be reversed
N
120 OR 277 VAC
**BLUE wires can be reversed LOAD
H
120 OR 277 VAC
H BLU
BLK
BLU
BLK
N
SWITCH
LOAD
WHT
347 VAC OPTION (347)
Black wires are replaced w/ Red wires
INITIAL POWER UP
The sensor’s relays are shipped in a latched closed position so the lights will come on upon initial power-up. If the lights do not immediately turn on (initial installation only) the latching relays opened during shipment and will close within 30 secs. Note: If the sensor loses power, the internal relays will latch to on.