VARI-PRIME TM Control Technology Laars VARI-PRIMETM flow control matches the modulation rate of a MagnaTherm’s combustion system to the rate of a variable speed boiler pump. This unique on board control allows the MagnaTherm boiler to mirror the heating system’s profile during varying load conditions and optimize overall efficiency.
COMMERCIAL HIGH EFFICIENCY
Boiler pumps are typically sized for the maximum flow that a boiler needs, but boilers rarely operate at maximum capacity. A pump’s power consumption can drop by as much as 50% with only a 20% reduction in speed. By replacing a boiler’s typical on/off pump with a VARI-PRIMETM equipped MagnaTherm control and variable speed pump, over a thousand dollars in boiler pump watt usage can be saved per year. The payback for the variable speed pump setup can be realized in as little as one year!
Condensing Boiler and Volume Water Heater
The combined potential energy savings of the MagnaTherm’s high efficiency combustion coupled with the VARI-PRIMETM control system is huge. Only the Laars MagnaTherm with built in VARI-PRIMETM controls can offer such savings in one package!
with VARI-PRIME TM
Pump Control On-Board
VARI-PRIMETM Pump Control Energy Savings Example Typical boiler pump energy use seen over a full heating season located in upstate New York (September through April). When an On/Off Boiler Pump is used - kWH consumed When the Laars VARI-PRIME is used - kWH consumed
18,773 5,540
Annual VARI-PRIMETM kWH savings Annual Percent Pump Electrical Savings Annual Dollar Savings*
13,233 70% $1,417
View our entire product line at www.Laars.com
A Three Million BTU/hr MagnaTherm using VARI-PRIMETM pump control and a Goulds 22SH variable speed boiler pump were used in this example. *2013 US Average of 11 cents per kWH used, source US Energy Information Administration. See Laars VARI-PRIMETM white paper 9185 for complete details.
Lead Lag Cascading of up to 8 MagnaTherms The advanced MagnaTherm control system also includes a cascading feature that allows for up to eight units to be lead lagged together. This results in a modulating heating cell of up to 32 million BTU/hr with a combined 40:1 turndown. Also included is an auto rotation function that periodically changes lead boiler to evenly spread service between all boilers. Communication with Building Automation Systems happens seamlessly via a built-in Modbus protocol included with all MagnaTherm boilers. The Laars Gateway is available for use with BacNET and LON networks.
HLW
1.6, 2.0, 2.5, 3.0, 3.5 and 4.0 MILLION BTU/HR
• Fax 800.559.1583 (Customer Service and Product Support) 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130 800.900.9276
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1504 Document 1288C
95% Certified Thermal Efficiency Indoor and Outdoor Installation Laars Heat Exchanger Design
THE
MAGNATHERM
Getting to know the MAGNATHERM
Sizing Data, for the MAGNATHERM
CONDENSING BOILER & VOLUME WATER HEATER
Dimensional Data
Dimensional Data
Large Color Touch Screen
A Perfect Balance of Size, Form and Function Every commercial heating system is unique and as such requires a boiler that can respond to system fluctuations, while maintaining the energy conservation standards held by today’s building owners. Such a boiler now exists in the innovative Laars MagnaTherm.
A multi-color, simple to use smart touch screen display allows you to fully control and setup the MagnaTherm.
On board every boiler is MagnaTherm’s unique VARI-PRIMETM control that allows building owners to save thousands of dollars over the life of the boiler due to dramatically reduced energy costs versus a typical on/off pump arrangement. Only the Laars MagnaTherm includes the VARI-PRIMETM control that balances combustion, air flow and water flow on every boiler! The MagnaTherm’s small footprint, slim vertical design and removable top section help it to fit into tight mechanical rooms. It’s optional electrical packages allow for easy pairing with various field supply voltages. And the large easy-to-navigate color touch screen display results in quick setup and diagnostics and allows up to 8 MagnaTherms to be controlled in a cascading boiler bank.
Features: • • • • • • • • •
Laars designed and built heat exchanger Stylish, modern cabinet design Up to 99% thermal efficiency, condensing operation Reliable, smooth starting hot surface ignition Optimized gas usage for lower energy bills via a 5:1 (20% to 100% input) modulating gas valve Quiet, variable speed blower VARI-PRIMETM, variable speed pump control matches system pump with boiler modulation to optimize efficiency Small footprint compared to others in class Forward mounted low voltage panel for easy wiring and trouble shooting
• Unique, sealed condensate trap does not need to be primed at startup • Single or up to 8 boilers in a cascade installation • Up to 100 feet of vent • M eets the most stringent NOx emission requirements • 439 Stainless Steel Heat Exchanger for increased corrosion resistance • Advanced control system with temperature control, iagnostics, outdoor reset capability, and easy access d for field wiring • 10-year heat exchanger warranty
1600 2000 2500 3000 3500 4000
Removable Top Section An easy-to-remove top blower section makes Dimensional getting intoData tight spaces and elevators a smooth operation! A
Size
Full Access Inches
B
cm
Inches
Inches
3500
34.5
88
96.7 96.7
246 246
52.0 52.0
cm
132 132
Temperature Rise in °F 30°F 35°F 40°F Size Flow Head Loss* Flow Head Loss* Flow Head Loss* The MagnaTherm uses produced and GPM Feet American GPM Feet GPM 439 Feet 14.0 87 10.0withstand 76 8.0 316 1600 SS heat100exchanger materials to the 2000 temperatures 128 23.5 and 109 95 13.6 in extreme caustic17.1 conditions found 2500 158 23.6 136 17.6 119 13.6 high3000 efficiency combustion chambers. 190 34.2 164 25.8 142 18.9 3500 222 30.6 190 23.6 166 18.6 4000 255 38.2 218 28.5 190 22.5
Superior Heat Exchanger Materials
Indoor / Outdoor Installation
VolumeDesign, Water Heater, Water Flow Requirements Slim Small Footprint
The MagnaTherm’s width allows it to fit through standard doorways. Size Flow Rate Temp Rise Headloss* Flow Rate Temp Rise Headloss* GPM 152 152 190 190 222 224
°F 20 25 25 30 30 34
Ft 31.0 33.0 33.7 36.0 30.6 30.0
LPM 525 575 719 719 839 848
°C 11.1 14.0 13.9 17.0 17.0 19.0
Inches 79.8 79.8 87.0 87.0 96.7 96.7
cm 203 203 221 221 246 246
Inches 38.0 38.0 41.5 41.5 52.0 52.0
D cm 96 96 105 105 132 132
Inches 57.5 57.5 60.5 60.5 70.0 70.0
cm 147 147 154 178 178 178
E Water Gas 'Knock-down' Height Connection Connection Inches cm Groove Lock (NPT) 60.8 154 3" 2" 60.8 154 3" 2" 71.0 180 3" 2" 71.0 180 3" 2" 80.8 205 4" 2" 80.8 205 4" 2"
Condensate
Trap Line 1" 1" 1" 1" 1" 1"
Minimum Gas Boiler Water Heater Vent Vent Product Weight Operating Weight Shipping Weight Supply Thermal Efficiency Thermal Efficiency Diameter Length cm MBH KW MBH KW % % Lbs Kg Lbs Kg Lbs Kg " w.c. Pa in (cm) ft (m) Temperature Rise in °F Temperature Rise in °C 1600 147 1599 469 1512 443 95.0 96 1390 630 1562 709 1590 721 4 996 6 (15) 100 (30.5) 30°F 35°F 40°F 17°C 19°C 22°C 147 2000 1999 586 1883 552 95.0 96 1390 630 1562 709 1590 721 4 996 8 (20) 100 (30.5) Size Size Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Los 154 2500 2499 732 2374 696 95.0 96 1785 810 2039 925 1985 900 4 996 8 (20) 100 (30.5) GPM Feet GPM Feet GPM Feet LPM m LPM m LPM m 178 3000 3000 879 2814 825 95.0 95 1785 810 2039 925 1985 900 4 996 10 (25) 100 (30.5) 1600 1600 100 14.0 87 10.0 76 8.0 379 4.3 329 3.0 288 2.5 Dimensional Data Sizing Data 178 3500 3500 1025 3317 972 95.0 96 2278 1033 2742 1244 2478 1124 4 996 10 (25) 100 (30.5) 2000 128 23.5 109 17.1 95 13.6 2000 485 7.2 413 5.2 360 4.2 178 4000 4000 1172 3724 1091 95.0 96 2278 1033 2742 1244 2478 1124 4 996 12 (30) 100 (30.5) 2500 158 23.6 136 17.6 119 13.6 2500 599 7.0 514 5.0 449 4.1 E Condensate Water Gas A 190 C25.8 Input Rate Outp Size 34.2 B 164 142 D 18.9'Knock-down' Height Connection Connection 3000 719 10.4 621 7.9 538 5.8 Size 3000 Trap 3500 222 30.6 190 23.6 166 18.6 3500 839 9.0 719 7.0 629 6.0 Inches cm Inches cm Inches cm Inches cm Inches cm Groove Lock (NPT) Line MBH KW MBH Venting and piping locations on 255 38.2 190 4000 965 11.6 825 8.7 6.9 1600 400029.3 1600 75 79.8 203 218 38.0 28.596 57.5 147 22.5 60.8 154 3" 2" 1" 1599 719 469 1512 Back of MagnaTherm do vary 2000 29.3 75 79.8 203 38.0 96 57.5 147 60.8 154 3" 2" 1" 2000 1999 586 1883 Air from size to size. Volume Water Heater, Water 2500 30.8 78 87.0Flow Requirements 221 41.5 105 60.5 154 71.0 180 3" 2" 1" 2500 2499 732 2374 Temperature Rise in °C 3000 30.8 78 87.0 221 41.5 105 60.5 178 71.0 180 3" 2" 1" 3000 3000 879 2814 17°C 19°C 22°C For further details of MagnaTherm 3500 34.5 88 96.7 246 52.0 132 70.0 178 80.8 205 4" 2" 1" 3500 3500 1025 3317 Size Flow Head Loss* Flow Head Loss* Flow Head Loss* specifications, please the Rise 246 Size 34.5 Data Flow Rate Temp Headloss* Rise 178 Headloss* 4000Dimensional 88 see 96.7 52.0Flow Rate 132 Temp70.0 80.8 205 4" 2" 1" 4000 4000 Data 1172 3724 Sizing Dimensional Data Sizing LPM m LPM m LPM m Dimensional Data Sizing MagnaTherm Submittal Data GPM °F Ft LPM °C m 1600 379 4.3 329 3.0 288 2.5 1600 which are 152available online 20 31.0 525 11.1 10.1 Sheets EE Condensate Condensate E Condensate Gas Water Gas 2000 485 7.2 413 5.2 360 4.2 Water Gas Water A B C D A B 25 B C C D D Siz A Input Siz Ra Size 2000 152 33.0 575 14.0 10.1 Size Connection Trap at www.laars.com Size Connection Connection 'Knock-down' Height Connection Height Connection Trap 'Knock-down' Height'Knock-down' TrapConnection 2500 599 7.0 514 5.0 449 4.1 Size 2500 190 25 33.7 719 13.9 10.0 Inches cm Inches cm Inches cm Inches cm Inches cm Groove Lock (NPT) Line Boiler, Water Flowcm Requirements InchesInches cm cm Inches cmcm Inches cm cm Inches Groove Lock Line Inches Inches cm cm Inches Inches Inches Groove Lockcm (NPT) Line (NPT) MBH 3000 719 10.4 621 7.9 538 5.8 Water 2" 3000 190 17.0 96 11.0 57.5 1600 75 29.3 29.3 7530203 79.836.0 203 719 38.0 57.5 147154 60.8 60.8 3" 154 2" 3" 2" 1" 160 79.8 38.0 96 57.5 147 154 3" 1" 1" 1600 29.3 1600 79.8 75 38.0 203 96 147 60.8 1599 160 3500 839 9.0 719 7.0 629 6.01600 Outlet 3500 222Temperature 17.0 96 9.0 57.5 Rise 38.0 147 154 3" 1" 2000 75 29.3 29.3 7530 79.830.6 203 839 38.0 57.5 96 57.5 147154 60.8 60.8 3" 154Temperature 3" Rise 2" 1" 200 4000 965 11.6 825 8.7 719 6.92000 29.3 2000 79.8 75 203in °F 79.8 38.0 203 96 147 60.8 2" 1"in °C 2" 2000 1999 200 4000 224 848 41.5 19.0 105 9.1 60.5 2500 78 30°F 30.8 7834221 87.030.0 22140°F 60.5 154180 71.0 71.0 3"17°C 180 180 2" 3" 19°C 2" 1"22°C 250 35°F 87.0 30.8 154 3" 2" 1" 2500 30.8 2500 87.0 78 41.5 221 105 41.5 60.5 105 154 71.0 1" 2500 2499 250 Water MagnaTherm Electrical Size 3000 Size 3000Flow 30.8 Loss* 78 87.0 221 105 41.5 60.5 105 105 60.5 178 71.0 180Loss* 3" 1"Head Loss* 2" 1" Head Loss* 300 Flow221 Head87.0 Loss* Head Loss* Flow3" Head FlowOptions 30.8 221 41.5 60.5 178 180 3" 2" 1" 3000 30.8 78 Head 87.0 78 41.5 Flow 178 71.0 180 71.0 2" Flow 3000 3000 300 96.7 246 70.0 178 205 4" Feet96.7 88 GPM246 Feet LPM4" m 2" Inlet LPM LPM1" m 3500GPM 34.5 88 96.7 52.0 GPM 246 132 Feet52.0 52.0 70.0 132 132 70.0 178205 80.8 80.8 205 4" 1" m2" 2" 1" 350 3500 34.5 3500 88 34.5 178 80.8 3500 3500 350 Current (FLA) 4000 400010088 34.5 34.5 8887 246 10.0 96.7 52.0 76246 246 132 8.0 52.0 52.0 70.0 132 132 70.0 178 80.8 205 4" Voltage 2" 1" 400 1600 4000 1600 14.096.7 88 3794" 4.3 2" 329 288 1" 2.5 96.7 70.0 178 205 4" 4000 34.5 178 80.8 205 80.8 1" 3.02" 4000 400 2000 3500 3000 3500 2000 128 23.5 109 17.1 95 13.6 2000 485 7.2 413 5.2 360 1600 4.2 120V Phase 449 17.0 4.1 22.6 N/A N/A N/A 2500 158 23.6 136 17.6 119 13.6 2500 599 7.0 514 Single5.0 220V Phase 538 10.0 5.8 11.3 N/A N/A N/A 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 Single7.9 Vent 208V Phase 629 N/A 6.0 12.7 19.4 19.4 19.4 Water Requirements 3500Boiler, 222 Flow 190 23.6 166 18.6 3500 839 9.0 719 Three7.0 Boiler, Water Flow30.6 Requirements Boiler, Water Flow Requirements 480V Phase 719 N/A 6.9 6.2 8.7 8.7 8.7 4000 255 38.2 218 28.5 190 22.5 4000 965 11.6 825 Three8.7 600V Three Phase N/A 4.5 5.9 5.9 5.9 Temperature Rise in °F Temperature Rise in °C Temperature Rise in °F Temperature Rise in °C Temperature Rise in °F Temperature Rise in °C 30°F 35°F 40°F 17°C 19°C 22°C Volume Water 30°FRequirements 35°F40°F 40°F 17°C 19°C 19°C 22°C 22°C 30°FHeater, Water Flow 35°F 17°C Loss* Loss* Head Loss* Loss* Head Size Size Size Size Flow FlowHead Head Head Loss*Loss*Flow FlowFlowHead HeadHead Loss*Loss*Flow Flow Head Loss* Loss* Flow FlowHead Head Head Loss* Loss*Flow Flow FlowHead Head Head Loss* Loss*Flow Flow Head Loss* Loss* Flow Size Head Loss*Flow Flow Size Head Loss*Flow Feet LPM m GPM GPM Feet Feet Feet GPM GPMGPM Feet Feet Feet GPM GPM Feet LPM LPM m m m LPM LPM LPM m m m LPM LPM m GPM Feet GPM LPM m The MagnaTherm’s heat exchanger design is the latest from MagnaTherm Electrical Options Size 1600 100 14.0 76 8.0 2.5 Flow14.0 Rate Temp Rate76Temp10.0 Rise 8.0 Headloss* 1600 1600 4.3 379 100 Rise 14.0 10.0 Flow87 87 10.0 76 8.0 379 329 4.3 4.3 3.0 329 329 288 3.0 3.0 2.5 288 288 2.5 1600 1600 100 87 Headloss* 379 1600 Laars engineering. You can rely on years of worry free service Ft 17.1 LPM 109 13.6 4.2 2000GPM 128°F 109 23.5 23.5 109 95 °C17.1 17.1 13.6 m 95 95 13.6 2000 7.2 485 485 413 7.2 7.2 5.2 413 413 360 5.2 5.2 4.2 360 360 4.2 2000 128 2000 23.5 128 2000 485 2000 Current (FLA) knowing that the heart Voltage of the MagnaTherm was designed and 136 17.6 13.6 4.1 31.017.6 525 2500152 15820 136 23.6 23.6 136 119 11.1 17.6 13.610.1119 119 13.6 2500 7.0 599 599 514 7.0 7.0 5.0 514 514 449 5.0 5.0 4.1 449 449 4.1 158 2500 23.6 158 2500 599 2500 1600 2000 3500 3000 35002500 4000 1600 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 built at the Laars headquarters in 2000 152 25 33.0 575 14.0 10.1 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 120V manufacturing Single Phase 17.0 22.6 N/A N/A N/A N/A 190 23.6 18.6 6.0 33.723.6 719 3500190 22225 190 30.6 30.6 190 166 13.9 23.6 18.610.0166 166 18.6 3500 9.0 839 839 719 9.0 9.0 7.0 719 719 629 7.0 7.0 6.0 629 629 6.0 222 3500 30.6 222 3500 839 3500 Rochester, NH,220V USA. Single Phase 10.0 11.3 N/A N/A N/A3500 N/A 2500 218 28.5 22.5 6.9 36.028.5 719 4000190 25530 218 38.2 38.2 218 190 17.0 28.5 22.511.0190 190 22.5 4000 11.6 965 965 825 11.6 11.6 8.7 825 825 719 8.7 8.7 6.9 719 719 6.9 255 4000 38.2 255 4000 965 4000 208V Three Phase N/A 12.7 19.4 19.4 19.44000 19.4 3000 3500 222 30 30.6 839 17.0 9.0 480V Three Phase N/A 6.2 8.7 8.7 8.7 8.7 *Headloss is for the heater only (no piping). 4000Volume 224 34 Water 848 19.0 9.1 Water Flow Volume Water Heater, Water30.0 Flow Requirements Requirements Volume Water Water FlowHeater, Requirements 600V Three Phase N/A 4.5 5.9 5.9 5.9 5.9 Heater,
D
The MagnaTherm comes with a centralized electrical load center that allows for various voltage packages (single andFlow three phase), to better match job site Boiler, Water Requirements requirements.
1600 2000 2500 3000 3500 4000
cm 75 75 78 78 88 88
C
Sizing Data
C
cm
Inches 29.3 29.3 30.8 30.8 34.5 34.5
B
Sizing Data
Inches 57.5 57.5 60.5 60.5 70.0 70.0
29.3 removable 75 79.8 203 complete 38.0 96 Two1600 full-swing doors allow access 2000 29.3 75 79.8 203 38.0 96 to electrical, controls, gas valves and accessories from 2500 30.8 78 87.0 221 41.5 105 the front 3000 of the 30.8 MagnaTherm 78 87.0for quick 221 setup. 41.5 105 4000 34.5 88 Electrical Flexibility
A
Size
m 10.1 10.1 10.0 11.0 9.0 9.1
E Condensate Water Gas 'Knock-down' Height Connection Connection Trap Inches cm Groove Lock (NPT) Line 60.8 154 3" 2" 1" 60.8 154 3" 2" 1" 71.0 180 3" 2" 1" 71.0 180 3" 2" 1" 80.8 205 4" 2" 1" 80.8 205 4" 2" 1"
Rate Output Rate Size WaterInput Boiler, Flow Requirements
Front
Side
Back
Boiler, Water Flow Requirements
Designed and Made in America
Optimized Heat Transfer Technology and Extended Life
The MagnaTherm’s efficiency secret lies in its precise alignment Size of micro-finned heating tubes combined with highly engineered flue gas channels. This arrangement optimizes the flow of flue 1600 2000 gases in order to transfer maximum heat to the water inside the 2500 heating tubes and extending heat exchanger life. 3000 3500 4000 Boasting an AHRI certified 95% or higher Thermal Efficiency, indoor or outdoor certification, a 5:1 turndown and the Laars boiler VARI-PRIMETM control package, the Laars MagnaTherm is the clear choice when selecting a high efficiency boiler or volume water heater.
Volume Water Heater, Flow Requirements Flow Temp Rise Headloss* Flow Rate Size Flow Rate Rate TempFlow Rise Rate Headloss* FlowHeadloss* Rate Temp Temp Rise Rise Headloss* Headloss* Flow Rate Size Temp Rise Headloss* Temp Rise GPM °F Ft LPM °C m GPM Ft °F LPM Ft °C LPM m °C m GPM °F 152 31.0 10.1 1600 20 152 31.0 20 20 525 31.0 11.1 525 525 10.1 11.1 11.1 10.1 152 1600 152 33.0 10.1 2000 25 152 33.0 25 25 575 33.0 14.0 575 575 10.1 14.0 14.0 10.1 152 2000 190 33.7 10.0 2500 25 190 33.7 25 25 719 33.7 13.9 719 719 10.0 13.9 13.9 10.0 190 2500 190 36.0 11.0 3000 30 190 36.0 30 30 719 36.0 17.0 719 719 11.0 17.0 17.0 11.0 190 3000 222 30.6 17.0 9.0 3500 30 222 30.6 30 30 839 30.6 17.0 839 839 9.0 17.0 9.0 222 3500 224 30.0 19.0 9.1 4000 34 224 30.0 34 34 848 30.0 19.0 848 848 9.1 19.0 9.1 224 4000
Water Hardness of 1-10 grains per gallon. Allowable pH: 6.5 to 9.5 *Headloss is for the heater only (no piping).
MagnaTherm Electrical Options
MagnaTherm Electrical Options Voltage 120V Single Phase 220V Single Phase 208V Three Phase 480V Three Phase 600V Three Phase
1600 17.0 10.0 N/A N/A N/A
2000 22.6 11.3 12.7 6.2 4.5
Current (FLA) 3500 N/A N/A 19.4 8.7 5.9
3000 N/A N/A 19.4 8.7 5.9
3500 N/A N/A 19.4 8.7 5.9
4000 N/A N/A 19.4 8.7 5.9
MagnaTherm MagnaTherm Electrical Options Options MagnaTherm Electrical OptionsElectrical Voltage 120V Single Phase 220V Single Phase 208V Three Phase 480V Three Phase 600V Three Phase
Voltage Voltage 1600 2000 120V 120V Single Single Phase 22.6 17.0 Phase 220V 220V Single Single Phase 11.3 10.0 Phase 208V 208V Three Three Phase 12.7 N/A Phase 480V 480V Three Three Phase 6.2 N/A Phase 600V 600V Three Three Phase 4.5 N/A Phase
Current Current (FLA) (FLA) Current (FLA) 1600 1600 3500 2000 2000 3000 3500 3500 3500 17.0 17.0 N/A 22.6 22.6 N/A N/A N/A N/A 10.0 10.0 N/A 11.3 11.3 N/A N/A N/A N/A N/A N/A 19.4 12.7 12.7 19.4 19.4 19.4 19.4 N/A N/A 8.7 6.2 6.2 8.7 8.7 8.7 8.7 N/A N/A 5.9 4.5 4.5 5.9 5.9 5.9 5.9
3000 3000 4000 N/A N/A N/A N/A N/A N/A 19.4 19.4 19.4 8.7 8.7 8.7 5.9 5.9 5.9
3500 3500 N/A N/A N/A N/A 19.4 19.4 8.7 8.7 5.9 5.9
4000 4000 N/A N/A N/A N/A 19.4 19.4 8.7 8.7 5.9 5.9
THE
MAGNATHERM
Getting to know the MAGNATHERM
Sizing Data, for the MAGNATHERM
CONDENSING BOILER & VOLUME WATER HEATER
A Perfect Balance of Size, Form and Function Every commercial heating system is unique and as such requires a boiler that can respond to system fluctuations, while maintaining the energy conservation standards held by today’s building owners. Such a boiler now exists in the innovative Laars MagnaTherm. On board every boiler is MagnaTherm’s unique VARI-PRIMETM control that allows building owners to save thousands of dollars over the life of the boiler due to dramatically reduced energy costs versus a typical on/off pump arrangement. Only the Laars MagnaTherm includes the VARI-PRIMETM control that balances combustion, air flow and water flow on every boiler! The MagnaTherm’s small footprint, slim vertical design and removable top section help it to fit into tight mechanical rooms. It’s optional electrical packages allow for easy pairing with various field supply voltages. And the large easy-to-navigate color touch screen display results in quick setup and diagnostics and allows up to 8 MagnaTherms to be controlled in a cascading boiler bank.
Features: • • • • •
• • • •
Laars designed and built heat exchanger Stylish, modern cabinet design Up to 99% thermal efficiency, condensing operation Reliable, smooth starting hot surface ignition Optimized gas usage for lower energy bills via a 5:1 (20% to 100% input) modulating gas valve Quiet, variable speed blower VARI-PRIMETM, variable speed pump control matches system pump with boiler modulation to optimize efficiency Small footprint compared to others in class Forward mounted low voltage panel for easy wiring and trouble shooting
• Unique, sealed condensate trap does not need to be primed at startup • Single or up to 8 boilers in a cascade installation • Up to 100 feet of vent • M eets the most stringent NOx emission requirements • 439 Stainless Steel Heat Exchanger for increased corrosion resistance • Advanced control system with temperature control, iagnostics, outdoor reset capability, and easy access d for field wiring • 10-year heat exchanger warranty
Dimensional Data
Dimensional Data
Large Color Touch Screen
A multi-color, simple to use smart touch screen display allows you to fully control and setup the MagnaTherm.
1600 2000 2500 3000 3500 4000
Removable Top Section
An easy-to-remove top blower section makes Dimensional getting intoData tight spaces and elevators a smooth operation! Size
Full Access Inches
A
B
cm
Inches
Inches
3500
34.5
88
96.7 96.7
246 246
52.0 52.0
cm
132 132
Temperature Rise in °F 30°F 35°F 40°F Size Flow Head Loss* Flow Head Loss* Flow Head Loss* The MagnaTherm uses produced and GPM Feet American GPM Feet GPM 439 Feet 14.0 87 10.0withstand 76 8.0 316 1600 SS heat100exchanger materials to the 2000 temperatures 128 23.5 and 109 95 13.6 in extreme caustic17.1 conditions found 2500 158 23.6 136 17.6 119 13.6 high3000 efficiency combustion chambers. 190 34.2 164 25.8 142 18.9 3500 222 30.6 190 23.6 166 18.6 4000 255 38.2 218 28.5 190 22.5
Superior Heat Exchanger Materials
Indoor / Outdoor Installation
VolumeDesign, Water Heater, Water Flow Requirements Slim Small Footprint
The MagnaTherm’s width allows it to fit through standard doorways. Size Flow Rate Temp Rise Headloss* Flow Rate Temp Rise Headloss* GPM 152 152 190 190 222 224
°F 20 25 25 30 30 34
Ft 31.0 33.0 33.7 36.0 30.6 30.0
LPM 525 575 719 719 839 848
°C 11.1 14.0 13.9 17.0 17.0 19.0
Inches 79.8 79.8 87.0 87.0 96.7 96.7
cm 203 203 221 221 246 246
Inches 38.0 38.0 41.5 41.5 52.0 52.0
D cm 96 96 105 105 132 132
Inches 57.5 57.5 60.5 60.5 70.0 70.0
cm 147 147 154 178 178 178
E Water Gas 'Knock-down' Height Connection Connection Inches cm Groove Lock (NPT) 60.8 154 3" 2" 60.8 154 3" 2" 71.0 180 3" 2" 71.0 180 3" 2" 80.8 205 4" 2" 80.8 205 4" 2"
Condensate
Trap Line 1" 1" 1" 1" 1" 1"
Minimum Gas Boiler Water Heater Vent Vent Product Weight Operating Weight Shipping Weight Supply Thermal Efficiency Thermal Efficiency Diameter Length cm MBH KW MBH KW % % Lbs Kg Lbs Kg Lbs Kg " w.c. Pa in (cm) ft (m) Temperature Rise in °F Temperature Rise in °C 1600 147 1599 469 1512 443 95.0 96 1390 630 1562 709 1590 721 4 996 6 (15) 100 (30.5) 30°F 35°F 40°F 17°C 19°C 22°C 147 2000 1999 586 1883 552 95.0 96 1390 630 1562 709 1590 721 4 996 8 (20) 100 (30.5) Size Size Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Los 154 2500 2499 732 2374 696 95.0 96 1785 810 2039 925 1985 900 4 996 8 (20) 100 (30.5) GPM Feet GPM Feet GPM Feet LPM m LPM m LPM m 178 3000 3000 879 2814 825 95.0 95 1785 810 2039 925 1985 900 4 996 10 (25) 100 (30.5) 1600 1600 100 14.0 87 10.0 76 8.0 379 4.3 329 3.0 288 2.5 Dimensional Data Sizing Data 178 3500 3500 1025 3317 972 95.0 96 2278 1033 2742 1244 2478 1124 4 996 10 (25) 100 (30.5) 2000 128 23.5 109 17.1 95 13.6 2000 485 7.2 413 5.2 360 4.2 178 4000 4000 1172 3724 1091 95.0 96 2278 1033 2742 1244 2478 1124 4 996 12 (30) 100 (30.5) 2500 158 23.6 136 17.6 119 13.6 2500 599 7.0 514 5.0 449 4.1 E Condensate Water Gas A 190 C25.8 Input Rate Outp Size 34.2 B 164 142 D 18.9'Knock-down' Height Connection Connection 3000 719 10.4 621 7.9 538 5.8 Size 3000 Trap 3500 222 30.6 190 23.6 166 18.6 3500 839 9.0 719 7.0 629 6.0 Inches cm Inches cm Inches cm Inches cm Inches cm Groove Lock (NPT) Line MBH KW MBH Venting and piping locations on 255 38.2 190 4000 965 11.6 825 8.7 6.9 1600 400029.3 1600 75 79.8 203 218 38.0 28.596 57.5 147 22.5 60.8 154 3" 2" 1" 1599 719 469 1512 Back of MagnaTherm do vary 2000 29.3 75 79.8 203 38.0 96 57.5 147 60.8 154 3" 2" 1" 2000 1999 586 1883 Air from size to size. Volume Water Heater, Water 2500 30.8 78 87.0Flow Requirements 221 41.5 105 60.5 154 71.0 180 3" 2" 1" 2500 2499 732 2374 Temperature Rise in °C 3000 30.8 78 87.0 221 41.5 105 60.5 178 71.0 180 3" 2" 1" 3000 3000 879 2814 17°C 19°C 22°C For further details of MagnaTherm 3500 34.5 88 96.7 246 52.0 132 70.0 178 80.8 205 4" 2" 1" 3500 3500 1025 3317 Size Flow Head Loss* Flow Head Loss* Flow Head Loss* specifications, please the Rise 246 Size 34.5 Data Flow Rate Temp Headloss* Rise 178 Headloss* 4000Dimensional 88 see 96.7 52.0Flow Rate 132 Temp70.0 80.8 205 4" 2" 1" 4000 4000 Data 1172 3724 Sizing Dimensional Data Sizing LPM m LPM m LPM m Dimensional Data Sizing MagnaTherm Submittal Data GPM °F Ft LPM °C m 1600 379 4.3 329 3.0 288 2.5 1600 which are 152available online 20 31.0 525 11.1 10.1 Sheets EE Condensate Condensate E Condensate Gas Water Gas 2000 485 7.2 413 5.2 360 4.2 Water Gas Water A B C D A B 25 B C C D D Siz A Input Siz Ra Size 2000 152 33.0 575 14.0 10.1 Size Connection Trap at www.laars.com Size Connection Connection 'Knock-down' Height Connection Height Connection Trap 'Knock-down' Height'Knock-down' TrapConnection 2500 599 7.0 514 5.0 449 4.1 Size 2500 190 25 33.7 719 13.9 10.0 Inches cm Inches cm Inches cm Inches cm Inches cm Groove Lock (NPT) Line Boiler, Water Flowcm Requirements InchesInches cm cm Inches cmcm Inches cm cm Inches Groove Lock Line Inches Inches cm cm Inches Inches Inches Groove Lockcm (NPT) Line (NPT) MBH 3000 719 10.4 621 7.9 538 5.8 Water 2" 3000 190 17.0 96 11.0 57.5 1600 75 29.3 29.3 7530203 79.836.0 203 719 38.0 57.5 147154 60.8 60.8 3" 154 2" 3" 2" 1" 160 79.8 38.0 96 57.5 147 154 3" 1" 1" 1600 29.3 1600 79.8 75 38.0 203 96 147 60.8 1599 160 3500 839 9.0 719 7.0 629 6.01600 Outlet 3500 222Temperature 17.0 96 9.0 57.5 Rise 38.0 147 154 3" 1" 2000 75 29.3 29.3 7530 79.830.6 203 839 38.0 57.5 96 57.5 147154 60.8 60.8 3" 154Temperature 3" Rise 2" 1" 200 4000 965 11.6 825 8.7 719 6.92000 29.3 2000 79.8 75 203in °F 79.8 38.0 203 96 147 60.8 2" 1"in °C 2" 2000 1999 200 4000 224 848 41.5 19.0 105 9.1 60.5 2500 78 30°F 30.8 7834221 87.030.0 22140°F 60.5 154180 71.0 71.0 3"17°C 180 180 2" 3" 19°C 2" 1"22°C 250 35°F 87.0 30.8 154 3" 2" 1" 2500 30.8 2500 87.0 78 41.5 221 105 41.5 60.5 105 154 71.0 1" 2500 2499 250 Water MagnaTherm Electrical Size 3000 Size 3000Flow 30.8 Loss* 78 87.0 221 105 41.5 60.5 105 105 60.5 178 71.0 180Loss* 3" 1"Head Loss* 2" 1" Head Loss* 300 Flow221 Head87.0 Loss* Head Loss* Flow3" Head FlowOptions 30.8 221 41.5 60.5 178 180 3" 2" 1" 3000 30.8 78 Head 87.0 78 41.5 Flow 178 71.0 180 71.0 2" Flow 3000 3000 300 96.7 246 70.0 178 205 4" Feet96.7 88 GPM246 Feet LPM4" m 2" Inlet LPM LPM1" m 3500GPM 34.5 88 96.7 52.0 GPM 246 132 Feet52.0 52.0 70.0 132 132 70.0 178205 80.8 80.8 205 4" 1" m2" 2" 1" 350 3500 34.5 3500 88 34.5 178 80.8 3500 3500 350 Current (FLA) 4000 400010088 34.5 34.5 8887 246 10.0 96.7 52.0 76246 246 132 8.0 52.0 52.0 70.0 132 132 70.0 178 80.8 205 4" Voltage 2" 1" 400 1600 4000 1600 14.096.7 88 3794" 4.3 2" 329 288 1" 2.5 96.7 70.0 178 205 4" 4000 34.5 178 80.8 205 80.8 1" 3.02" 4000 400 2000 3500 3000 3500 2000 128 23.5 109 17.1 95 13.6 2000 485 7.2 413 5.2 360 1600 4.2 120V Phase 449 17.0 4.1 22.6 N/A N/A N/A 2500 158 23.6 136 17.6 119 13.6 2500 599 7.0 514 Single5.0 220V Phase 538 10.0 5.8 11.3 N/A N/A N/A 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 Single7.9 Vent 208V Phase 629 N/A 6.0 12.7 19.4 19.4 19.4 Water Requirements 3500Boiler, 222 Flow 190 23.6 166 18.6 3500 839 9.0 719 Three7.0 Boiler, Water Flow30.6 Requirements Boiler, Water Flow Requirements 480V Phase 719 N/A 6.9 6.2 8.7 8.7 8.7 4000 255 38.2 218 28.5 190 22.5 4000 965 11.6 825 Three8.7 600V Three Phase N/A 4.5 5.9 5.9 5.9 Temperature Rise in °F Temperature Rise in °C Temperature Rise in °F Temperature Rise in °C Temperature Rise in °F Temperature Rise in °C 30°F 35°F 40°F 17°C 19°C 22°C Volume Water 30°FRequirements 35°F40°F 40°F 17°C 19°C 19°C 22°C 22°C 30°FHeater, Water Flow 35°F 17°C Loss* Loss* Head Loss* Loss* Head Size Size Size Size Flow FlowHead Head Head Loss*Loss*Flow FlowFlowHead HeadHead Loss*Loss*Flow Flow Head Loss* Loss* Flow FlowHead Head Head Loss* Loss*Flow Flow FlowHead Head Head Loss* Loss*Flow Flow Head Loss* Loss* Flow Size Head Loss*Flow Flow Size Head Loss*Flow Feet LPM m GPM GPM Feet Feet Feet GPM GPMGPM Feet Feet Feet GPM GPM Feet LPM LPM m m m LPM LPM LPM m m m LPM LPM m GPM Feet GPM LPM m The MagnaTherm’s heat exchanger design is the latest from MagnaTherm Electrical Options Size 1600 100 14.0 76 8.0 2.5 Flow14.0 Rate Temp Rate76Temp10.0 Rise 8.0 Headloss* 1600 1600 4.3 379 100 Rise 14.0 10.0 Flow87 87 10.0 76 8.0 379 329 4.3 4.3 3.0 329 329 288 3.0 3.0 2.5 288 288 2.5 1600 1600 100 87 Headloss* 379 1600 Laars engineering. You can rely on years of worry free service Ft 17.1 LPM 109 13.6 4.2 2000GPM 128°F 109 23.5 23.5 109 95 °C17.1 17.1 13.6 m 95 95 13.6 2000 7.2 485 485 413 7.2 7.2 5.2 413 413 360 5.2 5.2 4.2 360 360 4.2 2000 128 2000 23.5 128 2000 485 2000 Current (FLA) knowing that the heart Voltage of the MagnaTherm was designed and 136 17.6 13.6 4.1 31.017.6 525 2500152 15820 136 23.6 23.6 136 119 11.1 17.6 13.610.1119 119 13.6 2500 7.0 599 599 514 7.0 7.0 5.0 514 514 449 5.0 5.0 4.1 449 449 4.1 158 2500 23.6 158 2500 599 2500 1600 2000 3500 3000 35002500 4000 1600 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 built at the Laars headquarters in 2000 152 25 33.0 575 14.0 10.1 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 120V manufacturing Single Phase 17.0 22.6 N/A N/A N/A N/A 190 23.6 18.6 6.0 33.723.6 719 3500190 22225 190 30.6 30.6 190 166 13.9 23.6 18.610.0166 166 18.6 3500 9.0 839 839 719 9.0 9.0 7.0 719 719 629 7.0 7.0 6.0 629 629 6.0 222 3500 30.6 222 3500 839 3500 Rochester, NH,220V USA. Single Phase 10.0 11.3 N/A N/A N/A3500 N/A 2500 218 28.5 22.5 6.9 36.028.5 719 4000190 25530 218 38.2 38.2 218 190 17.0 28.5 22.511.0190 190 22.5 4000 11.6 965 965 825 11.6 11.6 8.7 825 825 719 8.7 8.7 6.9 719 719 6.9 255 4000 38.2 255 4000 965 4000 208V Three Phase N/A 12.7 19.4 19.4 19.44000 19.4 3000 3500 222 30 30.6 839 17.0 9.0 480V Three Phase N/A 6.2 8.7 8.7 8.7 8.7 *Headloss is for the heater only (no piping). 4000Volume 224 34 Water 848 19.0 9.1 Water Flow Volume Water Heater, Water30.0 Flow Requirements Requirements Volume Water Water FlowHeater, Requirements 600V Three Phase N/A 4.5 5.9 5.9 5.9 5.9 Heater,
D
The MagnaTherm comes with a centralized electrical load center that allows for various voltage packages (single andFlow three phase), to better match job site Boiler, Water Requirements requirements.
1600 2000 2500 3000 3500 4000
cm 75 75 78 78 88 88
C
Sizing Data
C
cm
Inches 29.3 29.3 30.8 30.8 34.5 34.5
B
Sizing Data
Inches 57.5 57.5 60.5 60.5 70.0 70.0
29.3 removable 75 79.8 203 complete 38.0 96 Two1600 full-swing doors allow access 2000 29.3 75 79.8 203 38.0 96 to electrical, controls, gas valves and accessories from 2500 30.8 78 87.0 221 41.5 105 the front 3000 of the 30.8 MagnaTherm 78 87.0for quick 221 setup. 41.5 105 4000 34.5 88 Electrical Flexibility
A
Size
m 10.1 10.1 10.0 11.0 9.0 9.1
E Condensate Water Gas 'Knock-down' Height Connection Connection Trap Inches cm Groove Lock (NPT) Line 60.8 154 3" 2" 1" 60.8 154 3" 2" 1" 71.0 180 3" 2" 1" 71.0 180 3" 2" 1" 80.8 205 4" 2" 1" 80.8 205 4" 2" 1"
Rate Output Rate Size WaterInput Boiler, Flow Requirements
Front
Side
Back
Boiler, Water Flow Requirements
Designed and Made in America
Optimized Heat Transfer Technology and Extended Life
The MagnaTherm’s efficiency secret lies in its precise alignment Size of micro-finned heating tubes combined with highly engineered flue gas channels. This arrangement optimizes the flow of flue 1600 2000 gases in order to transfer maximum heat to the water inside the 2500 heating tubes and extending heat exchanger life. 3000 3500 4000 Boasting an AHRI certified 95% or higher Thermal Efficiency, indoor or outdoor certification, a 5:1 turndown and the Laars boiler VARI-PRIMETM control package, the Laars MagnaTherm is the clear choice when selecting a high efficiency boiler or volume water heater.
Volume Water Heater, Flow Requirements
Flow Temp Rise Headloss* Flow Rate Size Flow Rate Rate TempFlow Rise Rate Headloss* FlowHeadloss* Rate Temp Temp Rise Rise Headloss* Headloss* Flow Rate Size Temp Rise Headloss* Temp Rise GPM °F Ft LPM °C m GPM Ft °F LPM Ft °C LPM m °C m GPM °F 152 31.0 10.1 1600 20 152 31.0 20 20 525 31.0 11.1 525 525 10.1 11.1 11.1 10.1 152 1600 152 33.0 10.1 2000 25 152 33.0 25 25 575 33.0 14.0 575 575 10.1 14.0 14.0 10.1 152 2000 190 33.7 10.0 2500 25 190 33.7 25 25 719 33.7 13.9 719 719 10.0 13.9 13.9 10.0 190 2500 190 36.0 11.0 3000 30 190 36.0 30 30 719 36.0 17.0 719 719 11.0 17.0 17.0 11.0 190 3000 222 30.6 17.0 9.0 3500 30 222 30.6 30 30 839 30.6 17.0 839 839 9.0 17.0 9.0 222 3500 224 30.0 19.0 9.1 4000 34 224 30.0 34 34 848 30.0 19.0 848 848 9.1 19.0 9.1 224 4000
Water Hardness of 1-10 grains per gallon. Allowable pH: 6.5 to 9.5 *Headloss is for the heater only (no piping).
MagnaTherm Electrical Options
MagnaTherm Electrical Options Voltage 120V Single Phase 220V Single Phase 208V Three Phase 480V Three Phase 600V Three Phase
1600 17.0 10.0 N/A N/A N/A
2000 22.6 11.3 12.7 6.2 4.5
Current (FLA) 3500 N/A N/A 19.4 8.7 5.9
3000 N/A N/A 19.4 8.7 5.9
3500 N/A N/A 19.4 8.7 5.9
4000 N/A N/A 19.4 8.7 5.9
MagnaTherm MagnaTherm Electrical Options Options MagnaTherm Electrical OptionsElectrical Voltage 120V Single Phase 220V Single Phase 208V Three Phase 480V Three Phase 600V Three Phase
Voltage Voltage 1600 2000 120V 120V Single Single Phase 22.6 17.0 Phase 220V 220V Single Single Phase 11.3 10.0 Phase 208V 208V Three Three Phase 12.7 N/A Phase 480V 480V Three Three Phase 6.2 N/A Phase 600V 600V Three Three Phase 4.5 N/A Phase
Current Current (FLA) (FLA) Current (FLA) 1600 1600 3500 2000 2000 3000 3500 3500 3500 17.0 17.0 N/A 22.6 22.6 N/A N/A N/A N/A 10.0 10.0 N/A 11.3 11.3 N/A N/A N/A N/A N/A N/A 19.4 12.7 12.7 19.4 19.4 19.4 19.4 N/A N/A 8.7 6.2 6.2 8.7 8.7 8.7 8.7 N/A N/A 5.9 4.5 4.5 5.9 5.9 5.9 5.9
3000 3000 4000 N/A N/A N/A N/A N/A N/A 19.4 19.4 19.4 8.7 8.7 8.7 5.9 5.9 5.9
3500 3500 N/A N/A N/A N/A 19.4 19.4 8.7 8.7 5.9 5.9
4000 4000 N/A N/A N/A N/A 19.4 19.4 8.7 8.7 5.9 5.9
THE
MAGNATHERM
Getting to know the MAGNATHERM
Sizing Data, for the MAGNATHERM
CONDENSING BOILER & VOLUME WATER HEATER
A Perfect Balance of Size, Form and Function Every commercial heating system is unique and as such requires a boiler that can respond to system fluctuations, while maintaining the energy conservation standards held by today’s building owners. Such a boiler now exists in the innovative Laars MagnaTherm. On board every boiler is MagnaTherm’s unique VARI-PRIMETM control that allows building owners to save thousands of dollars over the life of the boiler due to dramatically reduced energy costs versus a typical on/off pump arrangement. Only the Laars MagnaTherm includes the VARI-PRIMETM control that balances combustion, air flow and water flow on every boiler! The MagnaTherm’s small footprint, slim vertical design and removable top section help it to fit into tight mechanical rooms. It’s optional electrical packages allow for easy pairing with various field supply voltages. And the large easy-to-navigate color touch screen display results in quick setup and diagnostics and allows up to 8 MagnaTherms to be controlled in a cascading boiler bank.
Features: • • • • •
• • • •
Laars designed and built heat exchanger Stylish, modern cabinet design Up to 99% thermal efficiency, condensing operation Reliable, smooth starting hot surface ignition Optimized gas usage for lower energy bills via a 5:1 (20% to 100% input) modulating gas valve Quiet, variable speed blower VARI-PRIMETM, variable speed pump control matches system pump with boiler modulation to optimize efficiency Small footprint compared to others in class Forward mounted low voltage panel for easy wiring and trouble shooting
• Unique, sealed condensate trap does not need to be primed at startup • Single or up to 8 boilers in a cascade installation • Up to 100 feet of vent • M eets the most stringent NOx emission requirements • 439 Stainless Steel Heat Exchanger for increased corrosion resistance • Advanced control system with temperature control, iagnostics, outdoor reset capability, and easy access d for field wiring • 10-year heat exchanger warranty
Dimensional Data
Dimensional Data
Large Color Touch Screen
A multi-color, simple to use smart touch screen display allows you to fully control and setup the MagnaTherm.
1600 2000 2500 3000 3500 4000
Removable Top Section
An easy-to-remove top blower section makes Dimensional getting intoData tight spaces and elevators a smooth operation! Size
Full Access Inches
A
B
cm
Inches
Inches
3500
34.5
88
96.7 96.7
246 246
52.0 52.0
cm
132 132
Temperature Rise in °F 30°F 35°F 40°F Size Flow Head Loss* Flow Head Loss* Flow Head Loss* The MagnaTherm uses produced and GPM Feet American GPM Feet GPM 439 Feet 14.0 87 10.0withstand 76 8.0 316 1600 SS heat100exchanger materials to the 2000 temperatures 128 23.5 and 109 95 13.6 in extreme caustic17.1 conditions found 2500 158 23.6 136 17.6 119 13.6 high3000 efficiency combustion chambers. 190 34.2 164 25.8 142 18.9 3500 222 30.6 190 23.6 166 18.6 4000 255 38.2 218 28.5 190 22.5
Superior Heat Exchanger Materials
Indoor / Outdoor Installation
VolumeDesign, Water Heater, Water Flow Requirements Slim Small Footprint
The MagnaTherm’s width allows it to fit through standard doorways. Size Flow Rate Temp Rise Headloss* Flow Rate Temp Rise Headloss* GPM 152 152 190 190 222 224
°F 20 25 25 30 30 34
Ft 31.0 33.0 33.7 36.0 30.6 30.0
LPM 525 575 719 719 839 848
°C 11.1 14.0 13.9 17.0 17.0 19.0
Inches 79.8 79.8 87.0 87.0 96.7 96.7
cm 203 203 221 221 246 246
Inches 38.0 38.0 41.5 41.5 52.0 52.0
D cm 96 96 105 105 132 132
Inches 57.5 57.5 60.5 60.5 70.0 70.0
cm 147 147 154 178 178 178
E Water Gas 'Knock-down' Height Connection Connection Inches cm Groove Lock (NPT) 60.8 154 3" 2" 60.8 154 3" 2" 71.0 180 3" 2" 71.0 180 3" 2" 80.8 205 4" 2" 80.8 205 4" 2"
Condensate
Trap Line 1" 1" 1" 1" 1" 1"
Minimum Gas Boiler Water Heater Vent Vent Product Weight Operating Weight Shipping Weight Supply Thermal Efficiency Thermal Efficiency Diameter Length cm MBH KW MBH KW % % Lbs Kg Lbs Kg Lbs Kg " w.c. Pa in (cm) ft (m) Temperature Rise in °F Temperature Rise in °C 1600 147 1599 469 1512 443 95.0 96 1390 630 1562 709 1590 721 4 996 6 (15) 100 (30.5) 30°F 35°F 40°F 17°C 19°C 22°C 147 2000 1999 586 1883 552 95.0 96 1390 630 1562 709 1590 721 4 996 8 (20) 100 (30.5) Size Size Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Loss* Flow Head Los 154 2500 2499 732 2374 696 95.0 96 1785 810 2039 925 1985 900 4 996 8 (20) 100 (30.5) GPM Feet GPM Feet GPM Feet LPM m LPM m LPM m 178 3000 3000 879 2814 825 95.0 95 1785 810 2039 925 1985 900 4 996 10 (25) 100 (30.5) 1600 1600 100 14.0 87 10.0 76 8.0 379 4.3 329 3.0 288 2.5 Dimensional Data Sizing Data 178 3500 3500 1025 3317 972 95.0 96 2278 1033 2742 1244 2478 1124 4 996 10 (25) 100 (30.5) 2000 128 23.5 109 17.1 95 13.6 2000 485 7.2 413 5.2 360 4.2 178 4000 4000 1172 3724 1091 95.0 96 2278 1033 2742 1244 2478 1124 4 996 12 (30) 100 (30.5) 2500 158 23.6 136 17.6 119 13.6 2500 599 7.0 514 5.0 449 4.1 E Condensate Water Gas A 190 C25.8 Input Rate Outp Size 34.2 B 164 142 D 18.9'Knock-down' Height Connection Connection 3000 719 10.4 621 7.9 538 5.8 Size 3000 Trap 3500 222 30.6 190 23.6 166 18.6 3500 839 9.0 719 7.0 629 6.0 Inches cm Inches cm Inches cm Inches cm Inches cm Groove Lock (NPT) Line MBH KW MBH Venting and piping locations on 255 38.2 190 4000 965 11.6 825 8.7 6.9 1600 400029.3 1600 75 79.8 203 218 38.0 28.596 57.5 147 22.5 60.8 154 3" 2" 1" 1599 719 469 1512 Back of MagnaTherm do vary 2000 29.3 75 79.8 203 38.0 96 57.5 147 60.8 154 3" 2" 1" 2000 1999 586 1883 Air from size to size. Volume Water Heater, Water 2500 30.8 78 87.0Flow Requirements 221 41.5 105 60.5 154 71.0 180 3" 2" 1" 2500 2499 732 2374 Temperature Rise in °C 3000 30.8 78 87.0 221 41.5 105 60.5 178 71.0 180 3" 2" 1" 3000 3000 879 2814 17°C 19°C 22°C For further details of MagnaTherm 3500 34.5 88 96.7 246 52.0 132 70.0 178 80.8 205 4" 2" 1" 3500 3500 1025 3317 Size Flow Head Loss* Flow Head Loss* Flow Head Loss* specifications, please the Rise 246 Size 34.5 Data Flow Rate Temp Headloss* Rise 178 Headloss* 4000Dimensional 88 see 96.7 52.0Flow Rate 132 Temp70.0 80.8 205 4" 2" 1" 4000 4000 Data 1172 3724 Sizing Dimensional Data Sizing LPM m LPM m LPM m Dimensional Data Sizing MagnaTherm Submittal Data GPM °F Ft LPM °C m 1600 379 4.3 329 3.0 288 2.5 1600 which are 152available online 20 31.0 525 11.1 10.1 Sheets EE Condensate Condensate E Condensate Gas Water Gas 2000 485 7.2 413 5.2 360 4.2 Water Gas Water A B C D A B 25 B C C D D Siz A Input Siz Ra Size 2000 152 33.0 575 14.0 10.1 Size Connection Trap at www.laars.com Size Connection Connection 'Knock-down' Height Connection Height Connection Trap 'Knock-down' Height'Knock-down' TrapConnection 2500 599 7.0 514 5.0 449 4.1 Size 2500 190 25 33.7 719 13.9 10.0 Inches cm Inches cm Inches cm Inches cm Inches cm Groove Lock (NPT) Line Boiler, Water Flowcm Requirements InchesInches cm cm Inches cmcm Inches cm cm Inches Groove Lock Line Inches Inches cm cm Inches Inches Inches Groove Lockcm (NPT) Line (NPT) MBH 3000 719 10.4 621 7.9 538 5.8 Water 2" 3000 190 17.0 96 11.0 57.5 1600 75 29.3 29.3 7530203 79.836.0 203 719 38.0 57.5 147154 60.8 60.8 3" 154 2" 3" 2" 1" 160 79.8 38.0 96 57.5 147 154 3" 1" 1" 1600 29.3 1600 79.8 75 38.0 203 96 147 60.8 1599 160 3500 839 9.0 719 7.0 629 6.01600 Outlet 3500 222Temperature 17.0 96 9.0 57.5 Rise 38.0 147 154 3" 1" 2000 75 29.3 29.3 7530 79.830.6 203 839 38.0 57.5 96 57.5 147154 60.8 60.8 3" 154Temperature 3" Rise 2" 1" 200 4000 965 11.6 825 8.7 719 6.92000 29.3 2000 79.8 75 203in °F 79.8 38.0 203 96 147 60.8 2" 1"in °C 2" 2000 1999 200 4000 224 848 41.5 19.0 105 9.1 60.5 2500 78 30°F 30.8 7834221 87.030.0 22140°F 60.5 154180 71.0 71.0 3"17°C 180 180 2" 3" 19°C 2" 1"22°C 250 35°F 87.0 30.8 154 3" 2" 1" 2500 30.8 2500 87.0 78 41.5 221 105 41.5 60.5 105 154 71.0 1" 2500 2499 250 Water MagnaTherm Electrical Size 3000 Size 3000Flow 30.8 Loss* 78 87.0 221 105 41.5 60.5 105 105 60.5 178 71.0 180Loss* 3" 1"Head Loss* 2" 1" Head Loss* 300 Flow221 Head87.0 Loss* Head Loss* Flow3" Head FlowOptions 30.8 221 41.5 60.5 178 180 3" 2" 1" 3000 30.8 78 Head 87.0 78 41.5 Flow 178 71.0 180 71.0 2" Flow 3000 3000 300 96.7 246 70.0 178 205 4" Feet96.7 88 GPM246 Feet LPM4" m 2" Inlet LPM LPM1" m 3500GPM 34.5 88 96.7 52.0 GPM 246 132 Feet52.0 52.0 70.0 132 132 70.0 178205 80.8 80.8 205 4" 1" m2" 2" 1" 350 3500 34.5 3500 88 34.5 178 80.8 3500 3500 350 Current (FLA) 4000 400010088 34.5 34.5 8887 246 10.0 96.7 52.0 76246 246 132 8.0 52.0 52.0 70.0 132 132 70.0 178 80.8 205 4" Voltage 2" 1" 400 1600 4000 1600 14.096.7 88 3794" 4.3 2" 329 288 1" 2.5 96.7 70.0 178 205 4" 4000 34.5 178 80.8 205 80.8 1" 3.02" 4000 400 2000 3500 3000 3500 2000 128 23.5 109 17.1 95 13.6 2000 485 7.2 413 5.2 360 1600 4.2 120V Phase 449 17.0 4.1 22.6 N/A N/A N/A 2500 158 23.6 136 17.6 119 13.6 2500 599 7.0 514 Single5.0 220V Phase 538 10.0 5.8 11.3 N/A N/A N/A 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 Single7.9 Vent 208V Phase 629 N/A 6.0 12.7 19.4 19.4 19.4 Water Requirements 3500Boiler, 222 Flow 190 23.6 166 18.6 3500 839 9.0 719 Three7.0 Boiler, Water Flow30.6 Requirements Boiler, Water Flow Requirements 480V Phase 719 N/A 6.9 6.2 8.7 8.7 8.7 4000 255 38.2 218 28.5 190 22.5 4000 965 11.6 825 Three8.7 600V Three Phase N/A 4.5 5.9 5.9 5.9 Temperature Rise in °F Temperature Rise in °C Temperature Rise in °F Temperature Rise in °C Temperature Rise in °F Temperature Rise in °C 30°F 35°F 40°F 17°C 19°C 22°C Volume Water 30°FRequirements 35°F40°F 40°F 17°C 19°C 19°C 22°C 22°C 30°FHeater, Water Flow 35°F 17°C Loss* Loss* Head Loss* Loss* Head Size Size Size Size Flow FlowHead Head Head Loss*Loss*Flow FlowFlowHead HeadHead Loss*Loss*Flow Flow Head Loss* Loss* Flow FlowHead Head Head Loss* Loss*Flow Flow FlowHead Head Head Loss* Loss*Flow Flow Head Loss* Loss* Flow Size Head Loss*Flow Flow Size Head Loss*Flow Feet LPM m GPM GPM Feet Feet Feet GPM GPMGPM Feet Feet Feet GPM GPM Feet LPM LPM m m m LPM LPM LPM m m m LPM LPM m GPM Feet GPM LPM m The MagnaTherm’s heat exchanger design is the latest from MagnaTherm Electrical Options Size 1600 100 14.0 76 8.0 2.5 Flow14.0 Rate Temp Rate76Temp10.0 Rise 8.0 Headloss* 1600 1600 4.3 379 100 Rise 14.0 10.0 Flow87 87 10.0 76 8.0 379 329 4.3 4.3 3.0 329 329 288 3.0 3.0 2.5 288 288 2.5 1600 1600 100 87 Headloss* 379 1600 Laars engineering. You can rely on years of worry free service Ft 17.1 LPM 109 13.6 4.2 2000GPM 128°F 109 23.5 23.5 109 95 °C17.1 17.1 13.6 m 95 95 13.6 2000 7.2 485 485 413 7.2 7.2 5.2 413 413 360 5.2 5.2 4.2 360 360 4.2 2000 128 2000 23.5 128 2000 485 2000 Current (FLA) knowing that the heart Voltage of the MagnaTherm was designed and 136 17.6 13.6 4.1 31.017.6 525 2500152 15820 136 23.6 23.6 136 119 11.1 17.6 13.610.1119 119 13.6 2500 7.0 599 599 514 7.0 7.0 5.0 514 514 449 5.0 5.0 4.1 449 449 4.1 158 2500 23.6 158 2500 599 2500 1600 2000 3500 3000 35002500 4000 1600 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 built at the Laars headquarters in 2000 152 25 33.0 575 14.0 10.1 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 3000 190 34.2 164 25.8 142 18.9 3000 719 10.4 621 7.9 538 5.8 120V manufacturing Single Phase 17.0 22.6 N/A N/A N/A N/A 190 23.6 18.6 6.0 33.723.6 719 3500190 22225 190 30.6 30.6 190 166 13.9 23.6 18.610.0166 166 18.6 3500 9.0 839 839 719 9.0 9.0 7.0 719 719 629 7.0 7.0 6.0 629 629 6.0 222 3500 30.6 222 3500 839 3500 Rochester, NH,220V USA. Single Phase 10.0 11.3 N/A N/A N/A3500 N/A 2500 218 28.5 22.5 6.9 36.028.5 719 4000190 25530 218 38.2 38.2 218 190 17.0 28.5 22.511.0190 190 22.5 4000 11.6 965 965 825 11.6 11.6 8.7 825 825 719 8.7 8.7 6.9 719 719 6.9 255 4000 38.2 255 4000 965 4000 208V Three Phase N/A 12.7 19.4 19.4 19.44000 19.4 3000 3500 222 30 30.6 839 17.0 9.0 480V Three Phase N/A 6.2 8.7 8.7 8.7 8.7 *Headloss is for the heater only (no piping). 4000Volume 224 34 Water 848 19.0 9.1 Water Flow Volume Water Heater, Water30.0 Flow Requirements Requirements Volume Water Water FlowHeater, Requirements 600V Three Phase N/A 4.5 5.9 5.9 5.9 5.9 Heater,
D
The MagnaTherm comes with a centralized electrical load center that allows for various voltage packages (single andFlow three phase), to better match job site Boiler, Water Requirements requirements.
1600 2000 2500 3000 3500 4000
cm 75 75 78 78 88 88
C
Sizing Data
C
cm
Inches 29.3 29.3 30.8 30.8 34.5 34.5
B
Sizing Data
Inches 57.5 57.5 60.5 60.5 70.0 70.0
29.3 removable 75 79.8 203 complete 38.0 96 Two1600 full-swing doors allow access 2000 29.3 75 79.8 203 38.0 96 to electrical, controls, gas valves and accessories from 2500 30.8 78 87.0 221 41.5 105 the front 3000 of the 30.8 MagnaTherm 78 87.0for quick 221 setup. 41.5 105 4000 34.5 88 Electrical Flexibility
A
Size
m 10.1 10.1 10.0 11.0 9.0 9.1
E Condensate Water Gas 'Knock-down' Height Connection Connection Trap Inches cm Groove Lock (NPT) Line 60.8 154 3" 2" 1" 60.8 154 3" 2" 1" 71.0 180 3" 2" 1" 71.0 180 3" 2" 1" 80.8 205 4" 2" 1" 80.8 205 4" 2" 1"
Rate Output Rate Size WaterInput Boiler, Flow Requirements
Front
Side
Back
Boiler, Water Flow Requirements
Designed and Made in America
Optimized Heat Transfer Technology and Extended Life
The MagnaTherm’s efficiency secret lies in its precise alignment Size of micro-finned heating tubes combined with highly engineered flue gas channels. This arrangement optimizes the flow of flue 1600 2000 gases in order to transfer maximum heat to the water inside the 2500 heating tubes and extending heat exchanger life. 3000 3500 4000 Boasting an AHRI certified 95% or higher Thermal Efficiency, indoor or outdoor certification, a 5:1 turndown and the Laars boiler VARI-PRIMETM control package, the Laars MagnaTherm is the clear choice when selecting a high efficiency boiler or volume water heater.
Volume Water Heater, Flow Requirements
Flow Temp Rise Headloss* Flow Rate Size Flow Rate Rate TempFlow Rise Rate Headloss* FlowHeadloss* Rate Temp Temp Rise Rise Headloss* Headloss* Flow Rate Size Temp Rise Headloss* Temp Rise GPM °F Ft LPM °C m GPM Ft °F LPM Ft °C LPM m °C m GPM °F 152 31.0 10.1 1600 20 152 31.0 20 20 525 31.0 11.1 525 525 10.1 11.1 11.1 10.1 152 1600 152 33.0 10.1 2000 25 152 33.0 25 25 575 33.0 14.0 575 575 10.1 14.0 14.0 10.1 152 2000 190 33.7 10.0 2500 25 190 33.7 25 25 719 33.7 13.9 719 719 10.0 13.9 13.9 10.0 190 2500 190 36.0 11.0 3000 30 190 36.0 30 30 719 36.0 17.0 719 719 11.0 17.0 17.0 11.0 190 3000 222 30.6 17.0 9.0 3500 30 222 30.6 30 30 839 30.6 17.0 839 839 9.0 17.0 9.0 222 3500 224 30.0 19.0 9.1 4000 34 224 30.0 34 34 848 30.0 19.0 848 848 9.1 19.0 9.1 224 4000
Water Hardness of 1-10 grains per gallon. Allowable pH: 6.5 to 9.5 *Headloss is for the heater only (no piping).
MagnaTherm Electrical Options
MagnaTherm Electrical Options Voltage 120V Single Phase 220V Single Phase 208V Three Phase 480V Three Phase 600V Three Phase
1600 17.0 10.0 N/A N/A N/A
2000 22.6 11.3 12.7 6.2 4.5
Current (FLA) 3500 N/A N/A 19.4 8.7 5.9
3000 N/A N/A 19.4 8.7 5.9
3500 N/A N/A 19.4 8.7 5.9
4000 N/A N/A 19.4 8.7 5.9
MagnaTherm MagnaTherm Electrical Options Options MagnaTherm Electrical OptionsElectrical Voltage 120V Single Phase 220V Single Phase 208V Three Phase 480V Three Phase 600V Three Phase
Voltage Voltage 1600 2000 120V 120V Single Single Phase 22.6 17.0 Phase 220V 220V Single Single Phase 11.3 10.0 Phase 208V 208V Three Three Phase 12.7 N/A Phase 480V 480V Three Three Phase 6.2 N/A Phase 600V 600V Three Three Phase 4.5 N/A Phase
Current Current (FLA) (FLA) Current (FLA) 1600 1600 3500 2000 2000 3000 3500 3500 3500 17.0 17.0 N/A 22.6 22.6 N/A N/A N/A N/A 10.0 10.0 N/A 11.3 11.3 N/A N/A N/A N/A N/A N/A 19.4 12.7 12.7 19.4 19.4 19.4 19.4 N/A N/A 8.7 6.2 6.2 8.7 8.7 8.7 8.7 N/A N/A 5.9 4.5 4.5 5.9 5.9 5.9 5.9
3000 3000 4000 N/A N/A N/A N/A N/A N/A 19.4 19.4 19.4 8.7 8.7 8.7 5.9 5.9 5.9
3500 3500 N/A N/A N/A N/A 19.4 19.4 8.7 8.7 5.9 5.9
4000 4000 N/A N/A N/A N/A 19.4 19.4 8.7 8.7 5.9 5.9
®
VARI-PRIME TM Control Technology Laars VARI-PRIMETM flow control matches the modulation rate of a MagnaTherm’s combustion system to the rate of a variable speed boiler pump. This unique on board control allows the MagnaTherm boiler to mirror the heating system’s profile during varying load conditions and optimize overall efficiency.
COMMERCIAL HIGH EFFICIENCY
Boiler pumps are typically sized for the maximum flow that a boiler needs, but boilers rarely operate at maximum capacity. A pump’s power consumption can drop by as much as 50% with only a 20% reduction in speed. By replacing a boiler’s typical on/off pump with a VARI-PRIMETM equipped MagnaTherm control and variable speed pump, over a thousand dollars in boiler pump watt usage can be saved per year. The payback for the variable speed pump setup can be realized in as little as one year!
Condensing Boiler and Volume Water Heater
The combined potential energy savings of the MagnaTherm’s high efficiency combustion coupled with the VARI-PRIMETM control system is huge. Only the Laars MagnaTherm with built in VARI-PRIMETM controls can offer such savings in one package!
with VARI-PRIME TM
Pump Control On-Board
VARI-PRIMETM Pump Control Energy Savings Example Typical boiler pump energy use seen over a full heating season located in upstate New York (September through April). When an On/Off Boiler Pump is used - kWH consumed When the Laars VARI-PRIME is used - kWH consumed
18,773 5,540
Annual VARI-PRIMETM kWH savings Annual Percent Pump Electrical Savings Annual Dollar Savings*
13,233 70% $1,417
View our entire product line at www.Laars.com
A Three Million BTU/hr MagnaTherm using VARI-PRIMETM pump control and a Goulds 22SH variable speed boiler pump were used in this example. *2013 US Average of 11 cents per kWH used, source US Energy Information Administration. See Laars VARI-PRIMETM white paper 9185 for complete details.
Lead Lag Cascading of up to 8 MagnaTherms HLW
The advanced MagnaTherm control system also includes a cascading feature that allows for up to eight units to be lead lagged together. This results in a modulating heating cell of up to 32 million BTU/hr with a combined 40:1 turndown. Also included is an auto rotation function that periodically changes lead boiler to evenly spread service between all boilers. Communication with Building Automation Systems happens seamlessly via a built-in Modbus protocol included with all MagnaTherm boilers. The Laars Gateway is available for use with BacNET and LON networks.
1.6, 2.0, 2.5, 3.0, 3.5 and 4.0 MILLION BTU/HR
• Fax 800.559.1583 (Customer Service and Product Support) 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130 800.900.9276
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1504 Document 1288C
95% Certified Thermal Efficiency Indoor and Outdoor Installation Laars Heat Exchanger Design
®
VARI-PRIME TM Control Technology Laars VARI-PRIMETM flow control matches the modulation rate of a MagnaTherm’s combustion system to the rate of a variable speed boiler pump. This unique on board control allows the MagnaTherm boiler to mirror the heating system’s profile during varying load conditions and optimize overall efficiency.
COMMERCIAL HIGH EFFICIENCY
Boiler pumps are typically sized for the maximum flow that a boiler needs, but boilers rarely operate at maximum capacity. A pump’s power consumption can drop by as much as 50% with only a 20% reduction in speed. By replacing a boiler’s typical on/off pump with a VARI-PRIMETM equipped MagnaTherm control and variable speed pump, over a thousand dollars in boiler pump watt usage can be saved per year. The payback for the variable speed pump setup can be realized in as little as one year!
Condensing Boiler and Volume Water Heater
The combined potential energy savings of the MagnaTherm’s high efficiency combustion coupled with the VARI-PRIMETM control system is huge. Only the Laars MagnaTherm with built in VARI-PRIMETM controls can offer such savings in one package!
with VARI-PRIME TM
Pump Control On-Board
VARI-PRIMETM Pump Control Energy Savings Example Typical boiler pump energy use seen over a full heating season located in upstate New York (September through April). When an On/Off Boiler Pump is used - kWH consumed When the Laars VARI-PRIME is used - kWH consumed
18,773 5,540
Annual VARI-PRIMETM kWH savings Annual Percent Pump Electrical Savings Annual Dollar Savings*
13,233 70% $1,417
View our entire product line at www.Laars.com
A Three Million BTU/hr MagnaTherm using VARI-PRIMETM pump control and a Goulds 22SH variable speed boiler pump were used in this example. *2013 US Average of 11 cents per kWH used, source US Energy Information Administration. See Laars VARI-PRIMETM white paper 9185 for complete details.
Lead Lag Cascading of up to 8 MagnaTherms HLW
The advanced MagnaTherm control system also includes a cascading feature that allows for up to eight units to be lead lagged together. This results in a modulating heating cell of up to 32 million BTU/hr with a combined 40:1 turndown. Also included is an auto rotation function that periodically changes lead boiler to evenly spread service between all boilers. Communication with Building Automation Systems happens seamlessly via a built-in Modbus protocol included with all MagnaTherm boilers. The Laars Gateway is available for use with BacNET and LON networks.
1.6, 2.0, 2.5, 3.0, 3.5 and 4.0 MILLION BTU/HR
• Fax 800.559.1583 (Customer Service and Product Support) 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130 800.900.9276
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1504 Document 1288C
95% Certified Thermal Efficiency Indoor and Outdoor Installation Laars Heat Exchanger Design