C85 Long Life EOS Analyzer INSTRUCTION MANUAL ENGLISH

COp 28 CO2% 6.2

Eff X-Air

O2 CO Air Free

CO2 CO Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

1-800-547-5740 • Fax: (503) 643-6322 www.ueitest.com • Email: [email protected] 1

TABLE OF CONTENTS Display Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analyzer Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Menu / Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Auxiliary Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust Screen Contrast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Customizeable Header (on print-outs) . . . . . . . . . . . . . . . . . . . Set Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Viewing and Printing Reports. . . . . . . . . . . . . . . . . . . . . . . . . . Print Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Fast Start (Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Select Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connect Probe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Select Parameter to View / Log / Print . . . . . . . . . . . . . . . . . . Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Aux. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Eff- X Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . O2 CO Air Free. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CO2 CO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Date Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 3 4 4 4 4 4 4 5 5 6 6 7 7 8 8 8 8 8 8 8 9 9 9 9 9 9

Where To Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11 What Results Are Generally Acceptable. . . . . . . . . . . . . . . . 11 General Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Pre Test Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Setting Inlet Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Analyzer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Emptying, Cleaning Water Trap . . . . . . . . . . . . . . . . . . . . . . 12 Changing Particle Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Replacing Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Post Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Periodic Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Analyzer Re-Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Other Important Factors Related To Combustion. . . . . . . . . 14 Combustion Measurement Terms . . . . . . . . . . . . . . . . . . . . . . 14 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Electromagnetic Compatibility. . . . . . . . . . . . . . . . . . . . . . . . . 15 Limited Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

DISPLAY SYMBOLS Excess Air

Theoretical amount of air in excess of level needed to completely burn fuel

Delta T

Differential temperature

Losses

Losses calculated from oxygen and type of fuel

Inlet Temperature

Temperature measured and stored to calculate efficiency

Flue Temperature

Temperature measured by the flue probe or accessory k-type thermocouple

Ratio Carbon Monoxide

2

CO to CO2 Ratio. Used to indicate the general condition of the combustion process Carbon Monoxide measure in parts per million ppm

Carbon Dioxide

Carbon Dioxide measured in percentage%

Oxygen

Oxygen calculated

Efficiency

Calculated combustion efficiency based on net temperature, oxygen and fuel selected

ANALYZER OVERVIEW Infrared Printer Port

2 Line Backlit Display

COp 28 CO2% 6.2 BACKLIGHT / “s“ UP Press to HOLD values on display and navigate UP. Press and hold to turn Backlight on/off. PUMP / “t“ DOWN Press to turn pump on/off and navigate DOWN

On/Off Button Rotary Test Selector Dial

Eff X-Air

O2 CO Air Free

Temp

Aux

Battery Compartments in back under boot

Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

AC Power/Charge Indicator Light

SEND/ENTER “ ” to Select and Print

CO2 CO

Particle Filter Inside Water Trap

Flue Probe Temperature Plug (Plugs into T1)

Water Trap

Narrow Pin MUST be on the Right hand side.

Protective Rubber Boot w/ built-in Magnets

Flue Probe Gas Inlet Plug

Battery Charge AC Adapter Temperature Connections Flue Probe Temp: T1

Flue Gas Inlet Connection Water Trap Drain

3

GETTING STARTED SAFETY NOTES Before using this meter, read all safety information carefully. “WARNING” is used to indicate conditions or actions that may pose physical hazards to the user. “CAUTION” is used to indicate conditions or actions that may damage this instrument.

WARNING!

This analyzer extracts combustion gases that may be toxic in relatively low concentrations. These gases are exhausted from the back of the instrument. This instrument must only be used in well-ventilated locations. It must only be used by trained and competent persons after due consideration of all the potential hazards.

MENU SET TIME

MENU / SETUP

SET TIME

Eff X-Air

O2 CO Air Free

MENU SET TIME

CO2 CO

SET TIME 08:30:15 _

SET TIME 09:30:15 _

SET TIME 09:30:15

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Rotate dial to Menu

Eff X-Air

O2 CO Air Free

CO2 CO

SET TIME shows press “Send” Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

Eff X-Air

O2 CO Air Free

CO2 CO

Clock displays with the cursor underneath the first digit. Press “s“ UP or “t“ DOWN to increase or decrease and C85 press CO CO TEMP ENTER “ ” to set and proceed to the next digit. Temp

Aux

Status

Fuel

Date Time

Menu

Eff X-Air

MENU SET TIME

Eff X-Air

CO2 CO

O2 CO Air Free

CO2 CO

Press “Send” to complete Press “s“ UP or “t“ setting the time once all DOWN to increase or digits are set. decrease and press ENTER “ ” to set and to proceed to theC85 next digit. C85 Temp

Aux

Temp

Status

Fuel

Date Time

Menu

Status

Fuel

Date Time

Menu

CO2 CO TEMP

CO2 CO TEMP

2

LONG LIFE EOS ANALYZER

LONG LIFE EOS ANALYZER

O2 CO Air Free

Aux

LONG LIFE EOS ANALYZER

LONG LIFE EOS ANALYZER

SET DATE

Eff X-Air

O2 CO Air Free

MENU SET DATE

CO2 CO

SET DATE _ 01/21/15

SET DATE 01/21/15_

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

Rotate dial to Menu LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “SET DATE” Press ENTER “ ” Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

4

SET DATE _MM/DD/YY

Eff X-Air

O2 CO Air Free

CO2 CO

Set date displays with MM/DD/YY Press “s“ UP or “t“ DOWN to select a different format press ENTER “ ”C85 to proceed. CO CO TEMP Use MM/DD/YY for North American. Temp

Aux

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Eff X-Air

O2 CO Air Free

CO2 CO

Date displays with the Press ENTER “ ” to cursor underneath the first complete setting the date digit. Press “s“ UP or once all digits are set. “t“ DOWN to increase or decrease and C85 press C85 CO CO TEMP ENTER “CO CO TEMP ” to set and proceed to next digit. Temp

Aux

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

Temp

Aux

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

MENU SET TIME

MENU / SETUP (CONT.)

SET AUXILIARY SCREEN (Aux)

Eff X-Air

O2 CO Air Free

MENU AUX

CO2 CO

AUXPAGE1 LINE 1

AUX PAGE1

AUXPAGE1 01/20/15

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

Eff X-Air

Rotate dial to Menu

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “AUX” Press ENTER “ ”

LONG LIFE EOS ANALYZER

Temp

Aux

Status

Fuel

Date Time

Menu

Eff X-Air

Eff X-Air

O2 CO Air Free

CO2 CO

AUXPAGE1 LINE 2 shows press “Send” to continue to set line 2. Press “s“ UP or “t“ DOWN select between available C85 parameters CO CO and TEMP press ENTER “ ” to set. Temp

Aux

AUX PAGE 1 shows press ENTER “ ” to set. Status

Fuel

Date Time

Menu

Status

Fuel

Date Time

Menu

CO2 CO

Temp

Aux

Status

Fuel

Date Time

Menu

C85

O2 CO Air Free

Temp

Fuel

Date Time

Menu

Eff X-Air

CO2 CO

Temp

Status

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN select between available parameters and press ENTER “ ” to set. Temp

Status

Fuel

Date Time

Menu

CO2 CO TEMP

LONG LIFE EOS ANALYZER

AUX EXIT

O2 CO Air Free

AUX PAGE2 shows press Press ENTER “ ENTER “ ” to proceed to set page 2. Repeat the same process as page 1 to set page 2. Aux

Eff X-Air

Aux

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Fuel

Date Time

Menu

CO2 CO

” to exit.

Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

CO2 CO

Status

AUX PAGE2

Eff X-Air

O2 CO Air Free

AUXPAGE1 LINE 1 shows press ENTER “ ” to continue to set line 1.

C85

CO2 CO TEMP

2

LONG LIFE EOS ANALYZER

O2 CO Air Free

AUXPAGE1 EXIT shows press ENTER “ ” to proceed.

Eff X-Air

Aux

C85

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

AUXPAGE1 EXIT

Eff X-Air

CO2 CO

Temp

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

AUXPAGE1 LINE 2

O2 CO Air Free

Aux

CO2 CO TEMP

LONG LIFE EOS ANALYZER

LONG LIFE EOS ANALYZER

MENU SET TIME ADJUST CONTRAST

Eff X-Air

O2 CO Air Free

MENU CONTRAST

CO2 CO

CONTRAST SET 100

CONTRAST SET 150

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Rotate dial to Menu

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “CONTRAST” Press ENTER “ ” Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ Press ENTER “ ” to exit. DOWN to adjust screen contrast. NOTE: The higher the value the lighter the digits appear C85 C85 Aux

Status

Temp

Aux

Fuel

Date Time

Menu

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Status

Temp

Fuel

Date Time

Menu

CO2 CO TEMP

LONG LIFE EOS ANALYZER

5 5

MENU SET TIME

MENU / SETUP (CONT.)

CUSTOMIZABLE HEADER (ON PRINTOUTS)

Eff X-Air

O2 CO Air Free

MENU HEADER

CO2 CO

HEADER HEADER1

_HEADER SAMPLE

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

Eff X-Air

Rotate dial to Menu

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “HEADER” Press ENTER “ ”

LONG LIFE EOS ANALYZER

Temp

Aux

Status

Fuel

Date Time

Menu

C85

_PHONE NUMBER

Eff X-Air

O2 CO Air Free

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to select HEADER 1 Press ENTER “ ” to proceed. Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

Status

CO2 CO

Fuel

Date Time

Menu

Temp

Aux

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

2

LONG LIFE EOS ANALYZER

MENU SET TIME SET LANGUAGE

Eff X-Air

O2 CO Air Free

MENU LANGUAGE

CO2 CO

LANGUAGE ENGLISH

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

Eff X-Air

LONG LIFE EOS ANALYZER

Rotate dial to Menu

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “LANGUAGE” Press ENTER “ ” Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to change language and press ENTER “ ” to set and exit Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

O2 CO Air Free

CO2 CO

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

The existing HEADER 1 Repeat the process for will display with the cursor HEADER 2 and press underneath the first digit. ENTER “ ” to proceed. Press “s“ UP or “t“ DOWN to change and C85 C85 CO CO TEMP CO CO TEMP press ENTER “ ” to set and continue to the next digit. Press ENTER “ ” to proceed. Temp

Status

Date Time

Menu

Temp

Aux

Fuel

LONG LIFE EOS ANALYZER

The existing HEADER 2 Press ENTER “ ” to exit. will display with the cursor underneath the first digit. Press “s“ UP or “t“ DOWN to change C85 and C85 CO CO TEMP CO CO TEMP press ENTER “ ” to set and continue to the next digit. Press ENTER “ ” to proceed. Temp

Eff X-Air

Aux

2

LONG LIFE EOS ANALYZER

HEADER EXIT

CO2 CO

Aux

6

HEADER HEADER2

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

MENU SET TIME

MENU / SETUP (CONT.)

VIEWING AND PRINTING REPORTS

Eff X-Air

O2 CO Air Free

MENU REPORT

CO2 CO

REPORT VIEW

LOG 01 01/21/15

LOG 02 01/25/15

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

Eff X-Air

LONG LIFE EOS ANALYZER

Rotate dial to Menu

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “REPORT” Press ENTER “ ” Temp

Aux

Status

Fuel

Date Time

Menu

MENU SET TIME

Eff X-Air

O2 CO Air Free

Eff X-Air

CO2 CO

Press “s“ UP or “t“ DOWN to “VIEW” press ENTER “ ” to proceed. Temp

Status

Fuel

Date Time

Menu

C85

C85

CO2 CO TEMP

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Press and hold “s“ UP or “t“ DOWN to select log to view (LOG 01, LOG 02). Press “s“ UP or “t“ DOWN to scroll and view C85 CO CO on TEMPsecond line. parameters Temp

Aux

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

MENU REPORT

CO2 CO

O2 CO Air Free

Aux

LONG LIFE EOS ANALYZER

REPORT DEL ALL

Eff X-Air

O2 CO Air Free

CO2 CO

Press “Send” to print LOGGED results. press ENTER “ ” again to abort. Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

DEL ALL YES

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

Eff X-Air

LONG LIFE EOS ANALYZER

Rotate dial to Menu

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “REPORT” Press ENTER “ ” Temp

Aux

Status

Fuel

Date Time

Menu

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “DEL ALL” Press ENTER “ ” to proceed. Temp

Aux

Status

Fuel

Date Time

Menu

C85

C85

CO2 CO TEMP

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to select Yes or No Press ENTER “ ” to proceed. Analyzer will automaticallyC85 return to the CO CO TEMP menu. Temp

Aux

Status

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

LONG LIFE EOS ANALYZER

MENU SET TIME PRINT SETUP

Eff X-Air

O2 CO Air Free

MENU PRINTING

CO2 CO

PRINTING KMIRP

Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Rotate dial to Menu

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to “PRINTING” Press ENTER “ ” Temp

Aux

Status

Fuel

Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Eff X-Air

O2 CO Air Free

CO2 CO

Press “s“ UP or “t“ DOWN to select printer. Press ENTER “ ” to select. Analyzer will automaticallyC85 return to the CO CO TEMP menu. Temp

Aux

Status

Fuel

Printer Options • KMIRP2 for legacy infrared thermal printer • IRP-3 for easy-load fast printer NOTE: If using the KMIRP2 printer and incomplete reports are printing check the print setup

Date Time

Menu

2

LONG LIFE EOS ANALYZER

7

SET FUEL BASIC FAST START (OPERATION) NAT GAS

01/21/15 TIME 90 1. POWER ON

Eff X-Air

O2 CO Air Free

2. SELECT FUEL

01/21/15 TIME 90

CO2 CO

Eff X-Air

SET FUEL NAT GAS

CO2 CO Temp

Aux

Temp

Aux

O2 CO Air Free

Status

Status

Fuel

Fuel

Menu

Date Time

Menu

Date Time

C85

Eff X-Air

O2 CO Air Free

C85

CO2 CO

TEMP of fresh air and allow to countdown. On Power onCOinCOarea sealed combustion appliances (ducted inlet) connect flue probe and power on outside and allow to countown to set inlet temperature. (see page 12) 2

Temp

Aux

LONG LIFE EOS ANALYZER

Status

Fuel

Date Time

Menu

3. CONNECT PROBE

C85

CO2 CO TEMP

CO2 CO TEMP

Rotate test selector to Fuel. LONG LIFE EOS ANALYZER

COp 28 CO2% 6.2

Eff X-Air

Fuel

Date Time

Menu

2

LONG LIFE EOS ANALYZER

O2 CO Air Free

COp 28 CO2% 6.2

CO2 CO Temp

Aux Status

Fuel Date Time

Menu

C85

Eff X-Air

CO2 CO TEMP

Rotate selector to desired test.

Eff X-Air

O2 CO Air Free

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

8

Date Time

Rotate selector to Aux.

12:34:56 01/02/03

Eff X-Air

O2 CO Air Free

CO2 CO Temp

Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

The auxilliary menu shows user defined parameters. The display alternates between page 1 and page 2. To set up the auxilliary menu see instructions on page 5.

Aux

Date Time

Fuel

Menu

Aux

Temp Fuel

Press “Send” to print results or press and hold “Send” to log results from any screen. C85

CO2 CO

Status

Temp

Status

CO2 CO TEMP

Rotate selector to Status.

Aux

CO2 CO

LONG LIFE EOS ANALYZER

Status

The status menu shows battery life and the number of days until suggested re-certification. (CAL)

O2 CO Air Free

Aux

LONG LIFE EOS ANALYZER

BAT CAL 300

Temp

Status

4. SELECT PARAMETER TO VIEW / C85 LOG / PRINT CO CO TEMP

Eff X-Air

Insert Flue Probe in stack. Adjust the cone so the end of the probe is approximately at the center of the stack (4” stack adjust cone to aprox. 2” from end of probe.)

CO2 CO

Aux

LONG LIFE EOS ANALYZER

Connect flue probe thermocouple connector to T1, and connect flue probe to water trap as shown above.

O2 CO Air Free

Press “s“ UP or “t“ DOWN to scroll and press “Send” to select desired fuel. Bottom line displays selected fuel.

LONG LIFE EOS ANALYZER

Eff / X-Air

EfG 88.1 X 31.4

Eff X-Air

O2 CO Air Free

CO2 CO Temp

Aux Status

Fuel Date Time

Menu

Rotate selector to Eff X-Air. The Eff/X-Air screen shows calculated combustion efficiency using a Gross Condensing calculation and excess air. When below condensing temperature the efficiency calculation includes and estimated energy recovered during condensation that increases combustion efficiency. This calculated value is not the same as AFUE. Excess air is a calculated value representing the amount of air above the level needed to completely burn all of the fuel.

O2 CO Air Free Rotate selector to O2 CO Air Free.

O2% 21.9 COa -0>-

Eff X-Air

O2 CO Air Free

The O2/CO Air free screen shows the calculated amount of O2 (from CO2 measured and fuel selected), and CO Air Free.

CO2 CO Temp

Aux Status

Fuel Date Time

Menu

COppm =

C85

C85

CO2 CO TEMP

CO2 CO TEMP

LONG LIFE EOS ANALYZER

NOTE: Negative net temperature will result in efficiency greater than 100%

LONG LIFE EOS ANALYZER

[20.9 / (20.9 - O2 measured)]

CO2 CO

Temp Rotate selector to Temp.

Rotate selector to CO2 CO.

COp 28 CO2% 6.2

Eff X-Air

O2 CO Air Free

CO2 CO

The CO2 / CO screen is a direct display of measured gases. Carbon dioxide (CO2) is displayed in percentage (%), carbon monoxide (CO) is displayed in parts per million (ppm).

Tf 75.9F Ti 69.9F

Eff X-Air

Temp

Aux Status

Date Time

Menu

O2 CO Air Free

CO2 CO Temp

Aux

Fuel

These two measurements are commonly referenced target values for appliance set up.

Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Fuel

SET FUEL NAT GAS

Eff X-Air

O2 CO Air Free

Temp

Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

Date Time Rotate test selector to Date Time.

13:27:46 01/21/15

Press “s“ UP or “t“ DOWN to scroll and press ENTER “ ” to select desired fuel. Bottom line displays selected fuel selected for calculations

CO2 CO

Aux

Rotate test selector to Fuel. The fuel selector position will display the current fuel being used for calculations.

The temperature screen will display values for flue temperature (Tf) and inlet temperature (Ti). If inlet temperature was set during initial power on, it will display that temperature. If using ambient temperature you will observe the internal handset temperature. Note: The sample pump will stop when CO is less than 40ppm.

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

CO Air free is a calculated value for carbon monoxide as if there were no dilution from air.

Eff X-Air

O2 CO Air Free

Display shows internal clock and the date.

CO2 CO Temp

Aux Status

Fuel Date Time

Menu

C85

CO2 CO TEMP

LONG LIFE EOS ANALYZER

9

WHERE TO TEST

Air Conditioning / Heat Pump Suction Line: • Temperature Verify proper: • Static Duct Pressures • Temperature Differential • Static Pressure Drop Across Coils

to condensing unit

Boiler & Water Heaters & High Efficiency Modulating Hot Water Systems Boiler Verify proper combustion: • O2 • CO Air Free • Stack Temp • Stack Draft • SSE

Water Heater Draft Verify proper combustion: • O2 • CO • Stack Temp • Efficiency

HE Boiler Instant Water Heaters Draft Verify proper combustion: • O2 • CO • Stack Temp • Efficiency Hi / Low fire Gas Pressure Send and Return Water temp

Furnaces: 80% Furnaces: 90%

10

80% Furnace Verify proper combustion: • O2 • CO • Stack Temp • Vent Pressure • Efficiency

90%+ Furnace Verify proper combustion: • O2 • CO • Stack Temp • Vent Pressure • Efficiency

Verify/Set Up • Gas Pressure

Verify/Set Up • Gas Pressure

Test • Limit Switch • Pressure Switch

Test • Limit Switch • Pressure Switch

Verify proper operation: • Static Duct Pressure • Temperature Rise • AC side Static Pressure Drop across coils

Verify proper operation: • Static Duct Pressure • Temperature Rise • AC side Static Pressure Drop across coils

WHERE TO TEST (CONT.)

Furnaces (continued): Atmospheric, Gas & Oil

Natural Gas & Propane Verify proper combustion: • O2 • CO • Stack Temp • Vent Pressure • Efficiency

Atmospheric Furnace Draft Verify proper • Temperature Rise • AC side Static Pressure Drop across coils

Test • Limit Switch • Pressure Switch

Verify proper combustion: • O2 • CO • Stack Temp • Efficiency

Set Up • Gas Pressure Verify proper: • Static Duct Pressure • Temperature Rise • AC side Static Pressure Drop across coils

Oil Furnace Verify proper combustion: • O2 • CO • Stack Temp • Stack Draft • Efficiency Test & Verify: • Smoke Set Up • Over Fire Draft Verify proper • Static Duct Pressure • Temperature Rise • AC side Static Pressure Drop across coils

WHAT RESULTS ARE GENERALLY ACCEPTABLE Atmospheric Gas Fired Burners • Oxygen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 to 9% O2 • Stack Temperature . . . . . . . . . . . . . . . . . . . . . 325 to 500°F • Draft (Water Column Inches) . . . . . . . . . . . . -.02 to -.04wc” • Carbon Monoxide (parts per million) . . . . . . . . . . .