Fire Safety Installation Instructions Model D2300CPS Fiber Optic Interface
INTRODUCTION
MOUNTING
The Model D2300CPS from Siemens Building Technologies, Inc. (See Figure 1) is a Fiber Optic interface for the MXL’s RS-485 network (MNET or XNET) or the FireFinder XLS network (HNET or XNET). It uses a two-fiber (duplex) pair between each device. The D2300CPS can function as either a repeater or an end point unit.
The D2300CPS has four keyhole slots for #6 screws. Mount the device in the locations listed below using the four #6 screws provided.
D2300CPS RS485
DATA REC
(DO NOT USE) -4 (DO NOT USE) -3 - DATA -2 + DATA -1
A DATA XTMR POWER DATA REC
B DATA XTMR
POWER
-2 +24 VDC
-1
WARNING: This module is NOT backwards compatible with the existing 2300CP. This unit uses +24VDC. Make sure to read the front of the module and connect to the correct voltage. Otherwise, serious damage to the unit will result.
Figure 1 D2300CPS Module The D2300CPS can operate in either a daisy chain (See Figure 2) or star configuration (See Figure 3). This allows for network configurations that are not possible with the RS-485 network alone. WARNING: The D2300CPS module is not listed for use by Factory Mutual. Applications requiring fiber connectivity of voice modules/systems are therefore not Factory Mutual listed. WARNING: Do not use the D2300CPS with CXL Systems.
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932 P/N 315-050018-0
A bracket (P/N 500-692880) is available for mounting the D2300CPS in any MXL enclosure that will accept a MOM-4 (See Figure 4). This bracket has the same footprint as the MOM-4 and accommodates two D2300CPS modules. An assembly kit is included with the bracket that contains four nuts and eight screws. Mount the bracket in the enclosure with the four nuts at the positions labeled X (See Figure 4). Start four of the 6-32 screws and slip the keyhole slots in the D2300CPS over them. Tighten the four screws. System 3 style rails that mount on an MBR-2 or MME-3 backbox (P/N MSR-1) are also available and can be used for mounting the D2300CPS with the System 3 MPFO Bracket. Up to three brackets can be installed on a single rail. A bracket, Model D2300-MP, is available for mounting two D2300CPS modules in any FireFinder XLS CAB enclosure. The D2300-MP fits in the same footprint as a CC-5 and mounts to the CAB-MP. A hardware kit is provided for attaching the D2300-MP to the CAB-MP and mounting two D2300CPS modules onto the D2300-MP. Mount the D2300CPS modules prior to installing the D2300-MP onto the CAB-MP. Note that when using two D2300CPS modules, the center two mounting holes on each D2300CPS share the two center studs on the D2300-MP (See Figure 5).
ELECTRICAL CONNECTIONS POWER INPUT The D2300CPS uses filtered or unfiltered 24 VDC. The D2300CPS can only be powered from the sources listed in Table 1 on page 6.
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
DUPLEX OPTICAL FIBER POWER BUDGET - MAX LOSS -13 dB 62.5/125 FIBER - 9 dB 50/125 FIBER
DUPLEX OPTICAL FIBER POWER BUDGET - MAX LOSS -13 dB 62.5/125 FIBER - 9 dB 50/125 FIBER NO CONNECTION
SUPERVISED
NO CONNECTION
SUPERVISED
DATA REC
A
-2 +24 VDC -1
RS-485 32 NODES MAX SUPERVISED
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
-2 +24 VDC -1
EOLR 120 OHMS, 1/4W P/N 140-820150
PSR-1
DATA XTMR
D2300CPS
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
-2 +24 VDC -1
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
EOLR 120 OHMS, 1/4W P/N 140-820150
DATA REC
B
A
B
A
B
D2300CPS
POWER
DATA XTMR
DATA REC
DATA XTMR
DATA REC
DATA XTMR
DATA XTMR
DATA REC
DATA REC
POWER
POWER
DATA XTM
D2300CPS
EOLR 120 OHMS, 1/4W P/N 140-820150
RCC-1
EOLR 120 OHMS, 1/4W P/N 140-820150
RCC-1
RS-485 32 NODES MAX SUPERVISED
RS-485 32 NODES MAX SUPERVISED
MMB USE THE 120W, ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
PSR-1
Figure 2 Daisy Chain Configuration (MNET Shown)
2
EOLR 120 OHMS, 1/4W P/N 140-820150
DUPLEX OPTICAL FIBER POWER BUDGET - MAX LOSS -13 dB 62.5/125 FIBER - 9 dB 50/125 FIBER
SUPERVISED TO ADDITIONAL D2300CPS MODULES
NO CONNECTION
NO CONNECTION
DATA REC
DATA XTM
DATA REC
POWER
DATA XTMR
DATA REC
DATA REC
DATA XTMR
POWER
DATA XTMR
DATAPREC
DATAPXTMR
DATAPREC
POWER
DATAPXTMR
A
B
A
B
A
B
D2300CPS
NO CONNECTION
D2300CPS
D2300CPS
-2 +24 VDC -1
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
-2 +24 VDC -1
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
-2 +24 VDC -1
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
RS-485 32 NODES MAX SUPERVISED PSR-1
MMB USE THE 120W, ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
PSR-1
Figure 3 Star Configuration (MNET Shown)
3
EOLR 120 OHMS, 1/4W P/N 140-820150
POWER
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
-2 +24 VDC -1
X
D2300CPS
BRACKET
B DATAPREC
DATAPXTMR
-2 +24 VDC -1
OMM-1
POWER
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
DATAPXTMR
POWER
DATAPREC
A
P/N 500-692880
B DATAPREC
DATAPXTMR
DATAPXTMR
POWER
DATAPREC
A
D2300CPS
X
WARNING
DISCONNECT POWER PRIOR TO REMOVING TERMINAL BLOCK PROTECTION
Figure 4 Mounting the D2300CPS in an MBR-2 or MME-3 Backbox
POWER LIMITED HNET/XNET ROUTE AS SHOWN
FIBER OPTIC CABLE
D2300-MP
TB1
P5
DLC
DATA REC
DATA XTMR
DATA REC
POWER
DATA XTMR
DATA REC
DATA XTMR
A
B
A
HNET FAIL
HNET FAIL
GND FAULT
XNET FAIL
ALARM
GND FAULT
TROUBLE
LOOP A FAIL
ZONES STATUS
ACTIVE NETWORKS CAN
D2300CPS
1
7
12
Z O N E 1
XNET
RESET POWER MODULE FAIL CAN FAIL
CLASS A OPEN
HNET FAIL
CLASS A RETURN
GND FAULT
SHORT
Z O N E 2
HNET
PSC-12
24V 12A FAIL
CLASS A OPEN
24V 4A FAIL
CLASS A RETURN SHORT
+
+
1 -
STYLE 7
-2 +24 VDC -1
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
-2 +24 VDC -1
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
POWER
+
HNET/XNET STYLE
2
3
-
-
HNET
STYLE 4
GROUND FAULT ENABLED DISABLED
NETWORK PORT
+
+
+
1
2
3
-
-
-
HNET
+
1 -
+
+
2
3
-
-
BATTERY O —
HNET
ON
B
POWER CARD FAIL
CAN FAIL
LOOP B FAIL
D2300CPS
3
2
TB3
RESET
POWER CARD FAIL
OFF
DATA REC
POWER
DATA XTMR
RESET
4
2
1
P4
NIC-C
_
+ 6
1
1
P12
TB2 19
24 H 1 13
CAB-1
Figure 5 Mounting the D2300CPS in a CAB-1 Backbox 4
18
_
N GND
2
TB4 +
P9
_
+
DATA REC
A
DATA XTMR N.C.
DATA REC
N.C.
DATA XTMR
D2300CPS
END POINT
B FACP RS-485 NETWORK MNET/HNET/XNET (SEE FIGURES 7, 8 & 9)
SUPERVISED POWER BUDGET - MAX LOSS -13 dB 62.5/125 FIBER - 9 dB 50/125 FIBER
DATA REC
A
DATA XTMR
D2300CPS
DATA REC B
DATA XTMR
SUPERVISED POWER BUDGET - MAX LOSS -13 dB 62.5/125 FIBER - 9 dB 50/125 FIBER
DATA REC
DATA REC
N.C.
DATA XTMR
FACP
A
DATA XTMR N.C.
REPEATER
D2300CPS
END POINT
B
FACP
Figure 6 Wiring the D2300CPS as both a Repeater and End Point Unit RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
USE THE 120W, ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
MMB TB1
(DO NOT USE) (DO NOT USE) -DATA +DATA
4 (DO NOT USE)
-4 -3 -2 -1
3 (DO NOT USE) 2 1 SUPERVISED
D2300CPS
STYLE 4 MNET
(DO NOT USE) (DO NOT USE) -DATA +DATA
EOLR 120 OHMS, 1/4W P/N 140-820150
-4 -3 -2 -1
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
D2300CPS SUPERVISED
(DO NOT USE) (DO NOT USE) -DATA +DATA
-4 -3 -2 -1
EOLR 120 OHMS, 1/4W P/N 140-820150
SUPERVISED
D2300CPS
REFER TO NET-7 INSTALLATION INSTRUCTIONS P/N 315-091914 EOLR 120 OHMS, 1/4W P/N 140-820150
1
2
3
TB1
4
NET-7
MOM-4
STYLE 7 MNET
Figure 7 Wiring the RS-485 MNET Network in Style 4 and Style 7 5
Table 1 SYST EM
For non-power limited wiring, the PLM-35 (Installation Instructions P/N 315-093495) must be used to comply with NFPA 70 per NEC 760. All wiring must be in accordance with Article 760 of NEC or local building codes.
POWER SOURCE
MXL
MMB-2: TB1 4-5; TB5 9-12 MMB-3: TB9 +,-; TB5 9-12 PSR-1: TB3 1-2; 3-6
FireFinder XLS
PSC-12: TB4 +,PSX-12: TB4 +,-
For additional information on the MXL/MXLV System, refer to the MXL/MXLV Manual, P/N 315-092036.
POWER SOURCE PAD-3
AUX +,-
PS-35
TB1 5-6
24 VDC CURRENT CALCULATION (MXL ONLY) The 24 VDC output ratings for the MMB/SMB and PSR-1 are: MMB-2/-3 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) SMB-2 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) PSR-1 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) The following modules all draw current from the 24 VDC supply. Add the value for each module that is installed in the enclosure where the D2300CPS is to be installed. Be sure to include the D2300CPS in this calculation.
MODULE
ACT IVE 24 VDC MODULE CURRENT
ACM-1
85mA
ASC-1
41mA
ASC-2
61mA
CMI-300
0mA
CRM-4
75mA
CSM-4
34mA + 1.5A max per circuit
CZM-4
720mA 4 zones in alarm
D2300CPS
57mA
MKB-2/-4
0mA
NET-4
0mA
NET-7
0mA
NET-7M MOI-7
QUANT IT Y
0mA 120mA
MOD-16
850mA max
MID-16
32mA max
PIM-1
0mA
BTC-1
44mA
RCM-1
130mA
ZAC-30
3A at 30W
OCC-1
17mA
ZC1-8B
170mA
ZC2-8B
342mA
ZC2-4AB
167mA
ZC3-4AB
168mA
ZCT-8B
78mA T OTAL
6
T OTAL
EOLR 120 OHMS, 1/4W P/N 140-820150
*
(DO NOT USE) -4
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
(DO NOT USE) -3 -DATA -2 +DATA -1
D2300CPS*
*
SUPERVISED
*OMIT THIS EQUIPMENT FOR STYLE 4 XNET
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
D2300CPS
EOLR 120 OHMS, 1/4W P/N 140-820150
SUPERVISED
REFER TO NIM-1R OR NIM-1W INSTALLATION INSTRUCTIONS P/N 315-092953 OR P/N 315-099165, AS APPLICABLE EOLR 120 OHMS, 1/4W P/N 140-820150
1
2
Figure 8 Wiring the RS-485 XNET Network in Style 4 and Style 7 (MXL)
3
TB3
4
NIM-1R/-1W MOM-4
When installing the fiber pairs, each fiber must connect between the transmit data (DATA XTMR) on one D2300CPS and the receive data line (DATA REC) on the other D2300CPS.
RS-485 NETWORK The RS-485 MNET, XNET and HNET networks connect to the D2300CPS on the terminal block with the markings +DATA (1) and -DATA(2). Terminals 3 and 4 are not used. For Style 4 networks one D2300CPS is needed at each Fiber Optic drop. For Style 7 networks two D2300CPS modules are needed at each drop.End of line devices are required on each RS-485 pair in the system. Install them at the extreme ends of each pair. Refer to Figures 7 and 8 (MXL) and Figure 9 (FireFinder XLS) for wiring instructions and ratings for both Style 4 and Style 7.
The D2300CPS fiber connection is classified as Style DCLB per ULC-527.
INDICATORS The D2300CPS has five LED indicators for Power and Status. The LEDs are located on the side of the module with the Fiber Optic connectors. The Power LED is green and lights whenever there is 24 VDC. Both channels A and B have a yellow and green LED. The green LED indicates that the D2300CPS is transmitting data on that channel. The yellow LED lights when data is received.
NOTE: Positive and negative ground fault detected when terminals shorted to earth.
FIBER CONNECTIONS The D2300CPS can function as both a repeater and an end point unit. When used as an end point, connect to the fiber connectors labeled A. Make no connection to the B connectors. In the repeater mode, use both pairs of connectors, A and B. Two Fiber Optic cables are required between each pair of D2300CPS modules. Use a high quality duplex Fiber Optic cable containing either 50/125 or 62.5/125 fiber. Duplex fiber optic cable has two cables in a single shield similar to electrical zip cord. Use ST style fiber connectors. Please contact the fiber manufacturer regarding instructions for terminating the fiber.
ELECTRICAL RATINGS Active 24VDC Module Current
57mA
Standby 24VDC Module Current
57mA
Input Power Battery Power RS-485 Transmitter Power 7
18-31 VDC, 57mA max 24 VDC, 57mA max 8V (P-P), 150mA max 20µW (-17dBm) (62.5/125 Fiber)
EOLR 120 OHMS, 1/4W P/N 140-820150
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
D2300CPS
DO NOT USE
SUPERVISED
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
1
NO EOLR REQUIRED AT THE NIC-C
2
9
3
10
4
11
5
12
6
13
7
14
8
15
16
DO NOT USE
NIC-C ONE SLOT OF CC-5/CC-2 17
18
19
20
21
22
23
24
STYLE 4 HNET/XNET DO NOT USE
EOLR 120 OHMS, 1/4W P/N 140-820150
(DO NOT USE) -4 (DO NOT USE) -3 -DATA -2 +DATA -1
D2300CPS
(DO NOT USE) -4 SUPERVISED
(DO NOT USE) -3 -DATA -2 +DATA -1
D2300CPS RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN NO EOLR REQUIRED AT THE NIC-C
DO NOT USE
DO NOT USE
SUPERVISED
1
2
9
3
10
4
11
5
12
6
13
7
14
8
15
16
DO NOT USE
NIC-C ONE SLOT OF CC-5/CC-2
STYLE 7 HNET/XNET
17
18
19
20
21
22
23
24
DO NOT USE
Figure 9 Wiring the RS-485 HNET or XNET Network in Style 4 and Style 7 (FireFinder XLS) P/N 315-050018-0
Contacting us For help installing, operating, maintaining, and troubleshooting this product, refer to this document and any other documentation provided. If you still have questions, contact us during business hours (Monday through Friday, excluding holidays, between 5 a.m. and 5 p.m. Pacific Time). Table 3. Sales and support contact information
Sales Phone:
Toll-free: 888.437.3287 in the US, including Alaska and Hawaii; Puerto Rico; Canada. Outside the toll-free area: 503.885.5700.
E-mail Fax
Technical support
[email protected] 888.329.0331
888.329.0332
Note: Be ready at the equipment before calling.
Online Another great resource for assistance with your Interlogix product is our online publication library. To access the library, go to our website at the following location: http://www.interlogix.com1
1.
Many Interlogix documents are provided as PDFs (portable document format). To read these documents, you will need Adobe Reader, which can be downloaded free from Adobe’s website at www.adobe.com.
Copyright Trademarks and patents
Manufacturer
Certification FCC compliance
ACMA compliance
Canada
European Union directives
© 2011 UTC Fire & Security. All rights reserved. Interlogix and IFS names and logos are trademarks of UTC Fire & Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products. UTC Fire & Security Americas Corporation, Inc. 2955 Red Hill Avenue, Costa Mesa, CA 92626-5923, USA Authorized EU manufacturing representative: UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert, The Netherlands N4131 Class A: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Notice! This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. 2004/108/EC (EMC directive): Hereby, UTC Fire & Security declares that this device is in compliance with the essential requirements and other relevant provisions of Directive 2004/108/EC. 2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
Contact information
For contact information, see www.interlogix.com.