Data Sheet 2 - wesco

Report 2 Downloads 78 Views
OEM LOADCENTER INTERIOR ASSEMBLIES CIRCUIT BREAKERS AND ACCESSORIES

OEM Loadcenter Interior Assemblies

OEM INTERIOR ASSEMBLIES Page 1

Type CH Index

Type BR Index page(s)

page(s)

Type CH OEM Loadcenter Interior Assemblies ....................................... 4

Type BR OEM Loadcenter Interior Assemblies ..................................... 22

Type CH Loadcenter Accessories ..................... 5

Type BR Loadcenter Accessories ................... 23

Type CH Circuit Breakers .................................. 6

Type BR Circuit Breakers ................................ 24

Plug-On .......................................................... 7

Plug-On ............................................... 25 & 30

Plug-On Special Application ................... 7-11

Plug-On Special Application ...... 26, 27, & 30

Accessories ................................................. 12

Plug-On Duplex, Quadplex .................. 28, 29

Type CH Interior Assemblies Single-Phase, Single-Row Copper Bus, 70 and 125 Amp .................... 13 Single-Phase, Double-Row Copper Bus, 125, 200 and 225 Amp ..... 14-18 Three-Phase, Double-Row Copper Bus, 125 and 225 Amp ............. 19-21 Surge Protectors ............................................. 46

Accessories ................................................. 31 Type BR Interior Assemblies Single-Phase, Single-Row Aluminum Bus, 70 and 125 Amp ......... 32, 33 Single-Phase, Double-Row Aluminum Bus, 125, 200 and 225 Amp ........................... 34-39 Single-Phase, Double-Row Copper Bus, 125 and 200 Amp ............ 40, 41 Three-Phase, Double-Row Aluminum Bus, 125, 150, 200 and 225 Amp ................... 42-44 Three-Phase, Double-Row Copper Bus, 125 and 200 Amp .................. 45 Surge Protectors ............................................. 46

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

OEM INTERIOR ASSEMBLIES Page 2

General

Quality

As a leader in the electrical distribution equipment business, CutlerHammer has a unique product offering for equipment manufacturers, panel builders and virtually any OEM that has a need for power distribution within their equipment. The OEM interior offering consists of a wide variety of power distribution options utilizing components from CutlerHammer’s CH and BR Loadcenter product lines. With high-volume, standardized products, OEMs can expect to receive high-quality products in configurations meeting virtually any power distribution need.

Built in our ISO 9002 certified manufacturing facilities, customers can be assured of the process quality in place for the manufacture of these products. Utilizing the latest in computercontrolled plating, painting, molding, stamping and welding processes, our customers have come to expect consistent high quality from shipment to shipment.

Coupled with Cutler-Hammer’s expertise in circuit breaker design and manufacturing, our OEM interiors provide solid power distribution and circuit protection in a compact, easyto-install package. Interiors are offered from 2 to 42 circuits, and from 70 to 225 amperes.

Ordering Information Cutler-Hammer OEM interiors are as easy to order as they are to install. Customers place orders by catalog number in multiples of the standard package quantities. The products are either stocked in Cutler-Hammer warehouses or are shipped directly from the plant. For those panels shipping directly from the plant, shipping lead time is 10 working days. Distributors should refer to VISTA or the Cutler-Hammer Price and Availability Digest for pricing. For interiors not shown in this catalog, contact your local Cutler-Hammer sales engineer or the Customer Support Center at 1-800-356-1243.

Two Products Offer Design Flexibility As a manufacturer of two lines of loadcenters, we are in a unique position to offer the broadest range of interiors in the market. Each line has its own unique characteristics that appeal to various segments of the market. OEM interiors are UL recognized components and are listed in either of the following UL files: E8741 or E52977. The interiors are designed for either horizontal (single-row breaker mounting), or vertical (double-row breaker mounting). To comply with National Electrical Code® (NEC) requirements if mounted horizontally, when the breaker is ON, the handle should be in the UP position. When mounted vertically, the handle toggles from left to right, so this is not a concern.

Type CH The CH interiors feature 100% copper bus and use the CH 3/4-inch wide (19.1 mm) circuit breaker, which minimizes panel space. Recognized by contractors for its sturdy design, the CH interior will appeal to those customers seeking an industrial quality bolted bus bar and the space saving of 1/4-inch (6.4 mm) per bus stab. With a typical 12 circuit CH interior, this space savings amounts to an 1-1/2 inch (38.1 mm) savings over its 1-inch (25.4 mm) counterparts. The stab rating of the CH interiors is 140 amperes maximum, meaning that the handle rating of breakers mounted across from one another may not exceed 140 amperes.

Type BR The BR interiors are manufactured of formed, plated aluminum or copper, and use the Cutler-Hammer Type BR 1-inch wide (25.4 mm) circuit breaker. This design affords customers the most circuit flexibility as many of these interiors allow the installation of standard 1- and 2-pole breakers as well as duplex (2 poles in a 1-inch space, 25.4 mm), or quadplex (4 poles in a 2-inch space, 50.8 mm) breakers. The stab rating of the BR interiors is 200 amperes maximum, meaning that the handle rating of the breakers that are mounted across from one another may not exceed 200 amperes.

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

OEM Loadcenter Interior Assemblies

OEM INTERIOR ASSEMBLIES Page 3

Specifications, Listings

Underwriters Laboratories Inc. Listing

Lighting and Appliance Panelboards

Class CTL

All grounding bars manufactured comply with Underwriters Laboratories Inc. standards and are listed under Guide No. DHJR, File E31424, Volume W, Section 17.

Lighting and appliance branch circuit panelboards are defined in NEC Article 384 as “One having more than 10% of its overcurrent devices rated 30 amperes or less for which neutral connections are provided.” Article 384 also limits the number of overcurrent devices (branch circuit poles) to a maximum of 42 in any one cabinet. When the 42 poles are exceeded, two or more separate panels are required.

NEC Paragraph 384-15 requires branch circuit panelboards to be provided with physical means to prevent the installation of more overcurrent devices than the number of which the enclosure was designed, rated and approved. Class CTL duplex, quadplex and twin breakers (identified by a catalog number prefix BD, BQ, BQC and CHT) are equipped with a UL listed rejection tab over the line terminal. All OEM interiors have appropriately notched stabs to accept these rejection tab Class CTL breakers. Duplex, quadplex and twin breakers manufactured without the rejection tab (identified by a catalog number prefix BR, BRD and CHNT) are available for replacement purposes in older interiors.

All circuit breakers 10 amperes and larger comply with the Underwriters Laboratories Inc. “Standard for Branch Circuit and Service Circuit Breakers” UL489, Guide No. 60 10.2 File E31424; and “Requirements for Wire Connectors and Soldering Lugs” UL486B, Guide No. 461 10-C File E7830. All Cutler-Hammer breakers where marked, are suitable for use with 60/75°C rated wire, unless otherwise specified. All devices comply with the 22,000 AIC – 10,000 AIC UL series connected components File DKSY2 of the Recognized Components Index.

Federal Specifications All loadcenter enclosures meet Federal Specifications W-P-115b, Type 1, and Class 2 requirements. All 120/240V breakers, both 1-inch (25.4 mm), 1/2-inch (12.7 mm) and 3/4-inch (19.1 mm) per pole meet the requirement of Federal Specifications W-C 375B/Gen Type 1.

Canadian Standards Association Listing All 1-pole and 2-pole, 120/240V breakers, both 1-inch (25.4 mm), 1/2-inch (12.7 mm) and 3/4-inch (19.1 mm) per pole, 225 ampere maximum, are listed as certified by the Canadian Standards Association, Guide No. 69-11.19, Class 1432, File 18328.

NEC For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

5 1 4 8 3

TYPE

CH ASSEMBLIES

OEM Loadcenter Interior Assemblies

Page 4

Type CH OEM Loadcenter Interior Assemblies Ampere Rating

Maximum Number 1-Inch (24.5 mm) Spaces

UL File Single Poles Reference

Main Terminal Wire Size Range (Per Phase) Cu/Al 60°C or 75°C

Standard Package Quantity

Catalog Number

Diagram Reference Number

Page

Single-Phase Single-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire 70

2

2

E8741

(1) #8–#2 AWG Cu/Al

1

CH9MB270

1

13

125

2

2

E8741

(1) 2/0–#6 AWG Cu/Al

20

CH2L125INT

2

13

14

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire 125

4

4

E8741

(1) 2/0–#14 AWG Cu/Al

20

CH4L125INT

3

125

8

8

E8741

(1) 2/0–#6 AWG Cu/Al

20

CH8L125INT

4

14

125

12

12

E8741

(1) 2/0–#6 AWG Cu/Al

20

CH12L125INT

5

15

125

16

16

E8741

(1) 2/0–#6 AWG Cu/Al

20

CH16L125INT

6

15

200

12

12

E8741

(1) 300 kcmil–#4 AWG Cu/Al

20

CH12L200INT

7

16

200

16

16

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH16L200INT

8

16

225

24

24

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH24L225INT

9

17

225

32

32

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH32L225INT

10

17

225

42

42

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH42L225INT

11

18

Three-Phase Double-Row Breaker Mounting – Copper Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta 125

12

12

E8741

(1) 2/0–#6 AWG Cu/Al

10

CH12L3125INT

12

19

125

18

18

E8741

(1) 2/0–#6 AWG Cu/Al

10

CH18L3125INT

13

19

125

24

24

E8741

(1) 2/0–#6 AWG Cu/Al

10

CH24L3125INT

14

20

225

24

24

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH24L3225INT

15

20

225

30

30

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH30L3225INT

16

21

225

42

42

E8741

(1) 300 kcmil–#4 AWG Cu/Al

10

CH42L3225INT

17

21

Catalog Numbering System

CH 4 L 3 125 INT Breaker Type Maximum Single Poles Main Lug

OEM Interior Ampere Rating Single-Phase: Blank / Three-Phase: 3

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

Loadcenter Accessories

CH ASSEMBLIES Page 5

Neutral Assemblies Ampere Rating

UL File Reference

Main Incoming Terminal Wire Size Range 60°C or 75°C

125

E52977

#6–1/0 AWG Cu #6–2/0 AWG Al

125

E52977

125

Number of Terminals #6–1/0 AWG Cu #6–2/0 AWG Al

Standard Package Quantity

10



20

10NEU125B

1

5.938 (150.83)

5.400 (137.16)

#6–1/0 AWG Cu #6–2/0 AWG Al

17



20

17NEU125B

1

8.388 (213.06)

7.850 (199.40)

E52977

#6–1/0 AWG Cu #6–2/0 AWG Al

20



20

20NEU125B

1

9.438 (239.73)

8.900 (226.06)

225

E52977

#1–300 kcmil Cu/Al

24

1

20

24NEU225B

2

10.913 (277.19) 10.300 (261.62)

225

E52977

#1–300 kcmil Cu/Al

35

1

20

35NEU225B

2

15.813 (401.65) 15.200 (386.08)

125





4

2

1

BINA

3

2.266 (57.56)

#14–4 AWG Cu/Al

Figure 1

Catalog Number

Dimensions – Inches (mm) Figure Overall Length A

Mounting B

0.594 (15.09)

Figure 2 A

.269 (6.83)

A .344 (8.74)

B

.844 (21.44)

.269 (6.83)

B

.844 (21.44)

1.750 (44.45)

CL of Mounting Hole

CL of Mounting Hole

2.360 (59.94) 2.860 (72.64)

2.360 (59.94)

Figure 3 .120 (3.05)

A

.250 (6.35)

CL of Mounting Hole

1.182 (30.02) .750 (19.05)

.688 (17.47)

CL of Mounting Hole

.182 Diameter (4.62)

.156 (3.96)

1.750 (44.45)

1.187 (30.15)

B

.344 (8.74)

2.000 (50.80)

Add-on Lugs for Neutral Assemblies Description

Wire Size Range Cu/Al 60°C or 75°C

Ordering Quantity 1

Catalog Number

Neutral/Ground Lug Add-On Neutral or Ground Lug

#2/0 Maximum 1 #3/0 Maximum 1 300 kcmil Maximum 1

NL20 NL30 NL300

Length Inches (mm)

Ordering Quantity 1

Catalog Number

2.54 (64.5) 3.59 (91.2) 4.29 (109.0) 5.34 (135.6) 4.61 (117.1) 5.69 (144.5) 6.74 (171.2) 8.14 (206.8) 9.19 (233.4) 5.78 (146.8)

1 1 1 1 1 1 1 1 1 1

GBK5 2 GBK520 2 GBK10 2 GBK1020 2 GBK13 2 GBK14 2 GBK1420 2 GBK21 2 GBK2120 2 BRGBK39512 34

GBK14

Ground Bar Kits

f d f f f k f d f k f f f

dssssds dssssdsj dssssdssssss dssssdssssssj dssssdssssssssss dssssdssssssssssj dssssdsssssssssssssssss dssssdsssssssssssssssssj ofodofooofodofooofo 1 2 3 4

Must be purchased in multiples of ordering quantities indicated. Distance between mounting holes is 1-3/4 inches (44.5 mm). For 1- and 3-phase 400 and 600 ampere applications. Distance between mounting holes is 2-11/32 inches (59.5 mm).

BRGBK39512

Ground Bar Legend s (3) #14 – #10 Cu/Al or (1) #14 – #4 Cu/Al j (1) #6 – 2/0 Cu/Al o (1) #14 – #6 Cu/Al or (2) #14 – #12 Cu/Al (1) 1/0 – 14 or (3) #10 – 12 Cu/Al (1) #14 – 1/0 Cu/Al or (3) #14 – #10 Cu/Al f (1) #6 – 14 Cu/Al or (2) #1/0 – 14 Cu/Al d Mounting Hole

fk

Description (See Legend)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH CIRCUIT BREAKERS

Page 6

CH Circuit Breakers

Special Application Breakers

CH-HM Breakers

Cutler-Hammer Type CH plug-on breakers are a 3/4-inch (19.1 mm) design with a UL listed 10 kA interrupting rating. CH breakers can be used as main or branch disconnect devices. Several ratings are SWD and HACR approved. Typical ampacity range for CH breakers is 15 to 150 amperes.

As the name implies, these devices are designed for special applications as required by the National Electrical Code.

CH-HM breakers are designed with high magnetic trip settings. Singleand 2-pole CH-HM breakers (“HM” suffix) rated 15 and 20 amperes are recommended for circuits with inherently high inrush currents.

CH-GF People Protection Breakers Cutler-Hammer Type CH-GF (ground fault circuit breakers) combine stateof-the-art electronic technology with a circuit breaker mechanism in a compact 3/4-inch (19.1 mm) package. The CH-GF automatically senses hot wire-to-ground faults in a 4 to 6 mA range and disconnects the power, thus providing an extra margin of safety beyond that of conventional circuit breakers. CH-GF applications include bathrooms, cellar outlets, swimming pools, outdoor branch circuits and kitchen branch circuits. Available in UL listed 120 and 120/240V ratings. CutlerHammer also offers non-UL listed ground fault breakers for international applications as well as ground fault devices for equipment protection.

CH-EPD Equipment Protection Breakers The Cutler-Hammer Type CH-EPD device is similar to the CH-GP except that it is designed to protect equipment (not people) against damage from arcing ground faults. It is available with a 30 mA trip level. Applications include infrared heating equipment, process control equipment, etc.

Neutral Switching Breaker Primary application for the CutlerHammer switching neutral breaker is for protection of process equipment such as gas pumps that utilize flammable liquids. Non-automatic pole breaks the neutral power leg, minimizing the danger of arc conditions.

2-Pole Breakers 120V or More to Ground Used on Delta distribution systems, these Type CH breakers are applied on phase legs where voltage-to-ground is above 120V.

Arc Fault Circuit Interrupters (AFCIs) Reduce the risk of fire by detecting and interrupting electrical arcing faults which standard thermal magnetic breakers cannot. For more information, see page 9.

Calibrated one-piece bimetal for reliable thermal protection.

Heavy-duty over-center toggle spring to ensure a quick and reliable “make-break” action.

Unique two-position trip. Helps to eliminate nuisance callbacks, breaker trips to “OFF,” homeowner simply turns to “ON,” no reset required.

CH-M50 Breakers CH-M50 breakers are designed to operate at a maximum temperature of 50°C. Single- and 2-pole CH-M50 breakers (“M50” suffix) rated 15 to 50 amperes are recommended for applications where the ambient temperatures are above 40°C.

CHP Breakers CHP breakers are designed with a three-position commercial trip (ontripped-off). Single-, 2- and 3-pole CHP breakers rated 10 to 70 amperes are recommended for applications requiring a breaker center trip position.

Magnetic armature – assists in the instantaneous tripping for short circuit protection.

All internal metal components are plated to provide a 100% noncorrosive circuit breaker. Magnetic armature placement spring ensures consistent low instantaneous trip on 15 and 30 ampere breakers.

Plated steel latch lever provides load force for quick and reliable tripping during a thermal or magnetic trip condition.

Calibration screw (under UL label) provides for accurate and predictable protection every time. Factory calibrated. Heavy duty tin-plated copper box lugs for load termination. Rated for two 60/75 °C wire conductors.

Latch spring provides consistent relatching operation of the breaker trip mechanism.

Large gas port allowing short circuit gases to safely exit the circuit breaker.

Tin-plated copper contact stabs for good conductivity and quick installations. Contact clip spring for solid bus stab connection. Eliminates expansion during environmental changes. Large silver tungsten contacts for good contact wear and conductivity.

Zinc-plated magnetic pole piece – works with magnetic armature to provide instantaneous tripping for short circuit protection.

CH Breaker Section View

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Glass polyester base and cover for superior construction and durability. One-piece molded base allows for repeatable quality every time.

Plug-On Circuit Breakers Special Application Plug-On Circuit Breakers

TYPE

CH CIRCUIT BREAKERS Page 7

Plug-On Circuit Breakers, Type CH 10,000 Amperes Interrupting Capacity 120, 120/240 or 240V AC

Plug-on Circuit Breakers 1 2 3 4 5 6 7 8 9

For 1- and 2-pole breakers. Solid and stranded wire can be used together. For 3-pole breakers. Switching duty rated. HACR rated. 1-pole 60 – 70 amperes, 2-pole 80 – 125 amperes, 3-pole 40 – 100 amperes. 1-pole 40 – 50 amperes, 2-pole 40 – 70 amperes. 2-pole 150 amperes. CH2150 requires 4-pole spaces and is not suitable for use on 3-phase panels, not CSA certified.

Type CH Breakers, 3/4-inch (19.1 mm) per Pole 120, 120/240 or 240V AC, 10,000 AIC Ampere Rating

Wire Size Range Cu/Al 60ºC or 75°C

1-Pole 120/240V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

3-Pole 240V AC Common Trip Requires Three 3/4-inch (19.1 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

Catalog Number

10 15 20 25 30

(1) #14 – 8 1 (2) #14 – 10 12 (1) #14 – 6 3

CH110 CH115 45 CH120 45 CH125 5 CH130 5

CH210 CH215 5 CH220 5 CH225 5 CH230 5

CH310 CH315 5 CH320 5 CH325 5 CH330 5

35

#14 – 2 1 #14 – 6 3

CH135 5

CH235 5

CH335

#10 – 1/0 6 #14 – 2 7 #3/0 8

CH140 5 CH145 5 CH150 5 CH160 5 CH170 — — — — — —

CH240 5 CH245 5 CH250 5 CH260 5 CH270 CH280 CH290 CH2100 CH2110 CH2125 CH2150 9

CH340 5 CH345 5 CH350 5 CH360 5 CH370 CH3080 CH3090 CH3100 — — —

40 45 50 60 70 80 90 100 110 125 150

CH Neutral Switching Breakers — 10,000 Amperes Interrupting Capacity — 120 or 120/240V AC Type CH Neutral Switching Breakers, 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Used to open the neutral along power line(s) for applications of gas pumps. Ampere Rating

15 20 30 40 50 1 2

Wire Size Range Cu/Al 60ºC or 75°C

#14 – 8

2-Pole 120V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

(Hot leg) Neutral Out Neutral In

3-Pole 120/240V AC Common Trip Requires Three 3/4-inch (19.1 mm) Spaces

1 per Individual Carton

1 per Individual Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

CH215SW CH220SW CH230SW CH240SW CH250SW

1 1 1 1 1

Phase Phase Neutral Out Neutral In

CH315SW 2 CH320SW 2 CH330SW 2 CH340SW 2 CH350SW 2

For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space. Switching duty rated.

CH-HID Circuit Breakers — 10,000 Amperes Interrupting Capacity — 120, 120/240 or 240V AC Type CH-HID Circuit Breakers, 3/4-inch (19.1 mm) per Pole 120, 120/240 or 240V AC, 10,000 AIC Suitable for use in circuits for fluorescent and High Intensity Discharge lighting. Also suitable for HACR applications. Ampere Rating

15 20 30 1

Wire Size Range Cu/Al 60ºC or 75°C

#14 – 8

1-Pole 120/240V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

3-Pole 240V AC Common Trip Requires Three 3/4-inch (19.1 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

CH115HID CH120HID CH130HID

CH215HID CH220HID CH230HID

1

Catalog Number CH315HID CH320HID CH330HID

CH215HID is rated for 120/240V.

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH CIRCUIT BREAKERS

Special Application Plug-On Circuit Breakers

Page 8

Plug-On Ground Fault Circuit Breakers, Type CH 10,000 Amperes Interrupting Capacity 120 or 120/240V AC

Type CH Ground Fault Circuit Breakers (5 Milliampere) 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Ampere Rating

15 20 25 30 35 40 45 50 60 1

Type CH 1-Pole

Type CH 2-Pole

Ground Fault Application Notes Single-pole Type CHGFIs are designed for use in 2-wire, 120V AC circuits. Figure 4 shows a typical wiring configuration. Two-pole Type CHGFIs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multiwire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a 120/240V AC source. Figure 5 and Figure 6 illustrate typical wiring configurations for 120/240V AC multiwire circuits. Figure 7 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit. The figures are shown with a 120/240V AC, single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures the electrical operation of the Type CHGFI is not affected by the equipment ground.

Wire Size Range Cu/Al 60ºC or 75°C AWG

#14 –

61

1-Pole 120V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

1 per Shelf Carton

1 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

CH115GF CH120GF CH125GF CH130GF — — — — —

CH215GF CH220GF CH225GF CH230GF CH235GF CH240GF CH245GF CH250GF CH260GF

60 ampere breaker listed for 75°C Cu wire only.

Type CH Ground Fault Equipment Protection Circuit Breakers (30 Milliampere) 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Ampere Rating

15 20 25 30 40 50 60 1

Wire Size Range Cu/Al 60ºC or 75°C AWG

#14 – 6 1

1-Pole 120V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

1 per Shelf Carton

1 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

CH115EPD CH120EPD CH125EPD CH130EPD — — —

CH215EPD CH220EPD — CH230EPD CH240EPD CH250EPD CH260EPD

60 ampere breaker listed for 75°C Cu wire only.

Figure 4. 1-Pole

Figure 6. 2-Pole

Figure 5. 2-Pole

Figure 7. 2-Pole

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

Special Application Plug-On Circuit Breakers

CH CIRCUIT BREAKERS Page 9

Plug-On Arc Fault Circuit Breakers, Type CH 10,000 Amperes Interrupting Capacity 120 or 120/240V AC

Type CH FIRE-GUARD™ AFCI Circuit Breakers 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Poles

Ampere Rating

Configuration

Catalog Number

Wire Size Range Cu/Al 60ºC or 75ºC AWG

1-Pole 10 kAIC

15

AFCI AFCI with GFCI

CH115AF CH115AFGF

#14 – 6

20

AFCI AFCI with GFCI

CH120AF CH120AFGF

#14 – 6

15

AFCI Common Trip AFCI Independent Trip AFCI Common Trip with GFCI

CH215AF CH215AFIT CH215AFGF

#14 – 6

20

AFCI Common Trip AFCI Independent Trip AFCI Common Trip with GFCI

CH220AF CH220AFIT CH220AFGF

#14 – 6

2-Pole 10 kAIC 12

1

Type CH 1- and 2-Pole AFCI Circuit Breakers

2

Common trip refers to 2-pole 240V load application sourced by 120/240V AC (see Figure 10). Independent trip refers to 2-pole shared neutral circuits (see Figure 9 and Figure 11). 120/240V AC Source N A B

120/240V AC Source N A B

Line B

Line B

2 Pole

1 Pole

Line A

Neutral 120V Duplex Receptacle

Neutral

Neutral Equipment Ground

Equipment Ground

Figure 8. 1-Pole Single 120V Load Application Sourced by 120/240V AC 120/240V AC Source N A B

240V Duplex Receptacle

Figure 10. 2-Pole 240V Load Application Sourced by 120/240V AC 120/240V AC Source N A B

Line B

Line B Line A

2 Pole Neutral Neutral

2 Pole

2-120V Duplex Receptacles

Neutral

Line A

Neutral 120V Duplex Receptacle (With Line Side Jumper Removed) Equipment Ground

Equipment Ground

Figure 9. 1-Pole Shared Neutral with Multi-Duplex Receptacle Application

Figure 11. 2-Pole Shared Neutral with Duplex Receptacle Application

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH CIRCUIT BREAKERS

Special Application Plug-On Circuit Breakers

Page 10

CHP Commercial Breakers — 10,000 Amperes Interrupting Capacity 120, 120/240 or 240V AC Note: CHP Breakers feature on-off and trip positions for commercial applications

Type CHP Breakers, 3/4-inch (19.1 mm) per Pole 120, 120/240 or 240V AC, 10,000 AIC Note: CHP Breakers offer on-off and trip positions for commercial applications Ampere Rating

2 3 4 5 6 7

81 10 12 63

1-Pole 120/240V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

3-Pole 240V AC Common Trip Requires Three 3/4-inch (19.1 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

Catalog Number

CHP110 CHP115 45 CHP120 45 CHP125 5 CHP130 5

CHP210 CHP215 5 CHP220 5 CHP225 5 CHP230 5

CHP310 CHP315 5 CHP320 5 CHP325 5 CHP330 5

10 15 20 25 30

(1) #14 – (2) #14 – (1) #14 –

35

#14 – 2 1 #14 – 6 3

CHP135 5

CHP235 5

CHP335 5

#10 – 1/0 6 #14 – 2 7

CHP140 5 CHP145 5 CHP150 5 CHP160 5 CHP170 — — — — —

CHP240 5 CHP245 5 CHP250 5 CHP260 5 CHP270 CHP280 CHP290 CHP2100 CHP2110 CHP2125

CHP340 5 CHP345 5 CHP350 5 CHP360 5 CHP370 — — CHP3100 — —

40 45 50 60 70 80 90 100 110 125 1

Wire Size Range Cu/Al 60ºC or 75°C AWG

For 1- and 2-pole breakers. Solid and stranded wire can be used together. For 3-pole breakers. Switching duty rated. HACR rated. 1-pole 60 – 70 amperes, 2-pole 80 – 125 amperes, 3-pole 40 – 100 amperes. 1-pole 40 – 50 amperes, 2-pole 40 – 70 amperes.

CHP-GFCI Circuit Breakers — 10,000 Amperes Interrupting Capacity 120 or 120/240V AC Note: CHP Breakers offer on-off and trip positions for commercial applications.

Type CHP-GFCI Breakers — 5 Milliampere — 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Note: CHP Breakers offer on-off and trip positions for commercial applications. Ampere Rating

Wire Size Range Cu/Al 60ºC or 75°C AWG

1-Pole 120V AC Requires One 3/4-inch (19.1 mm) Space

Ground Fault Application Notes Single-pole Type CHP-GFI breakers are designed for use in 2-wire, 120V AC circuits. Figure 12 shows a typical wiring configuration. The figure is shown with a 120/240V AC, single-phase, 3-wire power source, but a 120/208V AC, 3-phase, 4-wire power supply is also applicable. Electrical operation of the Type CHPGFI is not affected by the equipment ground.

1 per Individual Carton 10,000 AIC Catalog Number 15 20 30

#14 – 6 #14 – 6 #14 – 6

CHP115GF CHP120GF CHP130GF

Figure 12. Typical 1-Pole Wiring Diagram

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Special Application Plug-On Circuit Breakers

TYPE

CH CIRCUIT BREAKERS Page 11

CHP Neutral Switching Breakers 10,000 Amperes Interrupting Capacity 120 or 120/240V AC Type CHP Neutral Switching Breakers, 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Used to open the neutral along power line(s) for applications of gas pumps. Ampere Rating

15 20 1

Wire Size Range Cu/Al 60ºC or 75°C AWG

#14 – 8

2-Pole 120V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

(Hot leg) Neutral Out Neutral In

3-Pole 120/240V AC Common Trip Requires Three 3/4-inch (19.1 mm) Spaces

1 per Shelf Carton

1 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

CHP215SW 1 CHP220SW 1

CHP315SW 1 CHP320SW 1

Phase Phase Neutral Out Neutral In

For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space.

CH-M50 High Ambient Breaker Type CH-M50 High Ambient Breakers 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Ampere Rating

15 20 25 30 35 40 45 50 60 70

Wire Size Range Cu/Al 60ºC or 75°C AWG

(1) #14 – 8 (2) #14 – 10

1-Pole 120/240V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

CH115M50 CH120M50 CH125M50 CH130M50 CH135M50 CH140M50 CH145M50 CH150M50 — —

CH215M50 CH220M50 CH225M50 CH230M50 CH235M50 CH240M50 CH245M50 CH250M50 CH260M50 CH270M50

CH-HM and CHP-HM High Magnetic Breakers Type CH-HM and CHP-HM High Magnetic Breakers 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC Ampere Rating

Wire Size Range Cu/Al 60ºC or 75°C AWG

1-Pole 120/240V AC Requires One 3/4-inch (19.1 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 3/4-inch (19.1 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

15 20

(1) #14 – 8 (2) #14 – 10

CH115HM CH120HM

CH215HM CH220HM

15 20

(1) #14 – 8 (2) #14 – 10

CHP115HM CHP120HM

CHP215HM CHP220HM

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH CIRCUIT BREAKERS

Accessories

Page 12

Circuit Breaker Accessories Description

Ordering Quantity 1

Handle Ties 2 Handle tie bar for physically joining the handles of two adjacent 1-pole Type CH Circuit Breakers. (Molded Plastic Handle Cover) Handle Lockoffs 34 Padlockable device for locking the handle of 1-, 2-, or 3-pole Type CH Circuit Breakers (Escutcheon Mounted) 5 Padlockable device for locking the handle of a 1-, 2- or 3-pole Type CHGFI Circuit Breaker. (Escutcheon Mounted) 5

Catalog Number

CHHT 25

CHHT

1

CHPL

1

CHPLGF

CHPL

46

Handle Lockdogs Device used to secure handle in “On” or “Off” position for 1-pole Type CH Circuit Breakers. (Handle Mounted) 7

10

CHLO

Hold-Down Kits 8 Hold-down retainer kit for 1-, 2-, 3-pole Type CH Circuit Breakers. For 6 – 24 circuit 125 ampere single- and 3-phase, 12 – 42 circuit singlephase 225 ampere and 24 – 42 circuit 3-phase 225 ampere MLO Type CH Loadcenters.

1

CH125RB

Hold-Down Kits 8 Hold-down retainer kit for 1-, 2-, 3-pole Type CH Circuit Breakers for 2 through 4 circuit MLO CH Loadcenters.

1

CH125RB24

Mechanical Interlock Type CH for 2-, 3- and 4-pole Breakers Shunt Trip for CH 120V AC

CHPLGF

10

CHML

1

ST 9

CHLO CH125RB

Main and Sub-Feed Lug Blocks Number of Poles

Ampere Rating

Number of 3/4-inch (19.1 mm) Spaces Needed

Wire Size Range Cu/Al 60ºC or 75ºC AWG

2 3

125 125

2 3

#1/0 #1/0

1 2 3 4 5 6 7 8 9

Ordering Quantity

Catalog Number

CHML 1 1

CHSF2125 CHSF3125

Must be purchased in multiples of ordering quantities indicated. Handle Ties: Typically used to join two similar independent single-pole breakers to form a 2-pole noncommon trip breaker. Handle Lockoffs: Devices that use a padlock to lock the circuit breaker’s handle in the “On” or “Off” position. Requires one additional pole space. Escutcheon Mounted: Device mounted semipermanently to the face of the circuit breaker and secured by the loadcenter deadfront. Handle Lockdogs: Devices that are used to secure a circuit breaker’s handle in the “On” or “Off” position. Handle Lockdogs are not padlockable devices. Handle Mounted: Device mounted above or below handle using spring pressure. Hold-Down Kits: Devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(g). Add suffix indicated to end of breaker catalog number.

CHSF2125

CHSF3125

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Single-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

TYPE

CH ASSEMBLIES Page 13

70 2 AMP

SPACES

2

SINGLE POLES

DIAGRAM 1 1.500 (38.10)

0.500 (12.70)

0.200 ± 0.005 Diameter (5.08 ± 0.13) 1.410 (35.81) 3.850 (97.79) 2.190 (55.63)

1.680 (42.67)

0.200 ± 0.005 Diameter (5.08 ± 0.13)

0.685 (17.40) 3.087 (78.41)

.188 (4.78) 0.750 (19.05)

3.805 (96.65) Maximum

#8 - #2 AWG (Al/Cu)

Handle Height

0.937 (23.80)

CH9MB270

125 2 AMP

SPACES

2

SINGLE POLES

DIAGRAM 2 .297 (7.54)

#10 Mounting Screws

.156 (3.96)

.625 (15.88)

4.588 2.844 2.250 (116.54) (72.24) (57.15)

.156 Diameter Nib

1.812 (46.02)

2.000 (50.80) 3.563 (90.50)

.031 x 45° Chamfer 1 Nib Required

.598 (15.19)

.188 (4.78) 3.000 (76.2) 3.700 (93.98) Maximum

1.063 (26.99)

2.688 (68.28)

Wire Range: (1) 2/0 - 14 AWG (Al/Cu)

Handle Height

.183 (4.65) 1.782 (45.26)

CH2L125INT

Legend Dimensions – Inches (mm)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

Page 14

125 4 AMP

SPACES

4

SINGLE POLES

DIAGRAM 3

125 8 AMP

2.041 (51.84)

1.625 (41.28)

.031 x 45° Chamfer 1 Nib Required

3.125 (79.38)

.183 (4.65)

SINGLE POLES

1.439 (36.55)

Wire Range: (1) 4/0 - #6 AWG (Al/Cu) Torque Wire Screws*

3.961 (100.61)

3.311 (84.10)

Maximum Handle Height

4.666 (118.52)

3.324 (84.43)

Maximum Handle Height

1.52 (38.61)

.188 (4.78)

.188 (4.78) Wire Range: (1) 2/0 - 14 AWG (Al/Cu)

6.332 (160.83)

2.000 (50.80)

6.00 (152.40)

.169 Diameter (4.29)

2.688 (67.28)

5.56 (141.22)

.203 Diameter (5.16)

3.125 (79.38)

.250 (6.35)

#10 Mounting Screws

1.182 (30.02) 3.563 (90.50)

8

DIAGRAM 4 .156 Diameter Nib

.781 (19.84)

SPACES

2.172 (55.17) CL breaker

2.250 (57.15)

1.063 (26.99)

2.844 (72.24)

.750 (19.05) 5.00 (127.00)

.780 (19.81) .203 Diameter (5.16)

3.125 (79.38)

.780 (19.81) .169 Diameter (4.29)

CH8L125INT

CH4L125INT

Legend Dimensions – Inches (mm)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

TYPE

CH ASSEMBLIES Page 15

125 12 AMP

SPACES

12

SINGLE POLES

DIAGRAM 5

AMP

1.439 (36.55)

Wire Range: 2/0 - #6 AWG (Al/Cu) Torque Wire Screws*

3.961 (100.61)

3.256 (82.70)

1.610 (40.90)

Maximum Handle Height

1.439 (36.55)

SINGLE POLES

Wire Range: 2/0 - #6 AWG (Al/Cu) Torque Wire Screws*

3.324 (84.43)

.188 (4.78)

1.610 (40.90)

.188 (4.78)

6.249 (158.72) 3.125 (79.38)

6.249 (158.72)

.218 Diameter (5.54)

.310 (7.87)

2.172 (55.17)

3.125 (79.38)

.218 Diameter (5.54)

2.172 (55.17)

CL breaker

7.750 (196.85)

16

3.961 (100.61)

3.324 (84.43)

.310 (7.87)

SPACES

DIAGRAM 6 3.125 (79.38)

Maximum Handle Height

125 16

CL breaker

.750 (19.05)

.750 (19.05)

9.250 (234.95)

7.000 (177.80)

8.400 (213.36)

.218 (5.54)

.218 (5.54)

CH12L125INT CH16L125INT

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

Page 16

200 12 AMP

SPACES

12

SINGLE POLES

DIAGRAM 7

AMP

1.451 (36.86)

3.124 (79.35)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

3.961 (100.61)

16

SINGLE POLES

1.451 (36.86)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

3.961 (100.61)

3.324 (84.43)

2.010 (51.05)

Maximum Handle Height

3.324 (84.43)

.188 (4.78)

2.010 (51.05)

.188 (4.78)

6.249 (158.72) .310 (7.87)

SPACES

DIAGRAM 8 3.124 (79.35)

Maximum Handle Height

200 16

3.125 (79.38)

6.249 (158.72)

.218 Diameter (5.54)

.310 (7.87)

2.797 (71.04)

3.125 (79.38)

.218 Diameter (5.54)

2.797 (71.04)

CL breaker

CL breaker

.750 (19.05)

.750 (19.05)

13.625 (346.08)

13.625 (346.08)

12.875 (327.03)

12.875 (327.03)

.218 (5.54)

.218 (5.54)

CH12L200INT

CH16L200INT

Legend Dimensions – Inches (mm)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

TYPE

CH ASSEMBLIES Page 17

225 24 AMP

SPACES

24

SINGLE POLES

DIAGRAM 9

AMP

1.451 (36.86)

3.124 (79.35)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

32

SINGLE POLES

1.451 (36.86)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

3.961 (100.61)

3.961 (100.61) 3.324 (84.43)

2.010 (51.05)

Maximum Handle Height

3.324 (84.43)

2.010 (51.05)

.188 (4.78)

.188 (4.78)

6.249 (158.72)

6.249 (158.72) .310 (7.87)

SPACES

DIAGRAM 10 3.124 (79.35)

Maximum Handle Height

225 32

3.125 (79.38)

.218 Diameter (5.54)

.310 (7.87)

3.125 (79.38)

.218 Diameter (5.54)

2.797 (71.04)

2.797 (71.04)

CL breaker

CL breaker

.750 (19.05)

.750 (19.05)

13.625 (346.08)

12.875 (327.03)

15.875 (403.23)

15.025 (381.64)

.218 (5.54)

CH24L225INT

.218 (5.54)

CH32L225INT

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

Page 18

225 42 AMP

SPACES

42

SINGLE POLES

DIAGRAM 11 3.125 (79.38)

1.451 (36.86)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

3.961 (100.61) Maximum Handle Height

3.324 (84.43)

2.010 (51.05)

.188 (4.78)

6.249 (158.72) .310 (7.87)

3.125 (79.38)

.218 Diameter (5.54)

2.797 (71.04) CL breaker

.750 (19.05)

19.625 (498.48)

18.875 (479.43)

.218 (5.54)

CH42L225INT

Legend Dimensions – Inches (mm)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Three-Phase Double-Row Breaker Mounting – Copper Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

TYPE

CH ASSEMBLIES Page 19

125 12 AMP

SPACES

12

SINGLE POLES

DIAGRAM 12

AMP

1.440 (36.58)

1.440 (36.58)

1.685 (42.80)

Wire Range: 2/0 - #6 AWG (Al/Cu) Torque Wire Screws*

3.324 (84.43)

1.610 (40.90)

Maximum Handle Height

1.440 (36.58)

1.440 (36.58)

SINGLE POLES

Wire Range: 2/0 - #6 AWG (Al/Cu) Torque Wire Screws*

3.324 (84.43)

1.610 (40.90)

.188 (4.78)

.188 (4.78)

6.249 (158.72)

6.249 (158.72) 3.125 (79.38)

.218 Diameter (5.54)

.310 (7.87)

3.125 (79.38)

.218 Diameter (5.54)

2.172 (55.17)

2.172 (55.17)

CL breaker

CL breaker

7.750 (196.85)

18

3.961 (100.61)

3.961 (100.61)

.310 (7.87)

SPACES

DIAGRAM 13

1.685 (42.80)

Maximum Handle Height

125 18

.750 (19.05)

.750 (19.05)

7.000 (177.80) 10.750 (273.05)

.218 (5.54)

10.000 (254.00)

CH12L3125INT .218 (5.54)

CH18L3125INT

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

CH ASSEMBLIES

Three-Phase Double-Row Breaker Mounting – Copper Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

Page 20

125 24 AMP

SPACES

24

SINGLE POLES

DIAGRAM 14

AMP

1.440 (36.58)

1.440 (36.58)

Wire Range: 2/0 - #6 AWG (Al/Cu) Torque Wire Screws*

3.961 (100.61)

24

SINGLE POLES

1.674 (42.52)

1.451 (36.86)

1.451 (36.86)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

3.961 (100.61)

3.324 (84.43)

1.610 (40.90)

Maximum Handle Height

3.324 (84.43)

.188 (4.78)

2.010 (51.05)

.188 (4.78)

6.249 (158.72) .310 (7.87)

SPACES

DIAGRAM 15

1.685 (42.80)

Maximum Handle Height

225 24

3.125 (79.38)

6.249 (158.72)

.218 Diameter (5.54)

.310 (7.87)

2.172 (55.17)

3.125 (79.38)

.218 Diameter (5.54)

2.797 (71.04)

CL breaker

CL breaker

.750 (19.05)

.750 (19.05)

12.250 (311.15) 13.625 (346.08)

11.500 (292.10)

12.875 (327.03)

.218 (5.54)

.218 (5.54)

CH24L3125INT CH24L3225INT

Legend Dimensions – Inches (mm)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Three-Phase Double-Row Breaker Mounting – Copper Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

TYPE

CH ASSEMBLIES Page 21

225 30 AMP

SPACES

30

SINGLE POLES

DIAGRAM 16

AMP

1.438 (36.53)

1.438 (36.53)

1.674 (42.52)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

42

SINGLE POLES

1.451 (36.86)

1.451 (36.86)

Wire Range: (1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

3.961 (100.61)

3.961 (100.61)

Maximum Handle Height

3.324 (84.43)

3.324 (84.43)

2.010 (51.05)

2.010 (51.05)

.188 (4.78)

.188 (4.78)

6.249 (158.72)

6.249 (158.72) .310 (7.87)

SPACES

DIAGRAM 17

1.687 (42.85)

Maximum Handle Height

225 42

3.125 (79.38)

.218 Diameter (5.54)

.310 (7.87)

3.125 (79.38)

.218 Diameter (5.54)

2.797 (71.04)

2.797 (71.04)

CL of breaker

CL breaker

.750 (19.05)

.750 (19.05)

15.875 (403.23)

15.025 (381.64)

19.625 (498.48)

.218 (5.54) 18.875 (479.43)

CH30L3225INT .218 (5.54)

CH42L3225INT

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

OEM Loadcenter Interior Assemblies

Page 22

Type BR Loadcenter Interior Assemblies Ampere Rating

Maximum Number 1-Inch (24.5 mm) Spaces

UL File Single Poles Reference

Main Terminal Wire Size Range (Per Phase) Cu/Al 60°C or 75°C

Standard Package Quantity

Catalog Number

Diagram Reference Number

Page

Single-Phase Single-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire 70

2

4

E8741

(1) #8–#2 AWG Cu/Al

20

24INT70B

18

32

125

2

4

E8741

(1) 1/0–#14 AWG Cu 2/0–12 AWG Al

20

24INT125B

19

32

125

6

12

E52977

(1) 2/0–#14 AWG Cu/Al

20

612INT125SRB

20

33

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire 125

4

8

E8741

(1) 2/0–#14 AWG Cu/Al

20

48INT125B

21

34

125

6

12

E8741

(1) 2/0–#14 AWG Cu/Al

20

612INT125B

22

34

125

8

16

E8741

(1) 2/0–#14 AWG Cu/Al

20

816INT125B

23

35

125

12

12

E52977

(1) 2/0–#14 AWG Cu/Al

20

1212INT125B

24

35

125

12

24

E52977

(1) 2/0–#14 AWG Cu/Al

20

1224INT125B

25

36

125

16

24

E52977

(1) 2/0–#14 AWG Cu/Al

20

1624INT125B

26

36

125

20

24

E52977

(1) 2/0–#14 AWG Cu/Al

10

2024INT125B

27

37

125

24

24

E52977

(1) 2/0–#14 AWG Cu/Al

10

2424INT125B

28

37

200

8

16

E52977

(1) 300 kcmil –#1 AWG Cu/Al

20

816INT200B

29

38

200

12

24

E52977

(1) 300 kcmil –#1 AWG Cu/Al

20

1224INT200B

30

38

200

30

40

E52977

(1) 300 kcmil –#1 AWG Cu/Al

10

3040INT200B

31

39

225

42

42

E52977

(1) 300 kcmil –#1 AWG Cu/Al

10

4242INT225B

32

39

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire 125

8

16

E52977

(1) 2/0–#14 AWG Cu/Al

20

816INT125BC

33

40

125

12

12

E52977

(1) 2/0–#14 AWG Cu/Al

20

1212INT125BC

34

40

200

12

24

E52977

(1) 300 kcmil –#1 AWG Cu/Al

20

1224INT200BC

35

41

Three-Phase Double-Row Breaker Mounting – Aluminum Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta 125

12

24

E52977

(1) 2/0–#8 AWG Cu/Al

10

1224INT3125B

36

42

150

18

36

E52977

(1) 300 kcmil–#2 AWG Cu/Al

10

1836INT3150B

37

42

150

24

42

E52977

(1) 300 kcmil–#2 AWG Cu/Al

10

2442INT3150B

38

43

200

30

42

E52977

(1) 300 kcmil–#2 AWG Cu/Al

10

3042INT3200B

39

43

225

42

42

E52977

(1) 300 kcmil–#2 AWG Cu/Al

10

4242INT3225B

40

44

Three-Phase Double-Row Breaker Mounting – Copper Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta 125

12

24

E52977

(1) 2/0–#8 AWG Cu/Al

10

1224INT3125BC

41

45

200

12

24

E52977

(1) 300 kcmil–#2 AWG Cu/Al

10

1224INT3200BC

42

45

Catalog Numbering System

12 24 INT 3 125 B Maximum Spaces Maximum Single Poles Interior

Bulk Pack / C Indicates Copper Bus Ampere Rating Single-Phase: Blank / Three-Phase: 3

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

Loadcenter Accessories

BR ASSEMBLIES Page 23

Neutral Assemblies Ampere Rating

UL File Reference

Main Incoming Terminal Wire Size Range 60°C or 75°C

Number of Terminals

125

E52977

#6–1/0 AWG Cu #6–2/0 AWG Al

10



20

10NEU125B

13

5.938 (150.83)

5.400 (137.16)

125

E52977

#6–1/0 AWG Cu #6–2/0 AWG Al

17



20

17NEU125B

13

8.388 (213.06)

7.850 (199.40)

125

E52977

#6–1/0 AWG Cu #6–2/0 AWG Al

20



20

20NEU125B

13

9.438 (239.73)

8.900 (226.06)

#14–4 AWG Cu/Al

#6–1/0 AWG Cu #6–2/0 AWG Al

Standard Catalog Package Number Quantity

Dimensions – Inches (mm) Figure Overall Length A

Mounting B

225

E52977

#1–300 kcmil Cu/Al

24

1

20

24NEU225B

14

10.913 (277.19) 10.300 (261.62)

225

E52977

#1–300 kcmil Cu/Al

35

1

20

35NEU225B

14

15.813 (401.65) 15.200 (386.08)

125





4

2

1

BINA

15

2.266 (57.56)

Figure 13

0.594 (15.09)

Figure 14 A

.269 (6.83)

A .344 (8.74)

B

.844 (21.44)

.269 (6.83)

B

.844 (21.44)

1.750 (44.45)

CL of Mounting Hole

CL of Mounting Hole

2.360 (59.94) 2.860 (72.64)

2.360 (59.94)

Figure 15 .120 (3.05)

A

.250 (6.35)

CL of Mounting Hole

1.182 (30.02) .750 (19.05)

.688 (17.47)

CL of Mounting Hole

.182 Diameter (4.62)

.156 (3.96)

1.750 (44.45)

1.187 (30.15)

B

.344 (8.74)

2.000 (50.80)

Add-on Lugs for Neutral Assemblies Description

Wire Size Range Cu/Al 60°C or 75°C

Ordering Quantity 1

Neutral/Ground Lug Add-On Neutral or Ground Lug

#2/0 Maximum 1 #3/0 Maximum 1 300 kcmil Maximum 1

NL20 NL30 NL300

Length Inches (mm)

Ordering Quantity 1

Catalog Number

2.54 (64.5) 3.59 (91.2) 4.29 (109.0) 5.34 (135.6) 4.61 (117.1) 5.69 (144.5) 6.74 (171.2) 8.14 (206.8) 9.19 (233.4) 5.78 (146.8)

1 1 1 1 1 1 1 1 1 1

GBK5 2 GBK520 2 GBK10 2 GBK1020 2 GBK13 2 GBK14 2 GBK1420 2 GBK21 2 GBK2120 2 BRGBK39512 34

Catalog Number

GBK14

Ground Bar Kits

f d f f f k f d f k f f f

dssssds dssssdsj dssssdssssss dssssdssssssj dssssdssssssssss dssssdssssssssssj dssssdsssssssssssssssss dssssdsssssssssssssssssj ofodofooofodofooofo 1 2 3 4

Must be purchased in multiples of ordering quantities indicated. Distance between mounting holes is 1-3/4 inches (44.5 mm). For 1- and 3-phase 400 and 600 ampere applications. Distance between mounting holes is 2-11/32 inches (59.5 mm).

BRGBK39512

Ground Bar Legend s (3) #14 – #10 Cu/Al or (1) #14 – #4 Cu/Al j (1) #6 – 2/0 Cu/Al o (1) #14 – #6 Cu/Al or (2) #14 – #12 Cu/Al (1) 1/0 – 14 or (3) #10 – 12 Cu/Al (1) #14 – 1/0 Cu/Al or (3) #14 – #10 Cu/Al f (1) #6 – 14 Cu/Al or (2) #1/0 – 14 Cu/Al d Mounting Hole

fk

Description (See Legend)

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR CIRCUIT BREAKERS

Page 24

BR Circuit Breakers Cutler-Hammer Type BR plug-on breakers in the standard 1-inch (25.4 mm) per pole package have unique color-coded cases that indicate UL listed 10 kA or 22 kA interrupting ratings and can be used as main or branch disconnect devices. All are type I.C. (interchangeable) devices; several ratings are SWD and HACR approved. Typical ampacity range for BR breakers is 15 to 150 amperes.

GFCB® People Protection Breakers Cutler-Hammer Type GFCBs (ground fault circuit breakers) combine state-ofthe-art electronic technology with a circuit breaker mechanism in a compact 1-inch (25.4 mm) per pole package. The GFCB automatically senses hot wire-to-ground faults in a 4 to 6 mA range and disconnects the power, thus providing an extra margin of safety beyond that of conventional circuit breakers. GFCB applications include bathrooms, cellar outlets, swimming pools, outdoor branch circuits and kitchen branch circuits. Available in UL listed 120 and 120/240V ratings. Cutler-Hammer also offers non-UL listed GFCBs for international applications as well as ground fault devices for equipment protection.

GFEP Equipment Protection Breakers The Cutler-Hammer Type GFEP device is similar to the GFCB, except that it is designed to protect equipment (not people) against damage from arcing ground faults. It is available with a 30 mA trip level. Applications include infrared heating equipment, computer equipment, process control equipment, etc.

BJ Circuit Breakers Available in 125 through 200 ampere frames, Cutler-Hammer Type BJ plugon breakers have 10 kA and 22 kA interrupting ratings that can be used as main or branch disconnect devices. Large extruded aluminum box lugs, complies with UL486B, provide cool operation. Tripping mechanism has thermal and magnetic protection for long-life performance. Rupture gas is safely vented into box gutter.

BD Circuit Breakers BD plug-on breakers have the same construction as Cutler-Hammer Type BR 1-inch (25.4 mm) per pole devices except that two poles are in a spacesaving 1-inch (25.4 mm) package.

UL listed interrupting rating is 10 kA. Some ratings are SWD and HACR approved. Exclusive CTL rejection feature allows only 42 circuits in the panel in compliance with NEC Article 384-15.

BQ Circuit Breakers Quadplex® construction of CutlerHammer Type BQ plug-on breakers incorporates two duplex breakers assembled together to provide various combinations of 2-pole and single-pole devices in a 2-inch (50.8 mm) package, and allows compliance with NEC Article 240-20(b). The 2-pole combinations of Cutler-Hammer Type BQ breakers are marked “independent trip” meaning that each pole of a 2-pole device trips independently of the other, but may be actuated jointly by means of the handle tie. Independent trip devices may only be used on 3-wire Edison circuits where the neutral is present.

BQC Circuit Breakers Quadplex construction of CutlerHammer Type BQC plug-on breakers incorporates a special internal common trip cam. BQC breakers are available in several combinations of 2-pole and single-pole devices wherein the 2-pole circuits have an internal common trip mechanism. These breakers are labeled “common trip” and meet all the requirements of UL489 paragraph 9.1 requiring multipole breakers to have common trip. Common trip breakers are required on all 240V circuits where there is no neutral present such as water heaters, baseboard heat, air conditioners and other motorloads. Heavy-duty mechanism spring for reliable operation.

Provision for handle tie.

Special Application Breakers As the name implies, these devices are designed for special applications as required by the National Electrical Code®.

Water Heater Breaker Some watthour meters incorporate rate register switches used in conjunction with off-peak rates. Water heater breakers do not derive their circuit from the loadcenter stab. The line and load side of the breaker are fed to terminals on the breaker. Except for these terminations, the device offers normal circuit breaker protection.

Switching Neutral Breaker Primary application for the CutlerHammer switching neutral breaker is for protection of process equipment such as gas pumps that utilize flammable liquids. Non-automatic pole breaks the neutral power leg, minimizing the danger of arc conditions.

2-Pole Breakers 120V or More-to-Ground Used on Delta distribution systems, these Type BR breakers are applied on phase legs where voltage-to-ground is above 120V.

Non-Automatic Molded Case Switch Identical to comparable circuit breaker frames with this exception: nonautomatic molded case switches do not have thermal or magnetic elements.

Arc Fault Circuit Interrupters (AFCIs) Reduce the risk of fire by detecting and interrupting electrical arcing faults which standard thermal magnetic breakers cannot. For more information, see page 27.

Black Molded Handle.

Hardened cradle for positive action under fault conditions.

Four-rivet construction enhances strength and structural integrity of breaker case.

Non-abrasive integrally molded pivot for quick mechanism response.

Common trip cam assures simultaneous pole opening. Heavy-duty multi-strand flexible copper shunt for cool operation.

One-piece moving contact arm for quick on/off response. Heavy-duty line terminal and spring clip for quick load center installation and cool operation.

Silver tungsten alloy contacts.

One-piece frame assembly for dimensional stability and reliable operation.

UL 486B approved terminal assembly for use with copper or aluminum wire. Callibrated onepiece bimetal for reliable thermal trip function.

Unique one-piece heavy-duty De-ion assembly for quick arc interruption.

Full width slot for channel type lead center hold-downs.

One-piece molded case construction.

BR Breaker Section View

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Large gas port for venting short circuit gases safely into load center gutter.

Plug-On Circuit Breakers

TYPE

BR CIRCUIT BREAKERS Page 25

Plug-On Circuit Breakers, Types BR 10,000/22,000/42,000 Amperes Interrupting Capacity 120, 120/240 or 240V AC

BR120

BR215

BR320

Type BR Breakers, 1-Inch (25.4 mm) per Pole 120, 120/240 or 240V AC, 10,000, 22,000 or 42,000 AIC Note: All Type BR 1-, 2-, and 3-pole circuit breakers carry listing for HACR application. For circuit breakers with a shunt trip, add ST suffix. Ampere Rating

Wire Size Range Cu/Al 60°C or 75°C AWG

1-Pole 120/240V AC Requires One 1-Inch (25.4 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 1-Inch (25.4 mm) Spaces

3-Pole 240V AC Common Trip Requires Three 1-Inch (25.4 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

10,000 AIC

22,000 AIC

10,000 AIC

22,000 AIC

42,000 AIC

10,000 AIC

22,000 AIC

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

10 15 20 25 30

#14 – 4

BR110 BR115 12 BR120 12 BR125 BR130

— BRH115 BRH120 BRH125 BRH130

BR210 BR215 3 BR220 3 BR225 3 BR230 3

— BRH215 BRH220 BRH225 BRH230

— — — — —

BR310 BR315 12 BR320 12 BR325 BR330

— BRH315 12 BRH320 12 BRH325 BRH330

35 40 45 50

#14 – 4

BR135 BR140 — BR150

BRH135 BRH140 BRH145 BRH150

BR235 3 BR240 3 BR245 3 BR250 3

BRH235 BRH240 3 BRH245 BRH250 3

— — — —

BR335 BR340 BR345 BR350

BRH335 BRH340 BRH345 BRH350

55

#14 – 3

BR150

BRH155

BR255

BRH255



BR355

BRH355

60 70 80 90 100 110

#4 – 1/0

BR160 BR170 — — — —

BRH160 BRH170 — — — —

BR260 BR270 BR280 BR290 BR2100 BR2110

BRH260 BRH270 BRH280 BRH290 BRH2100 BRH2110

BRHH260 BRHH270 BRHH280 BRHH290 BRHH2100 BRHH2110

BR360 BR370 BR380 BR390 BR3100 —

BRH360 BRH370 BRH380 BRH390 BRH3100 —

125 150

#4 – 2/0

— —

— —

BR2125 BR2150 4

BRH2125 —

BRHH2125 —

— —

— —

1 2 3 4

1-pole, 1-inch (25.4 mm) per pole circuit breakers are available with high magnetic setting for switching large tungsten lamp loads. Add-suffix H to catalog number. Switching duty rated. On the black handle breaker, add suffix “B” to the catalog number to obtain a tapped molded opening for proper use with hold-down kits. For use as a branch circuit breaker in 400 and 600 ampere panels only.

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR CIRCUIT BREAKERS

Special Application Plug-On Circuit Breakers

Page 26

Plug-On Ground Fault Circuit Breakers, Type GFCB and GFEP 10,000/22,000 Amperes Interrupting Capacity 120 or 120/240V AC

Type GFCB Ground Fault Circuit Breakers (5 Milliampere) 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC, 22,000 AIC Ampere Rating

Wire Size Range Cu/Al 60°C or 75°C AWG

1-Pole 120V AC Requires One 1-Inch (25.4 mm) Space

2-Pole 120/240V AC Common Trip Requires Two 1-Inch (25.4 mm) Spaces

1 per Shelf Carton 10,000 AIC

Type GFCB 1-Pole

1 per Shelf Carton

22,000 AIC

15 20 25 30 40 50 1 2

Type GFCB 2-Pole

Ground Fault Application Notes Single-pole GFCBs are designed for use in 2-wire, 120V AC circuits. Figure 16 shows a typical wiring configuration. Two-pole GFCBs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multiwire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a 120/240V AC source. Figures 17 and 18 illustrate typical wiring configurations for 120/240V AC multiwire circuits.

#14 – 4

GFCB115 GFCB120 GFCB125 GFCB130 GFCB140 —

10,000 AIC

GFCBH115 GFCBH120 GFCBH125 — — —

GFCB215 GFCB220 GFCB225 GFCB230 GFCB240 2 GFCB250 2

GFCBH215 GFCBH220 GFCBH225 GFCBH230 — —

Available with bell alarm or auxiliary switch. See circuit breaker accessories on Page 31. For use with copper wire only.

Type GFEP Ground Fault Equipment Protectors (30 Milliampere) 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC Ampere Rating

Wire Size Range 1-Pole Cu/Al 60°C or 75°C 120V AC AWG Requires One 1-Inch Space

2-Pole 120/240V AC Common Trip Requires Two 1-Inch Spaces

1 per Shelf Carton

15 20 25 30 40 50

#14 – 4

1 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number

Catalog Number

GFEP115 GFEP120 GFEP125 GFEP130 — —

GFEP215 GFEP220 GFEP225 GFEP230 GFEP240 GFEP250

Figure 19 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit. The figures are shown with a 120/240V AC, single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures, the electrical operation of the GFCB is not affected by the equipment ground.

22,000 AIC

Catalog Number

Catalog Number 1

Figure 16. 1-Pole

Figure 18. 2-Pole

Figure 17. 2-Pole

Figure 19. 2-Pole

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

Special Application Plug-On Circuit Breakers

BR CIRCUIT BREAKERS Page 27

Plug-On Arc Fault Circuit Breakers, Type BR 10,000 Amperes Interrupting Capacity 120 or 120/240V AC

Type BR FIRE-GUARD™ AFCI Circuit Breakers 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC Poles

Ampere Rating

Configuration

Catalog Number

Wire Size Range Cu/Al 60ºC or 75ºC AWG

1-Pole 10 kAIC

15

AFCI AFCI with GFCI

BR115AF BR115AFGF

#14 – 4

20

AFCI AFCI with GFCI

BR120AF BR120AFGF

#14 – 4

15

AFCI Common Trip AFCI Independent Trip AFCI Common Trip with GFCI

BR215AF BR215AFIT BR215AFGF

#14 – 4

20

AFCI Common Trip AFCI Independent Trip AFCI Common Trip with GFCI

BR220AF BR220AFIT BR220AFGF

#14 – 4

2-Pole 10 kAIC 12

1

Type BR 1- and 2-Pole AFCI Circuit Breakers

2

Common trip refers to 2-pole 240V load application sourced by 120/240V AC (see Figure 22). Independent trip refers to 2-pole shared neutral circuits (see Figure 21 and Figure 23). 120/240V AC Source N A B

120/240V AC Source N A B

Line B

Line B

2 Pole

1 Pole

Line A

Neutral 120V Duplex Receptacle

Neutral

Neutral Equipment Ground

Equipment Ground

Figure 20. 1-Pole, Single 120V Load Application Sourced by 120/240V AC 120/240V AC Source N A B

240V Duplex Receptacle

Figure 22. 2-Pole 240V Load Application Sourced by 120/240V AC 120/240V AC Source N A B

Line B

Line B Line A

2 Pole Neutral Neutral

2 Pole

2-120V Duplex Receptacles

Neutral

Neutral 120V Duplex Receptacle (With Line Side Jumper Removed) Equipment Ground

Line A Equipment Ground

Figure 21. 1-Pole Shared Neutral with Multi-Duplex Receptacle Application

Figure 23. 2-Pole Shared Neutral with Duplex Receptacle Application

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR CIRCUIT BREAKERS

Page 28

CTL Plug-On Circuit Breakers, Type BD Duplex, BQ and BQC Quadplex 10,000 Amperes Interrupting Capacity 120/240V AC

BQC230230

BQC2302115

Common Trip Quadplex Breakers Class CTL, 1-Inch (25.4 mm) per Pole 120/240V AC, 10,000 AIC — All circuit breakers have rejection tab feature. Type BQC Quadplex Common Trip Center Poles (UL Type BRD) 2-Pole 1 and 1-Pole 2

Wire Size Range Cu/Al 65°C or 75°C AWG

120V AC 120/240V AC 120V AC

Requires Two 1-Inch (25.4 mm) Spaces 5 per Shelf Carton 120V AC

Catalog Number

120/240V AC

Requires Two 1-Inch (25.4 mm) Spaces

120/240V AC

Catalog Number

Ampere Rating

Outer Left 1-Pole

Center 2-Poles Common Trip

Outer Right 1-Pole

15 15 15 15 15 — — —

20 25 30 40 50 — — —

15 15 15 15 15 — — —

BQC2202115 BQC2252115 BQC2302115 BQC2402115 BQC2502115 — — —

20 20 20 20 20 20

15 20 25 30 40 50

20 20 20 20 20 20

30 — — — —

50 — — — —

20 — — — —

2

120/240V AC

10,000 AIC 120/240V AC

Ampere Rating

1

2-Pole 1

5 per Shelf Carton

10,000 AIC 120V AC

Type BQC Quadplex Common Trip Center and Outer Poles (UL Type BRD)

Outer 2-Poles Common Trip

Center 2-Poles Common Trip

#14 – 4

15 15 15 20 20 20 20 20

15 20 30 15 20 30 40 50

BQC215215 BQC215220 BQC215230 BQC220215 BQC220220 BQC220230 BQC220240 BQC220250

BQC2152120 BQC2202120 BQC2252120 BQC2302120 BQC2402120 BQC2502120

#14 – 4

25 25 30 30 30 30 —

25 30 15 30 40 50 —

BQC225225 BQC225230 BQC230215 BQC230230 BQC230240 BQC230250 —

BQC2502030 — — — —

#14 – 4

40 40 40 50 50

30 40 50 20 50

BQC240230 BQC240240 BQC240250 BQC250220 BQC250250

All Type BQC Quadplex circuit breakers carry listing for HACR applications. All 15 and 20 ampere single poles are switching duty rated.

Notched Bus Stab

CTL Circuit Limiting Feature

Type BR or Type BD Duplex, (CTL), Type BQ and BQC Quadplex

Unnotched Bus Stab

Type BD Duplex Rejection Tab

Type BR

Notched Stab

Non-CTL Non-Circuit Limiting

Type BR

Figure 24. CTL and Non-CTL Breakers

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR CIRCUIT BREAKERS Page 29

BD2020

BQ230230

BQ2302115

Duplex and Independent Trip Quadplex Breakers Class CTL, 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC — All circuit breakers have rejection tab feature. Type BD Duplex (UL Type BRD) 1-Pole 1 120/240V AC 120/240V AC

Wire Size Range Cu/Al 65°C or 75°C AWG

Requires One 1-Inch (25.4 mm) Space

Type BQ Quadplex Independent Trip (UL Type BRD) 2-Pole 2 and 1-Pole 1

Type BQ Quadplex Independent Trip (UL Type BRD) 2-Pole 120/240V AC

120V AC 120/240V AC 120V AC

Requires Two 1-Inch (25.4 mm) Spaces

120/240V AC

Requires Two 1-Inch (25.4 mm) Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

Ampere Rating

10,000 AIC

10,000 AIC

10 – 10 15 – 15 15 – 20 15 – 30 20 – 15 20 – 20 20 – 30 25 – 25 30 – 15 30 – 20 30 – 30 30 – 40 30 – 50 50 – 30 1 2

10,000 AIC 120V AC

120V AC

Catalog Number

Ampere Rating

BD1010 BD1515 BD1520 BD1530 BD2015 BD2020 BD2030 BD2525 BD3015 BD3020 BD3030 BD3040 BD3050 BD5030

#14 – 4

120/240V AC

120V AC

Outer Left 1-Pole

Center 2-Poles Independent Trip

Outer Right 1-Pole

15 20 15 20 15 20 15 20 — — — — — —

20 20 30 30 40 40 50 50 — — — — — —

15 20 15 20 15 20 15 20 — — — — — —

Catalog Number

BQ2202115 BQ2202120 BQ2302115 BQ2302120 BQ2402115 BQ2402120 BQ2502115 BQ2502120 — — — — — —

120/240V AC Ampere Rating Outer 2-Poles Independent Trip

Center 2-Poles Independent Trip

15 20 20 20 20 25 30 30 30 40 40 50 — —

15 20 30 40 50 25 30 40 50 40 50 50 — —

All 15 and 20 ampere single poles are switching duty rated. All Type BD Duplex and BQ Quadplex circuit breakers carry listing for HACR applications.

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Catalog Number

BQ215215 BQ220220 BQ220230 BQ220240 BQ220250 BQ225225 BQ230230 BQ230240 BQ230250 BQ240240 BQ240250 BQ250250 — —

TYPE

BR CIRCUIT BREAKERS

Plug-On Circuit Breakers Special Application Plug-On Circuit Breakers

Page 30

Plug-On Circuit Breakers, Types BJ and BJH 10,000/22,000 Amperes Interrupting Capacity 120/240 or 240V AC For Use in 1-Phase and 3-Phase Loadcenters 150 Amperes and Above Type BJ

Types BJ and BJH Breakers, 1-Inch (25.4 mm) per Pole, 120/240 or 240V AC, 10,000, 22,000 AIC Note: If BJ or BJH breakers are used as a main or a back feed device, a hold-down kit is required. See Page 31. Ampere Rating

2-Pole 120/240V AC Common Trip Requires Four 1-Inch (25.4 mm) Spaces 1

Wire Size Range Cu/Al 60°C or 75°C

10 per Shelf Carton

125 150 175 200 1 2

3-Pole 240V AC Common Trip Requires Six 1-Inch (25.4 mm) Spaces 2 5 per Shelf Carton

10,000 AIC

22,000 AIC

10,000 AIC

22,000 AIC

Catalog Number

Catalog Number

Catalog Number

Catalog Number

BJ2125 BJ2150 BJ2175 BJ2200

BJH2125 BJH2150 BJH2175 BJH2200

BJ3125 BJ3150 BJ3175 BJ3200

BJH3125 BJH3150 BJH3175 BJH3200

#2 AWG – 300 kcmil

Breaker uses two 1-Inch (25.4 mm) pole spaces on left side and two 1-Inch (25.4 mm) pole spaces on right side of loadcenter. Breaker uses three 1-Inch (25.4 mm) pole spaces on left side and three 1-Inch (25.4 mm) pole spaces on right side of loadcenter.

Plug-On Special Application Circuit Breakers 10,000 Amperes Interrupting Capacity 120, 120/240 or 240V AC

BRWH215 Water Heater Breaker

BRSN220 Switching Neutral Breaker

Special Application Circuit Breakers, 1-Inch (25.4 mm) per Pole, 120, 120/240 or 240V AC Water Heater Breakers 2-Pole 120/240V AC Common Trip Requires Two 1-Inch (25.4 mm) Spaces

Switching Neutral Breakers

LINE LOAD

2-Pole 120V AC Common Trip Requires Two 1-Inch (25.4 mm) Spaces

OUT IN NEUTRAL

Wire Size Range Cu/Al 60°C or 75°C AWG

240V Breakers

Non-Automatic Molded Case Switches

2-Pole 240V AC Common Trip Requires Two 1-Inch (25.4 mm) Spaces

2-Pole 240V AC Requires Two 1-Inch (25.4 mm) Spaces

With Isolated Line Terminals for Separately Metered Water Heaters

With Switching Neutral Pole for Gasoline Pump Applications

Where Voltage to Ground is 240V AC

For Use as Disconnect Contains No Magnetic or Thermal Trip Properties

5 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

10,000 AIC

Ampere Rating

Catalog Number

Ampere Rating

Catalog Number

Ampere Rating

15 20 30 — — — — — — —

BRWH215 BRWH220 BRWH230 — — — — — — —

15 20 25 30 — — — — — —

BRSN215 BRSN220 BRSN225 BRSN230 — — — — — —

#14 – 4

— — — — —

— — — — —

— — — — —

— — — — —

#4 – 1/0

5,000 AIC Catalog Number

Ampere Rating

Catalog Number

10 15 20 25 30 35 40 45 50 55

BR210H BR215H BR220H BR225H BR230H BR235H BR240H BR245H BR250H BR255H

— — — — — — — — 50 —

— — — — — — — — BR250NA —

60 70 80 90 100

BR260H BR270H BR280H BR290H BR2100H

60 — — — 100

BR260NA — — — BR2100NA

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Accessories

TYPE

BR CIRCUIT BREAKERS Page 31

Circuit Breaker Accessories Ordering Catalog Quantity Number

Description

1

Handle Ties 2 Handle tie bar for physically joining the handles of two adjacent 1-pole Type BR Circuit Breakers. (Metal Cylinder Pin Type) Handle tie bar for joining two independent outside poles of Types BQ and BQC Quadplex and outside poles of two Type BD Duplex Circuit Breakers. Handle tie bar for joining two adjacent outside poles of Types BQ and BQC Quadplex and outside poles of two Type BD Duplex Circuit Breakers. Handle Lockoffs 3 Padlockable device for locking the handle of 1-, 2-, or 3-pole Type BR Circuit Breakers and 1-pole of a Type BD Duplex or one independent outside pole of a Type BQ or BQC Quadplex Circuit Breaker. (Escutcheon Mounted) 4 Padlockable device for locking the handle of a 1-pole Type BR Circuit Breaker. (Handle Mounted) 5 Padlockable device for locking the handle of a 2- and 3-pole Type BR Circuit Breaker. (Handle Mounted) 5 Padlockable device for locking the handle of a 1-pole Type BD Duplex, BQ or BQC Quadplex Circuit Breaker. (Handle Mounted) 5 Padlockable device for locking the handle of the two center poles and the two outer poles of a 2-pole Type BQ and BQC of Type BQ and BQC Quadplex Circuit Breakers. (Escutcheon Mounted) 4 Handle Lockdogs 6 Device used to secure handle in “On” or “Off” position for 1-, 2-, or 3-pole Type BR Circuit Breakers and 1-pole of Type BD Duplex and one independent outside pole of Type BQ or BQC Quadplex Circuit Breakers. (Escutcheon Mounted) 4 Device used to secure handle in “On” or “Off” position for 1-pole Type BR Circuit Breakers. (Handle Mounted) 5 Device used to secure handle in “On” or “Off” position for 2- and 3-pole Type BR Circuit Breakers. (Handle Mounted) 5 Device used to secure handle in “On” or “Off” position for 1-pole Type GFCB Ground Fault Circuit Breakers. (Handle Mounted) 5 Device used to secure handle in “On” or “Off” position for one independent outside pole of Types BQ and BQC Quadplex or 1-pole Type BD Duplex Circuit Breakers. (Handle Mounted) 5 Hold-Down Kits 7 Hold-down screw kit for 2-pole Type BR Circuit Breakers in 1-phase MLO Loadcenters through 125 amperes. Hold-down screw kit for 2-pole Type BR Circuit Breakers in MLO Loadcenters 150 through 225 amperes (1-phase only). Hold-down screw kit for 2-pole Types BJ and BJH Circuit Breakers in MLO Loadcenters 125 through 225 amperes. Hold-down screw kit for 3-pole Types BJ and BJH Circuit Breakers in MLO Loadcenters 125 through 225 amperes. Mechanical Interlocks Types BR for 2-, 3- and 4-pole Breakers

10

BHT

10

THOW

10

THS1

BHLW2

THS1

BRLW2 10

BRLW

10

BRLW1

10

BRLW2

10

BRDL1

10

BRQLW

BREQS125

BRHDK125

BRQLW 10

BHLW

10

BHLW1

10

BHLW2

10

BHGW

10

HLW1

1

BREQS125

1

BRHDK125

1

BJHDS

1

BJHDS3P

10

BRML

Shunt Trips for BR 120V

1

ST 8

Alarm Contacts for Type GFCB (1-Pole) Alarm Contact for GFCB (1-Pole) (1) N.O. and (1) N.C.

1 1

W1 8 W2 8

BHLW

THOW (Installed)

BRML

BRSF125

FIeld Installation Kits and Parts Number of Poles

Ampere Rating

Number of 1-inch (25.4 mm) Spaces Needed

Wire Size Range Cu/Al 60°C or 75°C

Ordering Catalog Quantity Number 1

Main and Sub-Feed Lug Blocks 2

125 150 225

2 2 2

#8 – 2/0 AWG #8 – 2/0 AWG #2 AWG – 300 kcmil

1 1 1

BRSF125 BRSF150 BRS225

3

150 225

3 3

#8 – 2/0 AWG #2 AWG – 300 kcmil

1 1

3BRSF150 3BRS225

1 2 3 4 5 6 7 8

3BRS225

Must be purchased in multiples of ordering quantities indicated. Handle Ties: Typically used to join two similar independent single-pole breakers to form a 2-pole noncommon trip breaker. Handle Lockoffs: Devices that use a padlock to lock the circuit breaker’s handle in the “On” or “Off” position. Escutcheon Mounted: Device mounted semipermanently to the face of the circuit breaker and secured by the loadcenter deadfront. Handle Mounted: Device mounted directly to the handle by the use of a set screw. Handle Lockdogs: Devices that are used to secure a circuit breaker’s handle in the “On” or “Off” position. Handle Lockdogs are not padlockable devices. Hold-Down Kits: Devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(g). Add suffix indicated to end of breaker catalog number.

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Single-Phase Single-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

Page 32

70 2 AMP

4

SPACES

SINGLE POLES

DIAGRAM 18 .703 (17.86)

#10 Mounting Screws

4.359 (110.72)

.297 .625 (7.54) (15.88)

.156 (3.96)

1.625 (41.28)

2.250 (57.15)

1.063 (26.99) .156 Diameter Nib

1.812 (30.02)

.031 x 45° Chamfer 1 Nib Required

2.000 (50.80) 3.563 (90.50)

.625 (15.88)

.187 (4.75) 3.000 (76.2) 3.345 (84.96) Maximum

1.063 (27.00)

2.688 (68.28)

Handle Height

#14 - 2 AWG (Al/Cu)

1.782 (45.26)

24INT70B

125 2 AMP

SPACES

4

SINGLE POLES

DIAGRAM 19 .703 (17.86)

#10 Mounting Screws

.297 .625 (7.54) (15.88)

.156 (3.96)

1.625 (41.28)

2.250 (57.15)

4.359 (110.72) 1.063 (26.99)

.156 Diameter Nib

1.812 (46.02)

.031 x 45° Chamfer 1 Nib Required

2.000 (50.80) 3.563 (90.50)

.625 (15.88)

.187 (4.75) 3.000 (76.20) 3.545 (90.04) Maximum

1.063 (26.99)

2.688 (68.28)

#2/0 to 12 AWG (Al)

Handle Height

.183 (4.65) 1.782 (45.26)

24INT125B

Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Single-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

TYPE

BR ASSEMBLIES Page 33

125 6 AMP

SPACES

12

SINGLE POLES

DIAGRAM 20 (

) Wire Range: (1) 2/0 - 14 AWG (Al/Cu)

2.146 (54.51)

4.152 (105.46)

.218 (5.54)

2.868 (72.85)

1.795 (45.59)

3.110 (78.99) 3.655 (92.84) Maximum Handle Height

.187 (4.75)

2.388 (60.66)

1.000 (25.40) 8.500 (215.90)

.310 (7.87) 9.250 (235.00)

612INT125SRB

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

Page 34

125 4 AMP

SPACES

8

125 6

SINGLE POLES

AMP

DIAGRAM 21

12

SINGLE POLES

DIAGRAM 22 1.795 (45.59)

.156 Diameter Nib .625 (15.88)

SPACES

XXXX (XXXX)

XXXX (XXXX)

.031 x 45° Chamfer 1 Nib Required

2.146 (54.51)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

3.655 (92.84) 3.000 (76.20)

Maximum Handle Height

1.389 (35.28)

3.110 (78.99)

3.545 (90.04) Maximum Handle Height

.187 (4.75) .187 (4.75) 5.736 (145.69) 2.250 (57.15)

1.812 (46.02)

.703 (17.86)

.310 (7.87)

2.388 (60.66) 2.688 (68.28)

2.000 (50.80)

7.249 (184.12) 1.782 (45.26)

1.063 (26.99)

.220 Diameter (5.59)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

#10 Mounting Screws

3.563 (90.50)

2.868 (72.85)

CL breaker

1.000 6.401 (25.40) (162.59)

1.063 (26.99)

5.874 (149.20) .218 (5.54)

612INT125B

48INT125B

Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

TYPE

BR ASSEMBLIES Page 35

125 8 AMP

SPACES

16

SINGLE POLES

DIAGRAM 23

AMP

2.146 (54.51)

1.795 (45.59)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

3.655 (92.84) 1.389 (35.28)

Maximum Handle Height

2.146 (54.51)

SINGLE POLES

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

1.389 (35.28)

3.110 (78.99)

.187 (4.75)

.187 (4.75)

5.736 (145.69) 2.868 (72.85)

5.736 (145.69)

.220 Diameter (5.59)

.310 (7.87)

2.388 (60.66)

7.249 (184.12)

12

3.655 (92.84)

3.110 (78.99)

.310 (7.87)

SPACES

DIAGRAM 24 1.795 (45.59)

Maximum Handle Height

125 12

2.868 (72.85)

.220 Diameter (5.59)

2.388 (60.66)

CL breaker

CL breaker

1.000 6.401 (25.40) (162.59)

1.000 (25.40) 9.250 (235.00)

8.500 (215.90)

.218 (5.54)

816INT125B

.218 (5.54)

1212INT125B

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

Page 36

125 12 AMP

SPACES

24

SINGLE POLES

DIAGRAM 25

AMP

2.146 (54.51)

1.795 (45.59)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

24

SINGLE POLES

2.146 (54.51)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

3.655 (92.84)

3.655 (92.84) 1.389 (35.28)

3.110 (78.99)

Maximum Handle Height

1.389 (35.28)

3.110 (78.99)

.187 (4.75)

.187 (4.75)

5.736 (145.69)

5.736 (145.69) .310 (7.87)

SPACES

DIAGRAM 26

1.795 (45.59)

Maximum Handle Height

125 16

2.868 (72.85)

.310 (7.87)

.220 Diameter (5.59)

2.868 (72.85)

.220 Diameter (5.59)

2.388 *(70.15)

2.388 (60.66)

CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40) 9.250 (235.00)

8.500 (215.90)

11.250 (285.75) 10.500 (266.70) .218 (5.54)

.218 (5.54)

1224INT125B

1624INT125B

Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

BR ASSEMBLIES

TYPE

Page 37

125 20 AMP

SPACES

24

SINGLE POLES

DIAGRAM 27

AMP

2.146 (54.51)

1.795 (45.59)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

3.655 (92.84)

24

2.146 (54.51)

SINGLE POLES

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

3.655 (92.84)

1.389 (35.28)

3.110 (78.99)

Maximum Handle Height

1.389 (35.28)

3.110 (78.99)

.187 (4.75)

.187 (4.75)

5.736 (145.69)

5.736 (145.69) .310 (7.87)

SPACES

DIAGRAM 28 1.795 (45.59)

Maximum Handle Height

125 24

2.868 (72.85)

.220 Diameter (5.59)

.310 (7.87)

2.868 (72.85)

.220 Diameter (5.59)

2.388 (60.66)

2.388 (60.66)

CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40)

13.250 (336.55) 12.500 (317.50) 15.250 (387.35) 14.500 (368.30)

.218 (5.54)

2024INT125B

.218 (5.54)

2424INT125B

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

Page 38

200 8 AMP

SPACES

16

SINGLE POLES

DIAGRAM 29

AMP

SPACES

24

2.954 (75.03)

1.391 (35.33)

Wire Range: (1) 300 kcmil - #6 AWG (Al/Cu)

2.954 (75.03)

Wire Range: 300 kcmil - #1 AWG (Al/Cu)

3.655 (92.84)

3.655 (92.84) 3.110 (78.99)

1.500 (38.10)

Maximum Handle Height

3.110 (78.99)

1.500 (38.10)

.187 (4.75)

.187 (4.75)

5.736 (145.69)

5.736 (145.69) .310 (7.87)

SINGLE POLES

DIAGRAM 30

1.391 (35.33)

Maximum Handle Height

200 12

2.868 (72.85)

.310 (7.87)

.220 Diameter (5.59)

2.868 (72.85)

.220 Diameter (5.59)

2.762 (70.15)

2.762 (70.15)

CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40) 9.625 (244.48)

9.625 (244.48)

8.875 (225.43)

8.875 (225.43)

.218 (5.54)

.218 (5.54)

.187 (4.75)

1224INT200B 3.655 (92.84) 2.671 (67.84)

Wire Range: 300 kcmil - #6 AWG (Al/Cu)

3.110 (78.99)

2.100 (53.34)

Maximum Handle Height

1.530 (38.86)

816INT200B

Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Double-Row Breaker Mounting – Aluminum Bus 120/240V AC, 3-Wire

TYPE

BR ASSEMBLIES Page 39

200 30 AMP

SPACES

40

SINGLE POLES

DIAGRAM 31

AMP

2.954 (75.03)

1.391 (35.33)

Wire Range: 300 kcmil - #1 AWG (Al/Cu)

42

2.954 (75.03)

SINGLE POLES

Wire Range: 300 kcmil - #1 AWG (Al/Cu)

3.655 (92.84)

3.655 (92.84) 3.110 (78.99)

1.500 (38.10)

Maximum Handle Height

3.110 (78.99)

1.500 (38.10)

.187 (4.75)

.187 (4.75)

5.736 (145.69)

5.736 (145.69) .310 (7.87)

SPACES

DIAGRAM 32

1.391 (35.33)

Maximum Handle Height

225 42

2.868 (72.85)

.220 Diameter (5.59)

.310 (7.87)

2.868 (72.85)

.220 Diameter (5.59)

2.762 (70.15)

2.762 (70.15)

CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40)

19.625 (498.48)

18.875 (479.43)

.218 (5.54)

25.625 (650.88)

3040INT200B

24.875 (631.83)

.218 (5.54)

4242INT225B

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

Page 40

125 8 AMP

SPACES

16

SINGLE POLES

DIAGRAM 33

AMP

2.146 (54.51)

1.795 (45.59)

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

3.655 (92.84) 1.389 (35.28)

Maximum Handle Height

2.146 (54.51)

SINGLE POLES

Wire Range: (1) 2/0 - #14 AWG (Al/Cu)

1.389 (35.28)

3.110 (78.99)

.187 (4.75)

.187 (4.75)

5.736 (145.69) 2.868 (72.85)

5.736 (145.69) .310 (7.87)

.220 Diameter (5.59)

2.388 (60.66)

7.249 (184.12)

12

3.655 (92.84)

3.110 (78.99)

.310 (7.87)

SPACES

DIAGRAM 34

1.795 (45.59)

Maximum Handle Height

125 12

2.868 (72.85)

.220 Diameter (5.59)

2.388 (60.66)

CL breaker

CL breaker

1.000 6.401 (25.40) (162.59)

1.000 (25.40) 9.250 (235.00)

8.500 (215.90)

.218 (5.54)

816INT125BC

.218 (5.54)

1212INT125BC

Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Single-Phase Double-Row Breaker Mounting – Copper Bus 120/240V AC, 3-Wire

TYPE

BR ASSEMBLIES Page 41

200 12 AMP

SPACES

24

SINGLE POLES

DIAGRAM 35

1.391 (35.33)

2.954 (75.03)

Wire Range: 300 kcmil - #1 AWG (Al/Cu)

3.655 (92.84) Maximum Handle Height

3.110 (78.99)

1.500 (38.10)

.187 (4.75)

5.736 (145.69) .310 (7.87)

2.868 (72.85)

.220 Diameter (5.59)

2.762 (70.15) CL breaker

1.000 (25.40) 9.625 (244.48)

8.875 (225.43)

.218 (5.54)

1224INT200BC

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Three-Phase Double-Row Breaker Mounting – Aluminum Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

Page 42

125 12 AMP

SPACES

24

SINGLE POLES

DIAGRAM 36

150 18 AMP

SPACES

36

DIAGRAM 37

1.570 (39.88)

Wire Range: #8 - 2/0 AWG (Al/Cu)

1.500 (38.10)

1.500 (38.10)

Wire Range: 300 kcmil - #2 AWG (Al/Cu)

3.655 (92.84) 2.811 (71.40)

1.612 (40.94)

Maximum Handle Height

2.572 (65.33)

3.110 (78.99)

.187 (4.75) Unuseable Space

5.736 (145.69) .310 (7.87)

SINGLE POLES

2.868 (72.85)

5.736 (145.69) .310 (7.87)

.220 Diameter (5.59)

2.388 (60.66)

2.868 (72.85)

.220 Diameter (5.59)

3.760 (95.50)

CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40)

13.250 (336.55)

13.625 (346.08)

12.500 (317.50)

12.875 (327.03)

.218 (5.54)

.218 (5.54)

1224INT3125B

1836INT3150B

Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Three-Phase Double-Row Breaker Mounting – Aluminum Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

TYPE

BR ASSEMBLIES Page 43

150 24 AMP

SPACES

42

SINGLE POLES

DIAGRAM 38

AMP

1.500 (38.10)

1.500 (38.10)

1.570 (39.88)

Wire Range: 300 kcmil - #2 AWG (Al/Cu)

3.655 (92.84)

2.572 (65.33)

3.110 (78.99)

42

1.500 (38.10)

1.500 (38.10)

SINGLE POLES

Wire Range: 300 kcmil - #2 AWG (Al/Cu)

3.655 (92.84) Maximum Handle Height

2.572 (65.33)

3.110 (78.99)

.187 (4.75)

.187 (4.75)

5.736 (145.69) .310 (7.87)

SPACES

DIAGRAM 39

1.570 (39.88)

Maximum Handle Height

200 30

2.868 (72.85)

5.736 (145.69)

.220 Diameter (5.59)

.310 (7.87)

3.760 (95.50)

2.868 (72.85)

.220 Diameter (5.59)

3.760 (95.50)

CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40)

19.625 (498.48)

19.625 (498.46)

18.875 (479.43)

18.875 (479.43)

.218 (5.54)

.218 (5.54)

2442INT3150B

3042INT3200B

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

TYPE

BR ASSEMBLIES

Three-Phase Double-Row Breaker Mounting – Aluminum Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

Page 44

225 42 AMP

SPACES

42

SINGLE POLES

DIAGRAM 40 1.570 (39.88)

1.500 (38.10)

1.500 (38.10)

Wire Range: 300 kcmil - #2 AWG (Al/Cu)

3.655 (92.84) Maximum Handle Height

2.572 (65.33)

3.110 (78.99)

.187 (4.75)

5.736 (145.69) .310 (7.87)

2.868 (72.85)

.220 Diameter (5.59)

3.760 (95.50)

CL breaker

1.000 (25.40)

25.625 (650.88)

24.875 (631.83)

.218 (5.54)

4242INT3225B Legend Dimensions – Inches (mm)

Notched Bus Stab

Solid Bus Stab

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

Three-Phase Double-Row Breaker Mounting – Copper Bus 208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

TYPE

BR ASSEMBLIES Page 45

125 12 AMP

SPACES

24

SINGLE POLES

DIAGRAM 41

200 12 AMP

SPACES

24

SINGLE POLES

DIAGRAM 42 1.570 (39.88)

1.500 (38.10)

1.500 (38.10)

Wire Range: 300 kcmil - #2 AWG (Al/Cu)

Wire Range: #8 - 2/0 AWG (Al/Cu)

3.655 (92.84) Maximum Handle Height

2.811 (71.40)

2.572 (65.33)

3.110 (78.99)

1.612 (40.94)

.187 (4.75)

Unuseable Space

5.736 (145.69) 5.736 (145.69) .310 (7.87)

2.868 (72.85)

.310 (7.87)

2.868 (72.85)

.220 Diameter (5.59)

.220 Diameter (5.59)

3.760 (95.50)

2.388 (60.66) CL breaker

CL breaker

1.000 (25.40)

1.000 (25.40)

13.250 (336.55)

13.625 (346.08) 12.500 (317.50)

12.875 (327.03)

.218 (5.54)

.218 (5.54)

1224INT3125BC

1224INT3200BC

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

OTHER

OEM PRODUCTS

Surge Protectors

Page 46

Surge Protectors

CHSA Surge Protector

CHSA — For use on single-phase, 120/240V AC systems. This easily plugs into a single-phase Type CH loadcenter and occupies two 3/4-inch (19.1 mm) pole spaces similar to a 2-pole Type CH breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire loadcenter. If internal components are damaged, the CHSA LED visual indicators will signal the need for replacement. This device is suitable for service entry locations installed in accordance with NEC Article 280. The CHSA is ideal for protecting sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.

BRSURGE — For use on single-phase, 120/240V AC systems. This easily plugs into a single-phase Type BR loadcenter and occupies two 1-inch (25.4 mm) pole spaces similar to a 2-pole Type BR breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire loadcenter. If internal components are damaged, the BRSURGE LED visual indicators will signal the need for replacement. This device is suitable for service entry locations installed in accordance with NEC Article 280. The BRSURGE is ideal for protecting sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.

BRSURGE Surge Protector

Surge Products Product

Catalog Number

Stage 1 Protection CHSP Micro™

CHSPMICRO CHSPMICRO230INT 1

CHSP Max™

CHSPMAX CHSPMAX230INT 1

CHSP 3-Way™

CHSPCHSR4P

CHSP Ultra™

CHSPULTRA

CHSP (Cutler-Hammer Surge Protector)

Primary Protection for Service Entrance The best place to install surge protection is at the electrical entrance point. The service entrance (loadcenter or breaker panel) is often where AC power, telephone lines and cable lines are located. Applying a CHSP product to your service entrance will reduce a voltage surge to an acceptable level for appliances and surge strips. For added protection, it is recommended that you install surge protection for your cable and telephone lines (see accessories) at the service entrance. The benefit of installing these products is that your AC, cable and telephone lines will all have the same ground potential, in one common location, for passing the surge away from your equipment.

Accessories SurgeTel™

DHW4PT

SurgeCable™

DCXCAB2

SurgeEthernet™

DRJ45D30R

Flushmount Kit™

CHSPFMKIT

1

230V, 50 Hz international applications.

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

OTHER

OEM PRODUCTS Page 47

Notes

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

OTHER

OEM PRODUCTS

Page 48

Notes

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

For more information on Cutler-Hammer products, call 1-800-525-2000 or 1-616-982-1059, for engineering services call 1-800-498-2678, or visit our website at www.cutlerhammer.eaton.com

Publication No. B.31.02.S.E February 2001 Printed in U.S.A. / CMS 7402

B3102SE

Cutler-Hammer, a part of Eaton Corporation, is a worldwide leader providing customer-driven solutions. From power distribution and electrical control products to industrial automation, Cutler-Hammer utilizes advanced product development, world-class manufacturing, and offers global engineering services and support.