DS9436 Fire Annunciator Keypad ▶ Compatible with DS9400 Series Fire Alarm Control Panels (with version 2.02 or higher firmware installed) ▶ 2-line, 16-character LCD display ▶ Onboard LEDs for Silenced, Fire, Alarm and Power indication ▶ Silence and Reset buttons ▶ Built-in keyswitch ▶ Attractive, low-profile enclosure ▶ UL Listed

The DS9436 is a 4-wire LCD annunciator keypad used with the DS9400 Series Fire Alarm Control Panels to establish the location of a fire alarm. The 2-line, 16-character display is capable of showing all messages normally displayed on the control panel. All alarm and status messages are included. Four onboard LEDs provide easy reading of the annunciators status from a distance. There are Silence and Reset buttons for controlling annunciator and control panel operation. A built-in keyswitch offers extra security by locking out the annunciator to prevent unwanted silence or resetting of the control panel.

The maximum length between any one device and the panel terminals depends on the current drawn on the branch that the device is on. The current draw on a particular branch can be found by adding together the individual current draws of each device connected to the branch.

Certifications and Approvals

Technical Specifications

Region

Certification

USA

UL

Compatible Control Panels:

UOXX: Control Unit Accessories, System (UL864)

Installation/Configuration Notes

Note

Please refer to the control panel’s Reference Guide for complete wire length calculations.

Number of Keypads Up to three keypads may be used on any single 305 m (1000 ft.) run of 1.2 mm (#18 AWG) wire.

Enclosure Design Base Dimensions (HxW):

11.6 cm x 21.0 cm (4.6 in. x 8.0 in.)

Cover Dimensions (HxW):

11.0 cm x 21.0 cm (4.3 in. x 8.0 in.)

Wiring Length per Current Draw For the DS9400 Series FACP, the maximum allowed DC current draw from the auxiliary power is 500 mA for keypads. The maximum length of wire (all branches added together) that can be connected to the option bus terminals is 1220 m (4000 ft.).

DS9400 Series Fire Alarm Control Panels with version 2.02 or higher firmware installed.

Power Requirements Current (Alarm):

100 mA

Current (Standby):

80 mA nominal

Voltage (Operating):

10.0 VDC to 13.8 VDC

www.boschsecurity.com

2 | DS9436 Fire Annunciator Keypad

Ordering Information DS9436 Fire Annunciator Keypad

DS9436

Accessories KEY‑ANN Replacement Key This is a spare or replacement key for the D7036 lock.

Americas: Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 [email protected] www.boschsecurity.us

KEY-ANN

Europe, Middle East, Africa: Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 [email protected] www.boschsecurity.com

© Bosch Security Systems Inc. 2010 | Data subject to change without notice T1119382795 | Cur: en-US, V4, 4 Jul 2010

Asia-Pacific: Represented by Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 [email protected] www.boschsecurity.com