evergreen corporate center

Report 12 Downloads 134 Views
EVERGREEN CORPORATE CENTER OFFICE FOR LEASE

33405 8th Avenue South, Federal Way, WA 98003

PROPERTY HIGHLIGHTS st

Available spaces 1 & 2

nd

Floors



From ±12,000 to ±65,000 SF



$14.00 PSF, NNN



56,000± SF floor plates



Interior & exterior remodel under way



Ample parking



Former Weyerhaeuser admin/data center



Great Federal Way/West Campus location



Available immediately!

FOR LEASE INFORMATION Contact: Mark Clirehugh or Bill Frame Kidder Mathews 1201 Pacific Avenue, Suite 1400 Tacoma, WA 98402 253.722.1400 www.kiddermathews.com Property Owned and Managed By: th 660 SW 39 Street, Suite 255 Renton, WA 98057 Phone: 425.272.0260 Fax: 425.727.0265

EVERGREEN CORPORATE CENTER FLOOR PLANS

First Floor

Second Floor

Property Owned and Managed By: th 660 SW 39 Street, Suite 255 Renton, WA 98057 Phone: 425.272.0260 Fax: 425.727.0265

EVERGREEN CORPORATE CENTER Building Specs

Building Description:

Two story office building with aluminum and glass curtain wall

Year Built:

1979

Construction Type:

V-N

Building RSF:

112,630

Parking Stalls:

371 (3.29 / 000 RSF)

Fire Sprinklers:

Yes

Ceiling Height:

8’11” (floor to finished ceiling)

Floor to Deck Height:

First Floor: Second Floor:

Loading:

Grade and partial height dock with lift

Elevators:

Two, one passenger, one passenger/freight

Utilities:

Electrical: Gas: Water/Sewer: Telephone:

12’8” 11’9”

Puget Sound Energy Puget Sound Energy Lakehaven Utility District Qwest

Electrical Service:

3,000 amp, 480/277 volt, 3-phase, 4-wire

Transformer Size:

750 KVA

Electrical Load (watts / SF): Useable w/SF: HVAC: Lighting: Data Center: Available for General Power:

20 11.5 1 2.5 5

Back-up Generator:

750 KVA Catapiller generator with 700 gallon fuel oil storage

Cooling:

Five rooftop VAV package units providing 230 tons of cooling

Heating:

Gas fired boilers to hot water terminals

Data Center:

Raised Floor: Control Center & Support: UPS Room: Battery Room: Raised Floor Height: UPS Units:

2,391 SF over standard height slab 5,000 SF over depressed height slab 1,081 SF 170 SF 156 SF 12” 1 – 225 KVA Liebert UPS 1 – 125 KVA Liebert UPS 1 – 75 KVA Liebert UPS

EVERGREEN CORPORATE CENTER Data Center Information/Systems

Electrical: Building Electrical Service: 750KVA PSE pad mounted transformer Emergency Generator:

750KVA Catapiller generator with 700 gallons fuel oil storage.

There are three UPS units in the facility serving data center 1 – 225KVA Liebert UPS 1 – 125KVA Liebert UPS 1 – 75KVA Liebert UPS 1 – 15KVA UPS unit serving wiring closet throughout building (network switch closet). Cooling Systems: The cooling system is designed for 100 tons of cooling load. There are three air-cooled chillers installed, two 50-ton Liebert air-cooled units on roof, and one 60-ton Liebert air-cooled unit at the north end of building at ground level. This system provides 100 tons of cooling with one unit for redundancy. The Data Center itself is equipped with chilled water cooling units, typically in the 20ton capacity range, which draw warm return air into the top of the unit and discharge cooler air below the raised floor.