EVERGREEN CORPORATE CENTER Building Specs
Building Description:
Two story office building with aluminum and glass curtain wall
Year Built:
1979
Construction Type:
V-N
Building RSF:
112,630
Parking Stalls:
371 (3.29 / 000 RSF)
Fire Sprinklers:
Yes
Ceiling Height:
8’11” (floor to finished ceiling)
Floor to Deck Height:
First Floor: Second Floor:
Loading:
Grade and partial height dock with lift
Elevators:
Two, one passenger, one passenger/freight
Utilities:
Electrical: Gas: Water/Sewer: Telephone:
12’8” 11’9”
Puget Sound Energy Puget Sound Energy Lakehaven Utility District Qwest
Electrical Service:
3,000 amp, 480/277 volt, 3-phase, 4-wire
Transformer Size:
750 KVA
Electrical Load (watts / SF): Useable w/SF: HVAC: Lighting: Data Center: Available for General Power:
20 11.5 1 2.5 5
Back-up Generator:
750 KVA Catapiller generator with 700 gallon fuel oil storage
Cooling:
Five rooftop VAV package units providing 230 tons of cooling
Heating:
Gas fired boilers to hot water terminals
Data Center:
Raised Floor: Control Center & Support: UPS Room: Battery Room: Raised Floor Height: UPS Units:
2,391 SF over standard height slab 5,000 SF over depressed height slab 1,081 SF 170 SF 156 SF 12” 1 – 225 KVA Liebert UPS 1 – 125 KVA Liebert UPS 1 – 75 KVA Liebert UPS
EVERGREEN CORPORATE CENTER Data Center Information/Systems
Electrical: Building Electrical Service: 750KVA PSE pad mounted transformer Emergency Generator:
750KVA Catapiller generator with 700 gallons fuel oil storage.
There are three UPS units in the facility serving data center 1 – 225KVA Liebert UPS 1 – 125KVA Liebert UPS 1 – 75KVA Liebert UPS 1 – 15KVA UPS unit serving wiring closet throughout building (network switch closet). Cooling Systems: The cooling system is designed for 100 tons of cooling load. There are three air-cooled chillers installed, two 50-ton Liebert air-cooled units on roof, and one 60-ton Liebert air-cooled unit at the north end of building at ground level. This system provides 100 tons of cooling with one unit for redundancy. The Data Center itself is equipped with chilled water cooling units, typically in the 20ton capacity range, which draw warm return air into the top of the unit and discharge cooler air below the raised floor.