Feeder MC
Armored Cable
Manufacturing quality. Delivering service.
XHHW-2 600 Volt Copper
Description:
3 or 4 conductors, stranded, insulated with heat & moisture resistant cross-linked polyethylene (type XHHW-2), phase identified, cabled together with suitable fillers** & green or bare ground conductor. Cable core covered with binder tape, aluminum or galvanized steel interlocked armor. Jacket available upon request.
Applications
Service Wire’s Feeder Size MC cable is designed to be a cost effective replacement for conduit & wire. Suitable for service, branch & feeder circuits. Ideal for use in commercial, industrial & utility applications. This flexible cable assembly offers: labor/time savings, an increased resistance to mechanical damage, system design flexibility & the reliability of a factory assembled & tested cable system.
THREE CONDUCTOR
TWO
Part Number
Size AWG or MCM
Strand (no.)
Standards:
• UL 1569, ICEA S-95-658/NEMA WC-70 • NEC Article 330 • Cable Tray Rated • RoHS Compliant • 600 Volt, 90°C rated
Color coding: K1 solid colors (#8-#1). Black and Numbered (1/0 and
larger). Green ground on #1 and smaller. Bare ground on 1/0 and larger.
Features
Suitable for use in NEC hazardous locations: • Class I, Div. 2 • Class II, Div. 2 Two-hour Firewall rated, (2/0 AWG and smaller) For use in Theatres (Article 520), Motion Picture & TV Studios (Article 530) & Places of Assembly with more than 100 people Can be messenger supported (Article 330)
Insulation Thickness (mils)
Insulated/Bare Copper Grounding Conductor(s) (AWG)
Diameter over Armor (inch)
Approx. Net Wt. per 1000 ft. (lbs.) Alum. Armor
Galv. Armor
Ampacity* (30°C Ambient Wet/Dry) 90°C
MC8/2
8
7
45
10
.71
259
337
55
MC6/2
6
7
45
8
.81
366
465
75
MC8/3
8
7
45
10
.81
339
434
55
MC6/3
6
7
45
8
.95
480
607
75
MC4/3
4
7
45
8
1.01
659
786
95
MC3/3
3
7
45
6
1.09
808
960
115
MC2/3
2
7
45
6
1.15
960
1,109
130
MC1/3
1
19
55
6
1.27
1,190
1,423
145
MC1/03
1/0
19
55
6
1.31
1,398
1,624
170
MC2/03
2/0
19
55
6
1.41
1,689
1,937
195
MC3/03
3/0
19
55
4
1.51
2,098
2,376
225
MC4/03
4/0
19
55
4
1.63
2,586
2,853
260
MC250/3
250
37
65
4
1.81
3,123
3,462
290
MC300/3
300
37
65
3
1.93
3,654
4,043
320
MC350/3
350
37
65
3
2.05
4,224
4,602
350
MC400/3
400
37
65
3
2.17
4,712
5,148
380
MC500/3
500
37
65
2
2.33
5,842
6,281
430
MC600/3
600
61
80
2
2.57
6,948
7,462
475
MC750/3
750
61
80
1
2.85
8,618
9,117
535
*Per NEC Table 310-16. **Fillers used when required. NOTE: The data shown is approximate and subject to standard industry tolerances. NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity.