For Use With PANDUIT Wyr-Grid PATHWAY SYSTEMS
Wyr-Grid Pathway Splices
Panduit Part Number: WGSPL1218**, WGSPL2430**
INSTALLATION INSTRUCTIONS © 2010 PANDUIT Corp.
PANDUIT CATALOG NUMBER
Wyr-Grid PATHWAY
WGSPL1218** WG12**10 WG18**10 WGSPL2430** WG24**10 WG30**10
Note: When Pathway Line Wires are cut in the field, maximum over hang should not exceed more than .100”
WGSPL1218**
1
WGSPL2430**
Installing Side Splices on Pathway of all widths
2
Installing Center Splices On 24” & 30” wide Pathways
Pull Up and Out
Engage Spring Tabs In four locations
4
Note: Install Center Splices on nd 2 top wire in from each side
Engage Bonding Screw Utilizing a 9/16” socket
3
Torque Specifications: 80 inch-pounds [9.0 N٠m] Note: Electrical Bonding is maintained if screw strips out.
Spring Tabs Side Splice
For Technical Assistance, Call: 800-777-3300
Wyr-Grid Intersection Splice
Panduit Part Number: WGINTSPL**
INSTALLATION INSTRUCTIONS PANDUIT CATALOG NUMBER
1
Wyr-Grid PATHWAY Any Combination Of WG12**10 WG18**10 WG24**10 WG30**10
WGINSTSPL**
Place Intersection Splices On main trunk
2
3 Slide to approximate width of Intersecting Pathway
4
Note: Pathway is placed on outside space of the Intersection Splice Spring Tabs
5 Spring Tab should be engaged to Prevent Pathway from lifting out Of Intersection Splice
Tighten until Seated With no gaps
Engage Bonding Screw Utilizing a 9/16” socket
Instruction Sheet RW273
WORLDWIDE SUBSIDIARIES AND SALES OFFICES 18900 Panduit Drive Tinley Park, IL 60487 Web Site: www.panduit.com
RACK SYSTEMS DIVISION
Fax: 708‐532‐1811 Technical Support: 800‐777‐3300 E‐mail:
[email protected]