GCV9 - Climate Solutions, Inc

Report 4 Downloads 126 Views
GMV95/GCV9 GAS FURNACE

P RODUCT S PECIFICATIONS The Goodman® GMV95/GCV9 95%/93% AFUE Two-Stage, Variable-Speed Gas Furnaces feature a patented aluminizedsteel tubular heat exchanger and durable Silicon Nitride Hot Surface Ignition system.

Standard Features • Patented TuffTube™ dual-diameter tubular heat exchanger with lifetime limited warranty plus 10-year limited furnace replacement warranty • Two-stage gas valve operates on two-stage or singlestage thermostats • Super-efficient, ultra-quiet variable-speed circulator motor gently ramps up or down according to heating or cooling demand • Silicon Nitride igniter with patented adaptive learning control for maximum igniter life • Furnace control board with self-diagnostics, color-coded lowvoltage terminals, and provisions for electronic air cleaner and 120-volt or 24-volt humidifiers • Extra-low constant fan allows homeowner to activate very low speed to efficiently circulate air throughout the home. This setting costs as little as a 75-watt light bulb to operate. • Dual-certified for sealed combustion direct vent (2-pipe) or non-direct vent (1-pipe) applications • Quiet two-speed induced draft blower • All models comply with California NOx emissions standards

95%/93% AFUE

Cabinet Features

MULTI-POSITION, TWO-STAGE/VARIABLE-SPEED HEATING INPUT: 46,000–115,000 BTU/H

• Fully insulated, heavy-gauge steel cabinet with durable baked-enamel finish • Foil-faced insulation lines the heat exchanger • Easy-to-install top venting is standard; alternate flue/vent located on the right (GMV95) • Designed for multi-position installation – GMV95: upflow, horizontal left or right; GCV9: downflow, horizontal left or right • Airtight solid bottom for side return applications and easy-cut tabs for effortless removal in bottom air inlet applications • Convenient left or right connection for gas and electric service • Coil and furnace fit flush for most installations

Contents Nomenclature ................................................................................................2 Product Specifications ................................................................................3 Dimensions .....................................................................................................4 Blower Performance Specifications........................................................7 Wiring Diagrams......................................................................................... 13 Accessories ................................................................................................... 15

SS-GMV95

www.goodmanmfg.com

6/08 Supersedes 1/08

PRODUCT SPECIFICATIONS

NOMENCLATURE G

M

V

95

70

4

B

X

A

1

2

3

4,5

6,7,8

9

10

11

12

Brand G Goodman® Brand or Distinctions™

Revisions A Initial Release B 1st Revision C 2nd Revision

Airflow Direction C Downflow/Horizontal D Dedicated Downflow H High Airflow K Dedicated Upflow M Upflow/Horizontal

NOx N Natural Gas X Low NOx

Description V Two-Stage/Variable-speed H Two-Stage/Multi-speed S Single-Stage/Multi-speed E Two-Stage/X-13 Motor

A B C D

AFUE 95 95% 9 90%+ 8 80%

Maximum CFM @ 0.5” ESP 3 1,200 4 1,600 5 2,000 045: 45,000 070: 70,000 090: 90,000

2

Cabinet Width 14” 17½” 21” 24½”

MBTU/h 115: 115,000 140: 140,000

www.goodmanmfg.com

SS-GMV95

PRODUCT SPECIFICATIONS

SPECIFICATIONS GMV95 0453BXB

GMV95 0704CXB

GMV95 0905DXB

GMV951155DXB

GCV9 0704CXB

GCV9 0905DXB

GCV9 1155DXA

High Fire Input¹

46,000

69,000

92,000

115,000

69,000

92,000

115,000

High Fire Output¹

45,000

67,000

90,000

109,000

65,000

87,000

109,000

Low Fire Input¹

32,000

48,000

64,000

80,000

48,000

64,000

80,000

Low Fire Output¹

30,800

46,400

61,700

77,400

45,000

60,100

77,400

95

95

95

95

93

93

93

1.5 - 3.0

1.5 - 4.0

2.0 - 5.0

2.0 - 5.0

1.5 - 4.0

2.0 - 5.0

2.0 - 5.0

30 - 60

30 - 60

30 - 60

30 - 60

30 - 60

30 - 60

40-70

10” X 7”

10” X 10”

11” X 10”

11” X 10”

10” x 10”

11” X 10”

11” X 10”

½

¾

1

1

¾

1

1

Heating Capacity

AFUE² Tons AC @ 0.5” ESP Temperature Rise Range (°F) Circulator Blower Size (D x W) Horespower @ 1750 RPM Speed

Variable

Variable

Vent Diameter³

2”

2”

3”

3”

2”

3”

3”

No. of Burners

2

3

4

5

3

4

5

Disposable

288

384

480

486

384

480

486

Permanent

576

768

960

972

768

960

972

10.4

12.8

14.6

14.6

12.8

14.6

14.6

15 amps

15 amps

15 amps

15 amps

15 amps

15 amps

15 amps

133

135

172

175

135

172

175

Filter Size (in²)

Electrical Data Min. Circuit Ampacity (amps)4 Max. Overcurrent Protection Ship Weight (lbs)

5

1– Natural Gas BTU/h 2– DOE AFUE based upon Isolated Combustion System (ICS) 3– Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2” or 3” in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. 4– Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. 5– Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size. May use fuses or HACR-type circuit breakers of the same size as noted. Notes: • All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply. • Gas Service Connection ½” FPT • Important: Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code and/or all existing local codes.

SS-GMV95

www.goodmanmfg.com

3

PRODUCT SPECIFICATIONS

GMV95 DIMENSIONS

Model

A

B

C

D

E

GMV950453BXB

17½”

16”

13⅛”

12⅛”

13⅝”

GMV950704CXB

21”

19½”

16⅛”

16

17½”

GMV950905DXB

24½”

23”

20⅝”

19⅜”

20⅞”

GMV951155DXB

24½”

23”

20⅝”

19⅜”

20⅞”

Notes: • Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2” or 3” in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. • Line voltage wiring can enter through the right or left side of the furnace. Low-voltage wiring can enter through the right or left side of furnace. • Conversion kits for high-altitude natural gas operation are available. Contact your Goodman distributor or dealer for details. • Installer must supply following gas line fittings, according to which entrance is used: Left—Two 90º elbows, one close nipple, straight pipe Right—Straight pipe to reach gas valve • For bottom return: Failure to unfold flanges may reduce airflow by up to 18%. This could result in performance and noise issues.

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS Position

Sides

Rear

Front

Bottom

Flue

Top

Upflow

0”

0”

3”

C

0”

1”

Horizontal

6”

0”

3”

C

0”

6”

C = If placed on combustible floor, the floor MUST be wood ONLY. Notes: • For servicing or cleaning, a 24” front clearance is required. • Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above. • In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.

4

www.goodmanmfg.com

SS-GMV95

PRODUCT SPECIFICATIONS

GCV9 DIMENSIONS

FOLDED FLANGES

FOLDED FLANGES

UNFOLDED FLANGES UNFOLDED FLANGES

Model

A

B

C

D

E

GCV90704CXB

21”

19½”

16⅛”

18”

19½”

GCV90905DXB

24½”

23”

20⅝”

21½”

23”

GCV91155DXB

24½”

23”

20⅝”

21½”

23”

Notes: • Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2” or 3” in diameter, depending upon furnace input, number of elbows, length of run, and installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. • Line voltage wiring can enter through the right or left side of the furnace. Low-voltage wiring can enter through the right or left side of furnace. • Conversion kits for high-altitude natural gas operation are available. Contact your Goodman distributor or dealer for details. • Installer must supply following gas line fittings, according to which entrance is used: Left—Two 90º Elbows, one close nipple, straight pipe Right—Straight pipe to reach gas valve • For bottom return: Failure to unfold flanges may reduce airflow by up to 18%. This could result in performance and noise issues.

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS Position

Sides

Rear

Front

Bottom

Flue

Top

Downflow

0”

0”

3”

NC

0”

1”

Horizontal

6”

0”

3”

C

0”

6”

C = If placed on combustible floor, the floor MUST be wood ONLY. NC = For installation on non-combustible floors only. A combustible floor sub-base must be used for installations on combustible flooring. Notes: • For servicing or cleaning, a 24” front clearance is required. • Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above. • In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.

SS-GMV95

www.goodmanmfg.com

5

PRODUCT SPECIFICATIONS

GMV95 HIGH- OR SINGLE-STAGE COOLING SPEEDS GMV950453BXB Cooling Speed Tap A

B

C

D ¹

GMV950704CXB

Adjust Tap

CFM¹

Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+)

540 600 660 720 800 880 900 1,000 1,100 1,080 1,200 1,320

Cooling Speed Tap A

B

C

D

GMV950905DXB

Adjust Tap

CFM¹

Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+)

540 600 660 720 800 880 990 1,100 1,210 1,286 1,429 1,572

Cooling Speed Tap A

B

C

D

GMV951155DXB

Adjust Tap

CFM¹

Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+)

720 800 880 990 1,100 1,210 1,260 1,400 1,540 1,620 1,800 1,980

Cooling Speed Tap A

B

C

D

Adjust Tap

CFM¹

Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+) Minus (-) Normal Plus (+)

720 800 880 990 1,100 1,210 1,260 1,400 1,540 1,620 1,800 1,980

@ .1” to .8” W.C. ESP

Notes: • All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed. • For most jobs, about 400 CFM per ton when cooling is desirable. • Do not operate above .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only. • Constant Fan mode is 50% of above values

GMV95 LOW-STAGE COOLING SPEEDS GMV950453BXB Cooling Speed Tap

A

B

C

D

¹

GMV950704CXB

Adjust Tap

CFM¹

Minus (-)

380*

Normal

390

Cooling Speed Tap

A

GMV950905DXB

Adjust Tap

CFM¹

Minus (-)

378*

Normal

390

Cooling Speed Tap

A

Adjust Tap

CFM¹

Minus (-)

513*

Normal

520

GMV951155DXB Cooling Adjust Speed CFM¹ Tap Tap Minus (-) 514* A

Normal

520 572

Plus (+)

429

Plus (+)

429

Plus (+)

572

Plus (+)

Minus (-)

468

Minus (-)

468

Minus (-)

644

Minus (-)

644

Normal

520

Normal

520

Normal

715

Normal

715

B

B

B

Plus (+)

572

Plus (+)

572

Plus (+)

787

Plus (+)

787

Minus (-)

585

Minus (-)

644

Minus (-)

819

Minus (-)

819

Normal

650

Normal

715

Normal

910

Plus (+)

715

C

Plus (+)

787

Plus (+)

1,001

Minus (-)

702

Minus (-)

836

Minus (-) 1,053

Normal

780

Plus (+)

858

D

Normal

929

Plus (+)

1,022

C

D

Normal

1,170

Plus (+)

1,287

C

Normal

910

Plus (+)

1,001

Minus (-) 1,053 D

Normal

1,170

Plus (+)

1,287

@ .1” to .8” W.C. ESP

Notes: • All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed. • For most jobs, about 400 CFM per ton when cooling is desirable. • Do not operate above .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.

6

www.goodmanmfg.com

SS-GMV95

PRODUCT SPECIFICATIONS

GMV95 HEATING SPEEDS Heating Speed Tap A

B

C

D

Heating Speed Tap A

B

C

D

SS-GMV95

GMV950453BXB (Rise Range: 30° - 60°F) Low Stage High Stage Adjust CFM @ .1” to CFM @ .1” to Tap .5” W.C. ESP .5” W.C. ESP Minus (-) 495 713 Normal 550 792 Plus (+) 605 871 Minus (-) 540 778 Normal 600 864 Plus (+) 660 950 Minus (-) 585 842 Normal 650 936 Plus (+) 715 1,030 Minus (-) 630 907 Normal 700 1,008 Plus (+) 770 1,109

GMV950905DXB (Rise Range: 30° - 60°F) Low Stage High Stage Adjust CFM @ .1” to CFM @ .1” to Tap .5” W.C. ESP .5” W.C. ESP Minus (-) 1,013 1,458 Normal 1,125 1,620 Plus (+) 1,238 1,782 Minus (-) 1,076 1,549 Normal 1,195 1,721 Plus (+) 1,315 1,893 Minus (-) 1,139 1,639 Normal 1,265 1,822 Plus (+) 1,392 2,004 Minus (-) 1,202 1,730 Normal 1,335 1,922 Plus (+) 1,469 2,115

Rise (°F) 57 51 46 52 47 43 48 43 39 45 40 36

Rise (°F) 56 50 45 52 47 43 49 44 40 47 42 38

Heating Speed Tap A

B

C

D

Heating Speed Tap A

B

C

D

www.goodmanmfg.com

GMV950704CXB (Rise Range: 30° - 60°F) Low Stage High Stage Adjust CFM @ .1” to CFM @ .1” to Tap .5” W.C. ESP .5” W.C. ESP Minus (-) 756 1,089 Normal 840 1,210 Plus (+) 924 1,331 Minus (-) 828 1,192 Normal 920 1,325 Plus (+) 1,012 1,457 Minus (-) 900 1,296 Normal 1,000 1,440 Plus (+) 1,100 1,584 Minus (-) 972 1,400 Normal 1,080 1,555 Plus (+) 1,188 1,711

GMV951155DXB (Rise Range: 30° - 60°F) Low Stage High Stage Adjust CFM @ .1” to CFM @ .1” to Tap .5” W.C. ESP .5” W.C. ESP Minus (-) 1,107 1,594 Normal 1,230 1,771 Plus (+) 1,353 1,948 Minus (-) 1,139 1,639 Normal 1,265 1,822 Plus (+) 1,392 2,004 Minus (-) 1,170 1,685 Normal 1,300 1,872 Plus (+) 1,430 2,059 Minus (-) 1,202 1,730 Normal 1,335 1,922 Plus (+) 1,469 2,115

Rise (°F) 56 50 46 51 46 42 47 42 38 43 39 35

Rise (°F) 63 57 52 62 56 50 60 54 49 58 53 48

7

PRODUCT SPECIFICATIONS

GMV95 BLOWER PERFORMANCE

8

www.goodmanmfg.com

SS-GMV95

PRODUCT SPECIFICATIONS

GCV9 COOLING SPEEDS HIGH- /SINGLE-STAGE & LOW-STAGE COOLING SPEEDS Cooling Speed Tap A

B

C

D

GCV90704CXA CFM at .1” to .8” w.c. ESP Adjust High/SingleTap Low Stage Stage Minus (-) 378* 540 Normal 390 600 Plus(+) 429 660 Minus (-) 468 720 Normal 520 800 Plus(+) 572 880 Minus (-) 644 990 Normal 715 1,100 Plus(+) 787 1,210 Minus (-) 836 1,286 Normal 929 1,429 Plus(+) 1,022 1,572

Cooling Speed Tap

* Motor CFM maximum

A

B

Cooling Speed Tap A

B

C

D

GCV91155DXA CFM at .1” to .8” w.c. ESP Adjust High/SingleTap Low Stage Stage Minus (-) 500* 705 Normal 508 783 Plus(+) 559 861 Minus (-) 621 982 Normal 690 1,091 Plus(+) 759 1,200 Minus (-) 815 1,265 Normal 906 1,406 Plus(+) 997 1,547 Minus (-) 1,049 1,628 Normal 1,165 1,809 Plus(+) 1,282 1,990

C

D

GCV90905DXA CFM at .1” to .8” w.c. ESP Adjust High/SingleTap Low Stage Stage Minus (-) 513* 720 Normal 520 800 Plus(+) 572 880 Minus (-) 644 990 Normal 715 1,100 Plus(+) 787 1,210 Minus (-) 819 1,260 Normal 910 1,400 Plus(+) 1,001 1,540 Minus (-) 1,053 1,620 Normal 1,170 1,800 Plus(+) 1,287 1,980

* Motor CFM maximum

* Motor CFM maximum Notes: • These charts are for furnaces installed at 0 - 2000 feet. At higher altitudes, a properly derated unit will have the same temperature rise at a particular CFM, while the ESP at that CFM will be lower. • The installation must be adjusted to obtain a temperature rise within the range listed on the furnace nameplate. • Do not operate above .5” w.c. ESP in heating mode. • Propane gas installations will have a High Stage rise approximately 4° lower than shown in above table.

SS-GMV95

www.goodmanmfg.com

9

PRODUCT SPECIFICATIONS

GCV9 COOLING SPEEDS (CONT.) COOLING-BASED CONTINUOUS FAN SPEEDS GCV90704CXA Continuous Cooling Adjust Fan Speed Speed Tap Tap CFM Minus (-) 380* A Normal 380* Plus(+) 380* Minus (-) 403 B Normal 448 Plus(+) 493 Minus (-) 554 C Normal 616 Plus(+) 678 Minus (-) 720 D Normal 800 Plus(+) 880

GCV90905DXA Continuous Cooling Adjust Tap Fan Speed Speed Tap CFM Minus (-) 513* A Normal 513* Plus(+) 513* Minus (-) 554 B Normal 616 Plus(+) 678 Minus (-) 706 C Normal 784 Plus(+) 862 Minus (-) 907 D Normal 1,008 Plus(+) 1,109

GCV91155DXA Continuous Cooling Adjust Tap Fan Speed Speed Tap CFM Minus (-) 500* A Normal 500* Plus(+) 500* Minus (-) 550 B Normal 611 Plus(+) 672 Minus (-) 709 C Normal 787 Plus(+) 866 Minus (-) 912 D Normal 1,013 Plus(+) 1,114

* Motor CFM maximum

AUTO-COMFORT MODE During Auto-Comfort mode, the furnace ramps up to 50% of the demand for half a minute. It then ramps to 82% of the full cooling demand airflow and operates there for approximately 7½ minutes. The motor then steps up to the full demand airflow. This mode spends a half minute at 50% airflow

STANDARD ALTITUDE INSTALLATIONS Manifold Pressure High Stage Low Stage

Pressure Switch Change

Gas

Altitude

Kit

Orifice

Natural

0-7000 Changeover

None

#43

3.5” W.C.

1.9” W.C.

None

Propane

0-7000

LPM-03B & LPM-05

#55

10.0: W.C.

6.0” W.C.

None

• For installation in Canada, gas furnaces are certified only to 4,500 ft. • For GCVA installations above 7,000 ft., please refer to your Goodman distributor for required kit(s).

10

www.goodmanmfg.com

SS-GMV95

PRODUCT SPECIFICATIONS

GCV9 HEATING SPEEDS GCV90704CXA (Rise Range: 30 - 60°F) Heating Speed Tap

Adjust Tap Minus (-) Normal Plus(+) Minus (-) Normal Plus(+) Minus (-) Normal Plus(+) Minus (-) Normal Plus(+)

A

B

C

D

Low-Stage High-Stage Rise CFM CFM 747 830 913 824 915 1,007 900 1,000 1,100 978 1,085 1,194

1,076 1,195 1,315 1,186 1,318 1,449 1,296 1,440 1,584 1,408 1,562 1,719

56 50 46 51 46 42 47 42 38 43 39 35

GCV90905DXA (Rise Range: 30 - 60°F) Heating Speed Tap

A

B

C GCV91155DXA (Rise Range: 30 - 60°F) Heating Speed Tap

A

B

C

D

Adjust Tap Minus (-) Normal Plus(+) Minus (-) Normal Plus(+) Minus (-) Normal Plus(+) Minus (-) Normal Plus(+)

Low-Stage High-Stage Rise CFM CFM 1,093 1,214 1,335 1,106 1,229 1,352 1,166 1,296 1,426 1,172 1,302 1,432

1,583 1,759 1,935 1,612 1,791 1,970 1,654 1,838 2,022 1,690 1,878 2,066

D

Adjust Tap Minus (-) Normal Plus(+) Minus (-) Normal Plus(+) Minus (-) Normal Plus(+) Minus (-) Normal Plus(+)

Low-Stage High-Stage Rise CFM CFM 999 1,110 1,221 1,067 1,185 1,303 1,134 1,260 1,386 1,202 1,335 1,469

1,439 1,598 1,758 1,536 1,706 1,876 1,633 1,814 1,996 1,730 1,922 2,115

56 50 46 52 47 43 49 44 40 46 42 38

63 56 51 61 55 50 60 54 49 59 53 48

Notes: • These charts are for furnaces installed at 0 - 2000 feet. At higher altitudes, a properly derated unit will have the same temperature rise at a particular CFM, while the ESP at that CFM will be lower. • The installation must be adjusted to obtain a temperature rise within the range listed on the furnace nameplate. • Do not operate above .5” w.c. ESP in heating mode. • Propane gas installations will have a High Stage rise approximately 4° lower than shown in above table.

SS-GMV95

www.goodmanmfg.com

11

PRODUCT SPECIFICATIONS

GCV9 BLOWER PERFORMANCE

12

www.goodmanmfg.com

SS-GMV95

PRODUCT SPECIFICATIONS

GMV95/ GCV9 WIRING DIAGRAM TO

ID BLOWER TWO-STAGE PRESSURE SWITCH ASSEMBLY HIGH FIRE PRESS. SWITCH

C NO

C

2

PM

1

RD WH

TWO STAGE GAS VALVE

VT

3

N

BR

WH-5 DISCONNECT

FLAME SENSOR

C

GY

GY NO

TO 115VAC/ 1Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE

C

FRONT COVER PRESSURE SWITCH

NO

L

WARNING:

OR BU

BU

PK

LOW FIRE PRESS. SWITCH

24V HUM.

BU

RD

AUTO RESET PRIMARY LIMIT CONTROL

VT

2

RD

1

BK

SWITCH JUNCTION BOX

115kBTU MODELS INDUCTOR COIL 70kBTU,90kBTU, ONLY

GND

BURNER COMPARTMENT BLOWER COMPARTMENT

DISCONNECT

DOOR

INDUCED DRAFT BLOWER

GN

WH

VT

3

N

GND

DISCONNECT POWER MUST BE PROPERLY BEFORE SERVICING. WIRING TO UNIT POLARIZED AND GROUNDED.

CHASSIS GROUND

MANUAL RESET ROLLOUT LIMIT CONTROLS (SINGLE CONTROL ON 45 kBTU)

WARNING:DISCONNECT PROPERLY POLARIZED SERVICING. WIRING TO UNIT MUST BE AND GROUNDED. POWER BEFORE

INDOOR AIR CIRCULATOR BLWR

VT

GND

YL

TWIN/ DEHUM

W2

R

W1

G

B/C

Y

YLO

O

RD

PK BK

10

11

12

7

8

9

4

5

6

BU GY

LINE-N

EAC-H

IND HI

HUM-N

HUM-H HUMIDIFIER

WH

GY

IGN-H

IGN-N

RD

OR

HOT SURFACE IGNITER FP (3)

BU

3

2

IND-N

ID BLWR IND LO

BR 1

EAC-N

ELECTRONIC AIR CLEANER

INTEGRATED CONTROL MODULE

FUSE

WH

INTEGRATED CONTROL MODULE

VT

24 V THERMOSTAT CONNECTIONS

BR

PK

GY

24V HUM.

24 V 3A

LINE-H

YL

MANUAL RESET AUXILIARY LIMIT CONTROL

VT

FLAME SENSOR

YL GN

XFMR-H

XFMR-N

115 VAC

OR VT

T-STAT SELECTOR

2

HEAT OFF DELAY DIP SWITCHES

PK 1 2

4

WH DIAGNOSTIC LED

GY 24 VAC 115 VAC

5

XFMR

HUM

40VA TRANSFORMER

BK

MANUALRESETAUXILIARYLIMIT CONTROLS W1

HLO (11) MANUAL RESETROLLOUT LIMIT CONTROL(S)

YLO

HL1 (6) W2

Y

TO MICRO

WH

WH

BK

BK BK

WH GND

PK

STEADY ON = NORMAL OPERATION

LOW VOLTAGE (24V)

1 FLASH = SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED)

2

2 FLASHES = LOW FIRE PRESSURE SWITCH STUCK CLOSED

3

3 FLASHES = LOW FIRE PRESSURE SWITCH STUCK OPEN

4

4 FLASHES = THERMAL PROTECTIVE DEVICE OPEN

6

5 FLASHES = FLAME SENSED WITH GAS VALVE DE-ENERGIZED

JUNCTION

7

7 FLASHES = LOW FLAME SENSE SIGNAL

TERMINAL

8

8 FLASHES = CHECK IGNITER OR IMPROPER GROUNDING

9

9 FLASHES = HIGH FIRE PRESSURE SWITCH STUCK OPEN

C

CONTINUOUS FLASHES = 115 VOLT AC POWER REVERSED

SWITCH (TEMP.)

INTERNAL TO INTEGRATED CONTROL

WH WHITE

BK BLACK

RD RED

IGNITER SWITCH (PRESS.)

PLUG CONNECTION

NOTES:

GY GRAY

FIELD SPLICE

HI VOLTAGE FIELD

1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS.

BU BLUE

FIELD GND

HI VOLTAGE (115V)

PK PINK

VT VIOLET

EQUIPMENT GND

LOW VOLTAGE FIELD

BR BROWN

OR ORANGE

GND

TR (9)

C GAS VALVE

INTEGRATED CONTROL MODULE

1

GN GREEN

HIGH FIRE PRESSURE SWITCH

MVC (8)

GND (10) BLOWER COMPARTMENT DOOR SWITCH (OPEN WHEN DOOR OPEN)

HI

C

PS2 (2)

GN INDUCTOR COIL 70kBTU,90kBTU, 115kBTU MODELS ONLY

COLOR CODES: YL YELLOW

NO

MVH (1)

24V HUMIDIFIER

BK

PM

C 6 5

4 3 2 1

LOW FIRE PRESSURE SWITCH

NO

MVL(7)

WH WH

5

C NO

FRONT COVER PRESSURE SWITCH C

16 WIRE ECM MTR HARNESS

24V HUM.

PS1 (12) G

NEUTRAL

HOT

CIRCULATOR BLOWER

0

3

BK LINE

PARK

COOL

EAC

HI HEAT

LO HEAT

TWO-STAGE INTEGRATED CONTROL MODULE

OR

AUTORESET PRIMARYLIMIT CONTROL

24 VAC

FUSE 3 A

4

9 CIRCUIT CONNECTOR

3

TH (5)

R

1

24V THERMOSTAT CONNECTIONS

BK RD WH

5 CIRCUIT CONNNECTOR

RD

40 VA TRANSFORMER

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

HI

L

BK -1

WARNING

1

2 CIRCUIT CONNECTOR

YL

2

OR

115 VAC/ 1Ø /60 HZ

POWER SUPPLY WITH PROTECTION DEVICE OVERCURRENT

JUNCTION BOX

HOT SURFACE IGNITER

GND

OVERCURRENT PROT. DEVICE

2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY. 4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES.

22314701 REV.00

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring schematic. SS-GMV95

www.goodmanmfg.com

13

US

S1

3 2 1

OFF

87 4321

87 4321

EAC

TWO HUM

LINE

www.goodmanmfg.com XFMR HUM

COOL

HI HEAT

LO HEAT

WH

OR

GY

BK

WH

WH

BK

BK

WH

OR

GY

BK WH

9 CIRCUIT CONNECTOR TO MAIN HARNESS

PIN 9

PIN 8

PIN 7

PIN 6

PIN 5

PIN 4

PIN 3

PIN 2

PIN 1

VT

TO ECM BLWR MOTOR

PK

GROUND TO SCROLL HOUSING

GN

PIN 1

YL

ECM BLOWER MOTOR

PK

AUXILIARY LIMITS (SIDES OF BLOWER HOUSING)

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

PARK

LOAD

LINE

WH

XFMR

TRANSFORMER

BK

NEUTRAL

CIRC

BK

CUT FOR DEHUM

EAC

HOT

W R

Intell-Ignition

S3

ON

OFF

LINE

WARNING

C

ON

TSTAT

S4

PIN 4

CFM

PIN 5

14 PIN 2

SINGLE

PIN 3

INTEGRATED CONTROL MODULE

INDUCTOR COIL (GUVA070,090,115 MODELS ONLY)

PRODUCT SPECIFICATIONS

GMV95/ GCV9 BLOWER ASSEMBLY SCHEMATIC

This schematic is for reference only. Not all wiring is as shown above. Refer to the appropriate wiring diagram for the unit being serviced.

SS-GMV95

SS-GMV95

www.goodmanmfg.com

IGNN

1M

.0005

IGNITOR

FP

FLAME SENSOR PROBE

LINE NEU

120 VAC

LINE HOT

IGN

K7

LOW HEAT

K1

C

COOL PARK

H1

P M

K6

W8

MV MVL COM

2 STAGE GAS VALVE

GND

Q22

K2

HIGH HEAT

CIRCULATOR BLOWER

PS1

2ND STAGE PRESSURE SWITCH

PS2

CIRC. NEU

HIGH LIMIT

HLO

EAC NEU

1ST STAGE PRESSURE SWITCH

ROLLOUT SWITCH

EAC

ELECTRONIC AIR CLEANER

K3

IND HI

AUX LIMIT

K8a

IND LO

HLI

IND NEU

INDUCER

MVH

K8b

HUM

HUMIDIFIER

HUMN

Y G W2 W1

W2 W1

R

3 AMP AUTOMOTIVE FUSE

MATE WITH AMP 1-480708-0 USING SOCKETS 350550-1

THERMOSTAT

24 V.A.C.

G

Y

B/C

TR

XFMRN

XFMR

TH

R

PRODUCT SPECIFICATIONS

GMV95/ GCV9 SCHEMATICS (CONT.)

WR 50V61-289 INTEGRATED IGNITION CONTROL

This schematic is for reference only. Not all wiring is as shown above. Refer to the appropriate wiring diagram for the unit being serviced.

15

PRODUCT SPECIFICATIONS

ACCESSORIES Model

GCV9 GCV9 GCV9 GMV95 GMV95 GMV95 GMV95 0453BXB 0704CXB 0905DXB 1155DXB 0704CXB 0905DXB 1155DXB

Description

LPM-03B

LP Conversion Kit (Gas Valve)

1

1

1

1

1

1

LPM-05

LP Conversion Kit (Springs & Orifice)

1

1

1

1

1

1

GSAS

Electronic Air Cleaners (-10, -11, -12 or -18)













GMU

Media Air Cleaners (1620, 2020, 1625 or 2025)





















2

2 2

2

2

2

2

2





DEHUM1

Dehumidistat





HAPS28

High-Altitude Pressure Switch Kit

2

2

HAPS29

High-Altitude Pressure Switch Kit

HAPS 31

High-Altitude Pressure Switch Kit

HALP11

High-Altitude Propane Gas Kit

HALP 13

High-Altitude Propane Gas Kit

HANG 13

2

2

2

2

High-Altitude Natural Gas Kit

3

3

3

3

HANG 14

High-Altitude Natural Gas Kit

4

4

4

4

HANG 16

High-Altitude Natural Gas Kit

EFR01

External Filter Rack









DCVK-20

Horizontal/Vertical Concentric Vent Kit (2”)







DCVK-30

Horizontal/Vertical Concentric Vent Kit (3”)







CFB21

Downflow Floor Base

CFB24

Downflow Floor Base

017K00000S

Flush-mount vent kit

√ √





√ √ √











1– All Models up to 7,000’ 2– 7,001’ to 11,000’ 3– 7,001’ to 9,000’ 4– 9,001’ to 11,000’ Note: All installations above 7,000’ require a pressure switch change. For installation in Canada, gas furnaces are certified only to 4,500’.

THERMOSTATS A two-stage thermostat should be used with the GMV95/GCV9 furnaces. Two-stage thermostats control which firing rate is used depending on the temperature difference between the set point and the room temperature. A properly used two-stage thermostat and furnace will maintain a much tighter Model Description control of temperature than a conventional single-stage thermostat and furnace. Two-stage furnaces have “W1” CHT90-120 Cooling/Heating, Mechanical and “W2” terminals. If the thermostat has “Y1” and “Y2” CH70TG Cooling/Heating, Digital, Non-programmable cooling connections and a single-stage cooling system is used, connect “Y” on the furnace control to “Y1” on CHSATG Cooling/Heating, Mechanical the thermostat. The table below describes two-stage H20TWR Heating Only, Mechanical thermostats that have been configured for use with this furnace.

Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2008 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.

16

www.goodmanmfg.com

SS-GMV95