GEL Battery - Amazon Simple Storage Service (S3)

Report 4 Downloads 42 Views
UPG No. 40703

GEL Battery Celled Silica technology for superior performance. Valve regulated, spill proof construction performance. Valve regulated, spill proof construction allows safe operation in any position. Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. r ecognized under file number MH 20567.

UBGC2 Maintenance-Free

Specification Nominal Voltage Nominal Capacity 20-hr. (10A) 10-hr. (18.6A) 5-hr. (34A) 1-hr. (120A) Approximate Weight Internal Resistance (approx.) Shelf Life (% of normal capacity at 77º F (25º C)) 3 Months 6 Months 91% 82% Temperature Dependancy of Capacity 104º F 77º F 32º F 102% 100% 85%

6 volts 77º F (25º C) 200 Ah 186 Ah 170 Ah 120 Ah 62.39 lbs (28.3 kgs) 4Ÿ Charge Method (Constant Voltage) Cycle Use (Repeating Use) Initial Current 40 A or smaller Control Voltage 7.1 - 7.2 V Float Use Control Voltage 6.6- 6.7V

12 Months 64% (20 hour rate) 5º F 65%

Physical Dimensions: in (mm) Terminals L: 10.24in (260 mm) W: 7.09in (180 mm) H: 9.72in (247 mm) TH: 10.67in (271 mm) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice.

For product and purchasing inquiries contact:

www.ecodirect.com

Cell voltage ( V/Cell )

Discharge Time vs. Discharge Current

Discharge Characteristics

( Hour )

( Minute ) Discharge time

www.upgi.com 1720 Hayden Drive

Carrollton, Texas 75006

VR072911

P 469.892.1122

T 866.892.1122

F 469.892.1123

[email protected]

UPG No. 40703

UBGC2 Maintenance-Free

Battery Charging Characteristics for Cyclic Use

Battery Charging Characteristics for Standby Use

Cell charge voltage

Cell charge voltage ( V/Cell )

1 Discharge 100 % (0.1CA*10h) -- 50 % (0.1CA*5h) 2 Constant voltage charging Charge voltage : 2.45V/cell Charge current : 0.3CA (77 ) 3 Temperature : 25

Charge current (CA)

Charge volume

Charge volume (%)

Cell charge voltage ( V/Cell )

Charge current (CA)

Charge volume (%)

Cell charge voltage

Charge volume

1 Discharge 100 % (0.1CA*10h) --50 % (0.1CA*5h) 2 Constant voltage charging Charge voltage : 2.275V/cell Charge current : 0.1CA (77 ) 3 Temperature : 25

Charge current

Charge current Charge Time (hr)

Charge Time (hr)

Shelf Life & Storage

Cycle Life vs Depth of Discharge

Open Circuit Voltage vs Residual Capacity

Effect of Temperature on Capacity

Charge Current & Final Discharge Voltage Application

Charge Voltage(V/Cell) Set Point

Allowable Range

Cycle Use

Temperature 25 (77 )

2.40

2.36~2.40

Standby

25 (77 )

2.23

2.20~2.23

Max.Charge Current

Final Discharge Voltage V/Cell

1.75

1.70

1.60

1.30

0.20C

Discharge Current(A)

0.2C>(A)

0.2C