All BQ/BQH/HBQ circuit breakers are supplied with load side lugs. If line side lugs are required, add suffix “L” to catalog number. Consult Siemens for any additional charge. All standard circuit breakers are calibrated for 40°C maximum ambient application.
Catalog Number Field/Factory Installed add suffix...00S01■ Factory add suffix...00S07■ Factory add suffix...01■ Factory ECPLD1 Field ECPLD2 Field ECQLD3 (Pkg of 10) Field ECHBD1 Field
Listed for use with 60/75° wire through 125 amps, HACR rated. 1A and 1B contacts. UL Listed for use on 3-phase grounded “B” systems — 10,000 for this application.
Siemens Industry, Inc. Industrial Controls Catalog
Lugs-For Use with BQ, BQH, HBQ Circuit Breaker Amp. Rtg. Line Side
Cab. Per Lug
10–40
1 1 1 1
#16–#6 Cu #12–#6 Al #8–#1 Cu #6–#1/0 Al
2 1 1 1 1 1 1 1 1 1 1 1 1
#16 Cu #14–#10 Cu #12–#10 Al #14–#6 Cu #12–#10 Al #8–#6 Cu #8–#4 Al #8–#4 Cu #8–#2 Al #4–#1/0 Cu #2–#1/0 Al #2–#1/0 Cu #1/0–#2/0 Al
45–100 Load Side 10 15–20 25–35 40–50 55–70 80–100 110–125
Lug Wire Range AWG
Catalog Number TC1Q1 TA1Q1
Connectors are Supplied with Circuit Breaker
are UL Listed for 60°/75°C conductors. Also CSA Listed. has steel construction.
17/10
Amperes
L
D1
D2
BQ, BQH BQ, BQH HBQ BQXD
15–50 55–125 15–125 15–60
33⁄4 4 4 41⁄2
23⁄8 23⁄8 23⁄8 23⁄8
3 3 3 3
Protects against accidental contact with lugs–1 per lug. Fits line and load end.
■ Built to order. Allow 2–3 weeks for delivery.
Connector
Dimensions (inches)
Breaker Type
Finger Safe Terminal Shield
For inches / millimeters conversion, see Application Data section. Terminals
List Price $ (Qty. 6)
Catalog Number
Qty
BQFS2
2
BQFS1K
1000
List Price $ each
Enclosures Type
Catalog Number
1
EB3100S
3R
WB3100
Surface
mounted indoor. If flush mounting is required, replace suffix “S” in catalog number with suffix “F”. Discount Schedule B. Does not include circuit breaker. Order circuit breaker separately. Neutral included in enclosure. Enclosure will not accept circuit breakers with shunt trips or auxiliary switches installed.
Product Category: MCCB
List Price $
Type
BQXD uses TA1Q1 or TC1Q1 lugs on line side of circuit breaker.
Accessories pages 17/103 to 17/108
Siemens Industry, Inc. Industrial Controls Catalog