Metal GroundinG and BondinG Hubbell's full line of grounding and bonding products will protect and secure active equipment from harmful electrical interference. These products provide the best performance and are highly adaptable to fit within numerous building applications.
P1
www.hubbell-premise.com
Product
PaGe
telecommunication room GroundinG . . . . . . . . . . . . . . . . . . . . . P7 data center GroundinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P9 Structural GroundinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P11
BondinG
Service entrance GroundinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . P5
and
GroundinG and BondinG network . . . . . . . . . . . . . . . . . . . . . . . . P3
M e ta l G r o u n d i n G
GroundinG and BondinG
rack and caBinet GroundinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . P13 Power StriP GroundinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P15 ladder rack GroundinG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P17 GroundinG acceSSorieS and toolS . . . . . . . . . . . . . . . . . . . . . . . . P18
www.hubbell-premise.com
P2
GroundinG
and
BondinG network Grounding and Bonding System The grounding network in any building is responsible for directing electricity, static noise and built up charges to an outside discharge away from people and equipment. The grounding products featured here are designed around the ANSI-J-STD-607-B, Commercial Building Grounding (Earthing) and Bonding requirements for telecommunications. This standard specifies the requirements for a uniform telecommunications grounding and bonding infrastructure that shall be followed within commercial buildings where telecommunications equipment will be installed.
According to the ANSI-J-STD-607-B Standard*, TBB Conductor size is directly related to the length of ground wire run. See the chart below for selecting the appropriate AWG size of wire.
TBB Conductor Size vs. Length TBB/GE Linear Length Feet (m)
TBB/GE Size (AWG)
Less than 13' (4)
6
14–20' (4 -6)
4
21–26' (6–8)
3
27–33' (8–10)
2
34–41' (10–13)
1
42–52' (13–16)
1/0
53–66' (16–20)
2/0
37–84' (20–26)
3/0
85–105' (26–32)
4/0
*Reference ANSI-J-STD-607-B for more information.
P3
www.hubbell-premise.com
and
Bonding Network
Service Entry The service entry location houses the last destination within the building before an electrical current leaves the building. The Telecommunications Main Grounding Busbar (TMGB) connects the external grounding rod to Telecommunications Bonding Backbone (TBB) located throughout the building.
M e ta l G r o u n d i n g
Grounding
and
Bonding
Telecommunications Room The grounding products in this section focus grounding noise that travels along cables. These rooms are located throughout the building, there can be multiple rooms per floor in many different sizes.
Data Center The grounding and bonding network in these rooms will ground the active equipment to the infrastructure. There is a significant need for grounding in this room to prevent equipment failure and increase overall equipment performance.
www.hubbell-premise.com
P4
Service entrance GroundinG
Flexibility
Ground wire connectors allow for building and expanding the grounding system.
Quality
Telecommunication Main Grounding Busbar (TMGB) connects the backbone pathways to the earth ground rod.
The service entrance is where the unwanted electrical charge leaves the structure. These products are generally larger and heavier for the environment in which they are located.
Robust
Pipe clamps allow for grounding to the building plumbing system.
Strong Background in Grounding (BURNDY®)
Full Product Line Offering to Ground Every Component
High Strength Products for the Rugged Service Area
Safe for the Environment
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P5
www.hubbell-premise.com
Compression Lugs Single Hole Lug 45 Degree 90 Degree
Straight
Double Hole Lug 45 Degree 90 Degree
6 AWG
HGBL06S
HGBL06S45
HGBL06S90
HGBL06D
HGBL06D45
HGBL06D90
4 AWG
HGBL04S
HGBL04S45
HGBL04S90
HGBL04D
HGBL04D45
HGBL04D90
2 AWG
HGBL02S
HGBL02S45
HGBL02S90
HGBL02D
HGBL02D45
HGBL02D90
1 AWG
HGBL01S
–
–
HGBL01D
–
–
1/0 AWG
HGBL10S
–
–
HGBL10D
–
–
Bonding
Straight
and
Wire Size
M e ta l G r o u n d i n g
Service Entrance Grounding
TMGB Telecommunications Main Grounding Busbar Dimensions Inches (mm) 0.25 x 4 x 16" (6 x 102 x 406)
Hole1 Qty 16
Hole1 Size Inches (mm) 0.44" (11)
Hole2 Qty 8
Hole2 Size Inches (mm) 0.44" (11)
Catalog No.
0.25 x 4 x 16" (6 x 102 x 406)
16
0.44" (11)
16
0.24" (6)
HBBB14416H
0.25 x 4 x 20" (6 x 102 x 508)
34
0.44" (11)
34
0.25" (6)
HBBB14420J
Ground Wire Connectors Wire Min.
HBBB14416G
Bonding Connector
Wire Max.
Catalog No.
8 AWG
1/0 AWG
HGBKSA10
6 AWG
2/0 AWG
HGBKVSW26
Contents: 100 SHIELDBOND connectors, 1 field installation tool kit
Catalog No.
BC285SB100
Braided Jumper
Pipe Grounding Clamps Pipe Dia.
Ground Wire Min.
Ground Wire Max.
Catalog No.
Length Inches (mm)
Width Inches (mm)
Hole Diameter Inches (mm)
Catalog No.
1"
4 AWG
2/0 AWG
HGBGAR1526
12" (305)
0.94" (24)
0.375" (10)
HGBBD12
1.5"
4 AWG
2/0 AWG
HGBGAR1626
18" (457)
0.94" (24)
0.375" (10)
HGBBD18
2"
4 AWG
2/0 AWG
HGBGAR1726
24" (610)
0.94" (24)
0.375" (10)
HGBBD24
2.5"
4 AWG
2/0 AWG
HGBGAR1826
3"
4 AWG
2/0 AWG
HGBGAR1926
3.5"
4 AWG
2/0 AWG
HGBGAR2026
www.hubbell-premise.com
P6
telecoMMunicationS rooM GroundinG
User Friendly
Grounding terminals are frequently used for creating connections on ladder rack.
Intuitive
Grounding strips are easily installed on racks or inside of cabinets.
The telecommunications rooms are located throughout the building and can be as small as a closet to a fully populated room. The focus in these rooms is to eliminate electrical static the will travel on cables or generated by equipment.
Configurability
Grounding kits are user configurable to meet the many needs of compression lug type and wire length.
Constructed with Hubbell Premium Products
Multiple Bracket Options to Suit Every Application
High Strength Products for the Rugged Service Area
Increases Safety
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P7
www.hubbell-premise.com
Compression Lugs Single Hole Lug 45 Degree
90 Degree
Straight
Double Hole Lug 45 Degree 90 Degree
6 AWG
HGBL06S
HGBL06S45
HGBL06S90
HGBL06D
HGBL06D45
HGBL06D90
4 AWG
HGBL04S
HGBL04S45
HGBL04S90
HGBL04D
HGBL04D45
HGBL04D90
2 AWG
HGBL02S
HGBL02S45
HGBL02S90
HGBL02D
HGBL02D45
HGBL02D90
1 AWG
HGBL01S
–
–
HGBL01D
–
–
1/0 AWG
HGBL10S
–
–
HGBL10D
–
–
Grounding Kit Configurator Contents: green coated #6 AWG copper wire, selected lugs, and the appropriate number of #12-24 and M6 screws S = Single lug, 1 #12-24 and M6 screw D = Double lug, 2 #12-24 and M6 screws DF = Double 45 lug, 2 #12-24 and M6 screws DN = Double 90 lug, 2 #12-24 and M6 screws Base Length Catalog No. Lug 1 In. (mm) Lug 2
HGRKT
S
10" (254)
S
D
20" (508)
D
Bonding
Straight
and
Wire Size
M e ta l G r o u n d i n g
Telecommunications Room Grounding
Bonding Connector Contents: 100 SHIELDBOND connectors, 1 field installation tool kit
Catalog No.
BC285SB100
Ground Wire Connectors
30" (762)
DF
144" (3658)
DN
Example: HGRKTS20DN: grounding kit with single lug, 20" of #6 AWG wire, double 90 degree lug, 3 #12-24 and M6 screws.
Wire Min
Wire Max
Catalog No.
8 AWG
1/0 AWG
HGBKSA10
6 AWG
2/0 AWG
HGBKVSW26
Grounding Terminals Catalog No.
HGBKA6U
HGBBGBL4
HGBKLU35
HGBCL501
Description
Al Standoff
Al Side Mount
Cop Standoff
Cop Side Mount
Material
Aluminum
Aluminum
Copper
Copper
Mounting Hole I.D.
0.25" (6)
0.22" (6)
0.19"(5)
0.22" (6)
Wire Diameter Min.
14 AWG
14 AWG
14 AWG
14 AWG
Wire Diameter Max.
6 AWG
4 AWG
6 AWG
4 AWG
TGB Telecommunications Grounding Busbar Dimensions Inches (mm)
Hole1 Qty
Hole1 Size
Hole2 Qty
Hole2 Size
0.25 x 2 x 10" (6 x 51 x 254)
16
0.28" (7)
–
–
HBBB14210A
0.25 x 2 x 24" (6 x 51 x 610)
36
0.28" (7)
–
–
HBBB14224B
Dimensions Inches (mm)
Hole1 Qty
Hole1 Size
Hole2 Qty
Hole2 Size
Catalog No.
0.25 x 0.75 x 19" (6 x 19 x 483)
8
#6-32
4
0.25" (6)
HBBBHR19
0.25 x 0.63 x 36" (6 x 16 x 914)
16
1/4-20
3
0.25 x 0.5" (6 x 13) Slot
HBBBVR36
Catalog No.
Grounding Bar
www.hubbell-premise.com
P8
data center GroundinG
Protection
Grounding kits are available and user configurable to meet many needs and protect active equipment.
Options
Telecommunication Busbars (TBB) are available in convenient sizes to meet the unique requirements of each data center.
Grounding and bonding in the data center is very important when protecting active equipment from dangerous electrical charges. The focus in this room is to safely ground charges and move the charge safely to the service entrance.
Secure
Connecting racks and cabinets to the raised floor structure provides a secure solution.
Strong Background in Grounding (BURNDY®)
Multiple Bracket Options to Suit Every Application
High Performance Products to Ensure Protection
Safe for the Environment
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P9
www.hubbell-premise.com
Compression Lugs Single Hole Lug 45 Degree
90 Degree
Straight
Double Hole Lug 45 Degree 90 Degree
6 AWG
HGBL06S
HGBL06S45
HGBL06S90
HGBL06D
HGBL06D45
HGBL06D90
4 AWG
HGBL04S
HGBL04S45
HGBL04S90
HGBL04D
HGBL04D45
HGBL04D90
2 AWG
HGBL02S
HGBL02S45
HGBL02S90
HGBL02D
HGBL02D45
HGBL02D90
1 AWG
HGBL01S
–
–
HGBL01D
–
–
1/0 AWG
HGBL10S
–
–
HGBL10D
–
–
Grounding Kit Configurator
Bonding Connector
Contents: green coated #6 AWG copper wire, selected lugs, and the appropriate number of #12-24 and M6 screws
Contents: 100 SHIELDBOND connectors, 1 field installation tool kit
S = Single lug, 1 #12-24 and M6 screw D = Double lug, 2 #12-24 and M6 screws DF = Double 45 lug, 2 #12-24 and M6 screws DN = Double 90 lug, 2 #12-24 and M6 screws
Bonding
Straight
and
Wire Size
M e ta l G r o u n d i n g
Data Center Grounding
Catalog No.
BC285SB100
Base Catalog No.
Lug 1
Length In. (mm)
Lug 2
HGRKT
S
10" (254)
S
D
20" (508)
D
Wire Min.
Wire Max.
Catalog No.
30" (762)
DF
8 AWG
1/0 AWG
HGBKSA10
144" (3658)
DN
6 AWG
2/0 AWG
HGBKVSW26
Ground Wire Connectors
Example: HGRKTS20DN: grounding kit with single lug, 20" of #6 AWG wire, double 90 degree lug, 3 #12-24 and M6 screws.
TGB Telecommunications Grounding Busbar Dimensions Inches (mm)
Hole1 Qty
Hole1 Size
Hole2 Qty
Hole2 Size
0.25 x 2 x 10" (6 x 51 x 254)
16
0.28" (7)
–
–
HBBB14210A
0.25 x 2 x 24" (6 x 51 x 610)
36
0.28" (7)
–
–
HBBB14224B
Dimensions Inches (mm)
Hole1 Qty
Hole1 Size
Hole2 Qty
Hole2 Size
Catalog No.
0.25 x 0.75 x 19" (6 x 19 x 483)
8
#6-32
4
0.25" (6)
HBBBHR19
0.25 x 0.63 x 36" (6 x 16 x 914)
16
1/4-20
3
0.25 x 0.5" (6 x 13) Slot
HBBBVR36
Catalog No.
Grounding Bar
www.hubbell-premise.com
P10
Structural GroundinG
Strength
Ground wire connectors allow for building and expanding the grounding system.
Ease of Use
Our raised floor grounding products work with square and round profiles of raised floor structures.
Structural grounding contains the products needed for grounding the stationary and structural components located within the telecommunications rooms and data center.
Strong Background in Construction and Electrical Products
Full Line of Grounding Solutions
High Strength Products for the Rugged Structural Needs
Ensure Building Safety
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P11
www.hubbell-premise.com
Robust
Grounding braids are available in many different configurations and withstand an abusive environment.
M e ta l G r o u n d i n g
Structural Grounding
Raised Floor Clamps HGBGRF4C3
HGBGP1526G1
0.75" (19) – 1.5" (38)
0.75" (19) – 1" (25)
1" (25) – 1.25" (32)
Pedestal Type
Round or Square
Round or Square
Round
Ground Wire Min.
6 AWG
8 AWG
4 AWG
Ground Wire Max.
4/0 AWG
2 AWG
2/0 AWG
Ground Wire Connectors
Bonding
HGBGXP1828RF
Pedestal Size
and
Catalog No.
Bonding Connector
Wire Min.
Wire Max.
Catalog No.
8 AWG
1/0 AWG
HGBKSA10
6 AWG
2/0 AWG
HGBKVSW26
Contents: 100 SHIELDBOND connectors, 1 field installation tool kit
Catalog No.
BC285SB100
Braided Jumper Length In. (mm)
Width In. (mm)
Hole Diameter In. (mm)
Catalog No.
12" (305)
0.94" (24)
0.375" (10)
HGBBD12
18" (457)
0.94" (24)
0.375" (10)
HGBBD18
24" (610)
0.94" (24)
0.375" (10)
HGBBD24
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
www.hubbell-premise.com
P12
r ack
and
caBinet GroundinG
Flexibility
Grounding strips are easily installed on racks or inside of cabinets that have TIA-310-D, 19" spacing.
Configurability
Grounding kits are available for equipment as well as cabinet doors.
Safely and Securely ground active equipment to the Racks and Cabinets while grounding these to the grounding backbone system.
Installation Ease
Grounding braids are available in many different configurations and withstand an abusive environment.
Knowledge of Grounding Solutions (BURNDY®)
Multiple Mounting Options to Suit Every Application
High Performance Products to Ensure Protection
Safe for Active Equipment
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P13
www.hubbell-premise.com
and
Cabinet Grounding
Grounding Terminals Catalog No.
HGBKA6U
HGBBGBL4
HGBKLU35
HGBCL501
Description
Al Standoff
Al Side Mount
Cop Standoff
Cop Side Mount
Aluminum
Aluminum
Copper
Copper
0.25" (6)
0.22" (6)
0.19"(5)
0.22" (6)
Wire Diameter Min.
14 AWG
14 AWG
14 AWG
14 AWG
Wire Diameter Max.
6 AWG
4 AWG
6 AWG
4 AWG
Bonding Connector
Contents: green coated #6 AWG copper wire, selected lugs, and the appropriate number of #12-24 and M6 screws
Contents: 100 SHIELDBOND connectors, 1 field installation tool kit
S = Single lug, 1 #12-24 and M6 screw D = Double lug, 2 #12-24 and M6 screws DF = Double 45 lug, 2 #12-24 and M6 screws DN = Double 90 lug, 2 #12-24 and M6 screws
Bonding
Grounding Kit Configurator
and
Material Mounting Hole I.D.
M e ta l G r o u n d i n g
R ack
Catalog No.
BC285SB100
Base Catalog No.
Lug 1
Length In. (mm)
Lug 2
HGRKT
S
10" (254)
S
D
20" (508)
D
Wire Min.
Wire Max.
Catalog No.
30" (762)
DF
8 AWG
1/0 AWG
HGBKSA10
144" (3658)
DN
6 AWG
2/0 AWG
HGBKVSW26
Ground Wire Connectors
Example: HGRKTS20DN: grounding kit with single lug, 20" of #6 AWG wire, double 90 degree lug, 3 #12-24 and M6 screws.
Grounding Bar Dimensions Inches (mm)
Hole1 Qty
Hole1 Size
Hole2 Qty
Hole2 Size
Catalog No.
0.25 x 0.75 x 19" (6 x 19 x 483) 8
#6-32
4
0.25" (6)
HBBBHR19
0.25 x 0.63 x 36" (6 x 16 x 914) 16
1/4-20
3
0.25 x 0.5" (6 x 13) Slot
HBBBVR36
Braided Jumper Length In. (mm)
Width In. (mm)
Hole Diameter In. (mm)
Catalog No.
12" (305)
0.94" (24)
0.375" (10)
HGBBD12
18" (457)
0.94" (24)
0.375" (10)
HGBBD18
24" (610)
0.94" (24)
0.375" (10)
HGBBD24
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
www.hubbell-premise.com
P14
Power StriP GroundinG
Ease of Use
Grounding strips are easily installed on racks or Inside of cabinets that have TIA-310-D, 19" spacing.
Configurability
Grounding kits are available for equipment as well as cabinet doors.
Proper grounding of the power strip will ensure electrical charges do not travel to the active equipment.
Robust
Grounding Braids are available in many different configurations and withstand an abusive environment.
Quality Manufacturing
Integrated with Premium Power Strips
Steady and Reliable Electrical Discharge
Increases Safety
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P15
www.hubbell-premise.com
Grounding Terminals Catalog No.
HGBKA6U
HGBBGBL4
HGBKLU35
HGBCL501
Description
Al Standoff
Al Side Mount
Cop Standoff
Cop Side Mount
Aluminum
Aluminum
Copper
Copper
0.25" (6)
0.22" (6)
0.19"(5)
0.22" (6)
Wire Diameter Min.
14 AWG
14 AWG
14 AWG
14 AWG
Wire Diameter Max.
6 AWG
4 AWG
6 AWG
4 AWG
Bonding Connector
Contents: green coated #6 AWG copper wire, selected lugs, and the appropriate number of #12-24 and M6 screws
Contents: 100 SHIELDBOND connectors, 1 field installation tool kit
S = Single lug, 1 #12-24 and M6 screw D = Double lug, 2 #12-24 and M6 screws DF = Double 45 lug, 2 #12-24 and M6 screws DN = Double 90 lug, 2 #12-24 and M6 screws Base Catalog No.
Lug 1
Length In. (mm)
Lug 2
HGRKT
S
10" (254)
S
D
20" (508)
D
30" (762)
DF
144" (3658)
DN
Catalog No.
Bonding
Grounding Kit Configurator
and
Material Mounting Hole I.D.
M e ta l G r o u n d i n g
Power Strip Grounding
BC285SB100
Example: HGRKTS20DN: grounding kit with single lug, 20" of #6 AWG wire, double 90 degree lug, 3 #12-24 and M6 screws.
Grounding Bar Dimensions Inches (mm)
Hole1 Qty
Hole1 Size
Hole2 Qty
Hole2 Size
Catalog No.
0.25 x 0.75 x 19" (6 x 19 x 483) 8
#6-32
4
0.25" (6)
HBBBHR19
0.25 x 0.63 x 36" (6 x 16 x 914) 16
1/4-20
3
0.25 x 0.5" (6 x 13) Slot
HBBBVR36
Braided Jumper Length In. (mm)
Width In. (mm)
Hole Diameter In. (mm)
Catalog No.
12" (305)
0.94" (24)
0.375" (10)
HGBBD12
18" (457)
0.94" (24)
0.375" (10)
HGBBD18
24" (610)
0.94" (24)
0.375" (10)
HGBBD24
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
www.hubbell-premise.com
P16
ladder r ack GroundinG
Ease of Use
Grounding terminals allow for any existing ladder rack to be grounded.
Grounding Kit Configurator Contents: green coated #6 AWG copper wire, selected lugs, and the appropriate number of #12-24 and M6 screws S = Single lug, 1 #12-24 and M6 screw D = Double lug, 2 #12-24 and M6 screws DF = Double 45 lug, 2 #12-24 and M6 screws DN = Double 90 lug, 2 #12-24 and M6 screws Base Catalog No.
Lug 1
Length In. (mm)
Lug 2
HGRKT
S
10" (254)
S
D
20" (508)
D
30" (762)
DF
144" (3658)
DN
Example: HGRKTS20DN: grounding kit with single lug, 20" of #6 AWG wire, double 90 degree lug, 3 #12-24 and M6 screws.
Grounding the ladder rack will help eliminate electrical signals that travel with cables.
Grounding Terminals Catalog No.
HGBKA6U
HGBBGBL4
HGBKLU35
HGBCL501
Description
Al Standoff
Al Side Mount
Cop Standoff
Cop Side Mount
Material
Aluminum
Aluminum
Copper
Copper
Mounting Hole I.D.
0.25" (6)
0.22" (6)
0.19"(5)
0.22" (6)
Wire Diameter Min
14 AWG
14 AWG
14 AWG
14 AWG
Wire Diameter Max
6 AWG
4 AWG
6 AWG
4 AWG
Strong Background in Grounding
The Solution for New or Existing Structures
High Quality Casting and Machined Components
Provide Safety for the Building
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
P17
www.hubbell-premise.com
and
Tools
PENETROX™ E
PENETROX A consists of a natural based vehicle in which zinc particles are suspended for aluminum-to-aluminum, aluminum-tocopper applications.
PENETROX E consists of a natural based vehicle in which copper particles are suspended for copper-to-copper applications.
HGBP8A
Catalog No.
HGBPENE8
Crimp Tool
Compression Tool Kit
Mechanical rotating crimp tool for aluminum lugs and splices from #8 - 4/0 AWG aluminum and copper conductors. Dies are integrated in the tool head and are rotated to the appropriate lug size.
Mechanical tool kit is a basic tool for crimping terminals ranging from 8 AWG to 4/0 AWG. Adjusting for the size of terminal is done my rotating a dial located on the tool head.
Catalog No.
HMRC840
Catalog No.
Bonding
Catalog No.
and
PENETROX™ A
M e ta l G r o u n d i n g
Grounding Accessories
HMY2911
Torque Wrench Torque wrench incorporates an easy-to-read scale measured in inch pounds (in-lb) that can be easily matched to the recommended torque of each of our mechanical connector products. (Sockets not included.) Description
Catalog No.
30-150 In
HBTW30150
150-750 In
HBTW150750
Note: Reference the ANSI-TIA-607-B Standard to ensure proper adherence to the standards.
www.hubbell-premise.com
P18