Intrinsically Safe Three Phase Duplex Control Panel - Amazon Simple ...

Report 20 Downloads 68 Views
Intrinsically Safe Three Phase Duplex Control Panel Installation and Operator’s Manual

IM 810, Rev. 0117

Intrinsically Safe WS Series® Duplex Control Panel

Panel Installation:

The WS Series® Duplex control panels will control two pumps in sewage, wastewater, and dewatering applications. See Water® duplex control panels come standard with a clear front NEMA 4X rated enclosure, four floats (stop, lead, lag, and high liquid alarm) IEC rated contactors, circuit breakers, and adjustable overloads. All panels are UL listed for the United States and Canada and come with a three year warranty.

1. Caution: To maintain the NEMA 4X rating, make all wiring connections with seal tight cable grips or conduit connections. 2. Determine mounting location for control panel. Mount panel using mounting feet supplied. 3. The control panel should not be mounted in an area that is subject to submersion. 4. Warning: Enclosure is to be mounted outside hazardous area. 5. Run pump cables and float cables through conduit. Make field connections as shown on wiring diagram. 6. Run power line conductor through conduit. Wire to terminals per enclosed schematic. Branch circuit protection to be provided by installer. 7. Float cables require separate conduit from power and pump cables. 8. Mount float switches at appropriate levels. Be sure that the floats have a free range of motion to prevent entanglement.

Models (Ratings): IS-WD3P-4-3021 (1.0-1.6 pump full load amps) IS-WD3P-4-3022 (1.6-2.5 pump full load amps) IS-WD3P-4-3023 (2.5-4.0 pump full load amps) IS-WD3P-4-3024 (4.0-6.3 pump full load amps) IS-WD3P-4-3025 (6.0-10.0 pump full load amps) IS-WD3P-4-3026 (9.0-14.0 pump full load amps) IS-WD3P-4-3027 (13.0-18.0 pump full load amps) IS-WD3P-4-3028 (17.0 -23.0 pump full load amps) IS-WD3P-4-3029 (20.0-25.0 pump full load amps) IS-WD3P-4-3030 (24.0-32.0 pump full load amps) Features: • • • • •

• • • • • •

Designed to Control Two 208/240/480VAC pumps in sewage applications Industrial Pump Control Panel that is UL 698A approved for Class 1, Groups A,B,C & D applications NEMA 4X enclosure: heavy duty polycarbonate with lockable latches Duplex provides pump rotation and high demand two pump operation Pump control visible features: pump hand-off-auto (H.O.A.) switches for pump #1 and pump #2, green pump run lights, red pump fault lights with reset button and green power on light Alarm visible features: red beacon alarm light, alarm test and silence buttons Alarm horn sounds at 85 decibels at 10’ Remote monitoring dry contacts: high liquid, pump #1 fault, pump #2 fault, pump #1 run, pump #2 run (normally open) Pump protection: motor protective switch included for both pumps (branch circuit protection, adjustable overload and disconnect), pump thermal cutout circuit Includes four narrow angle float switches with 20′ cords and mounting hardware Float status indicators (stop, lead, lag, high liquid)

1. All installations must be in accordance with the National Electrical Code, and any other applicable state and local electrical requirements.

Start up: 1. When the power is applied, the green power light located on the white front swing panel shall light. 2. The pump HOA switches shall be placed to the A (auto) position to ensure the pump will turn on from the commands of the floats. The pump can be tested or turned on manually if the HOA switch is held in the H (Hand-Manual) position. To test the alarm circuit, push the test button on the front panel, the audible alarm shall sound and the red beacon will light. Press the silence button to silence the alarm.

www.seewaterinc.com 951.487.8073 • 888.733.9283 [email protected] 22220 Opportunity Way, Suite 104 Riverside, CA 92518

Intrinsically Safe Three Phase Duplex Control Panel Additional Panel Options:

Warning:

LL - Low Level Alarm Circuit (optional)

Substitution of Components May Impair Intrinsic Safety. To prevent ignition of flammable or combustible atmospheres, disconnect power

Includes normally closed low level float switch. Alarm horn will sound and red beacon will light in the event of a low level. Comes with normally open low level dry contact. SF - Seal Failure Circuit (optional) The seal fail circuit will indicate when there is water in the pump chamber. The circuit is setup to work with a variety of pumps with a range of resistance sensitivity settings. AF - Alarm Flasher ET - Elapsed Timer Meter w/ LCD display & reset CC - Cycle Counter w/LCD display & reset LA - Lightning Secondary Surge Arrestor MD - Main Disconnect

Typical Installation for Duplex Control Panel A typical pump installation showing a stop float, lead pump on float, lag pump on float, and high liquid alarm float. All pump cords are connected to the wastewater control panel. On the models with three floats, the third float is lag pump operation and a high liquid alarm. On the models with four floats, the third float is lag pump operation and the fourth float is high liquid alarm. SEEWATER, Inc.

Wastewater/Sewage Duplex Panel PUMP # 1

HOA

PUMP ON

FAULT PUMP RESET

PUMP # 2

PUMP ON

HOA

FAULT

SEEWATER, Inc. Alarm System

Service:

SILENCE

Caution: Before checking electrical connections within the control or attempting to replace any components, turn off all branch circuits supplying power to the main control panel. Troubleshooting:

TEST

Conduit sized by end-user

Pump outlets

Alarm Circuit - HIGH LIQUID ALARM

To test the alarm light and buzzer, press the test button on the front panel. If either the light or buzzer do not indicate, replace the light bulb or buzzer with same type.

HIGH DEMAND TWO PUMP OPERATION

Control Board and Fuse If the power on light is not illuminating on the front panel, check the voltage at TS1-1 and TS1-2 with a voltage meter. The voltage should read 120VAC. If voltage present, check the fuse in the fuse block. If fuse is blown, replace fuse with same type. The dry contacts are rated for 0-60VAC, 1 amp maximum. Floats The control board has LED Indicators that will illuminate when the floats are in the closed position. Check floats for entanglement, full range of motion. Replace damaged floats.

www.seewaterinc.com 951.487.8073 • 888.733.9283 • [email protected] 22220 Opportunity Way, Suite 104 • Riverside, CA 92518

PUMP ON

PUMP OFF

For additional information regarding operation and troubleshooting questions, please call See Water, Inc. at 888-733-9283.