PowerPact™ H-, J-, and L-Frame Circuit Breakers Catalog Numbering
Catalog Numbering
–
J
L
L
3
6
250
Frame
Poles
Amperage
H H-Frame J J-Frame L L-Frame
2 2P 3 3P 4 4P
060 100 150 250 400 600 000
Terminations Brand _ Square D™ N Schneider Electric
L M P F A S N D K
Lugs Line/Load Side Lugs Line Side Lugs Load Side Bus Bar I-Line Rear Connected Plug-in Drawout Reverse I-Line
T
–
–––– Accessory Suffix Code (See Table 2) I-Line™ Phasing
60 A 100 A 150 A 250 A 400 A 600 A Switch or Frame only
Voltage 6 600 Vac
Trip Unit Micrologic™ Electronic Trip Units U31 U33 U43 U44 U53 U54 M37 M38 S40 S60 F40 F60
LI Standard Protection LSI Standard Protection LSI plus Ammeter LSIG plus Ammeter LSI plus Energy Management LSIG plus Energy Management Magnetic Only (L-Frame Only) Motor Protector Circuit Breaker 400 A Molded Case Switch (L-Frame Automatic Switch) 600 A Molded Case Switch (L-Frame Automatic Switch) 400 A L-Frame Only (No Trip Unit) 600 A L-Frame Only (No Trip Unit)
— ABC (3P) 6 CBA (3P) 1 AB (2P) 2 AC (2P) 3 BA (2P) 4 BC (2P) 5 CA (2P) 6 CB (2P)
Performance Level (kA) (See Table 1) Thermal-Magnetic Trip Units — Standard Fixed Trip Unit (Suitable for reverse connection) F06 60 A H-Frame Only (No trip unit) F15 150 A H-Frame Only (No trip unit) F25 250 A J-Frame Only (No trip unit) T Complete Circuit Breaker (Frame + removable trip unit) S15 150 A Molded Case Switch (H-Frame automatic switch) S17 175 A Molded Case Switch (J-Frame automatic switch) S25 250 A Molded Case Switch (J-Frame automatic switch) C 100% Rated Continuous Current Rating1 M71 30 A H-Frame Motor Circuit Protector (MCP) M72 50 A H-Frame Motor Circuit Protector (MCP) M73 100 A H-Frame Motor Circuit Protector (MCP) M74 150 A H-Frame Motor Circuit Protector (MCP) M75 250 A J-Frame Motor Circuit Protector (MCP) D81 500 Vdc 150–175 A J-Frame Molded Case Circuit Breaker D82 500 Vdc 200–250 A J-Frame Molded Case Circuit Breaker R 100% Rated Continuous Current Rating Complete Circuit Breaker (Frame + removable trip unit) 1
Table 1:
100% ratings valid for: 3P H/J frame unit mount only 3P/4P L-frame 250 A and 400 A unit mount 3P L-frame 250 A and 400 A I-Line
Interrupting Rating UL/CSA/NOM
240 Vac
480 Vac
IEC 647-2 Icu/Ics
600 Vac 250
Vdc1
500
Vdc2
220/240 Vac 380/440/415 Vac 500/525 Vac 690 Vac
250 Vdc1 500 Vdc3
D
25 kA
18 kA
14 kA
20 kA
—
25/25 kA
18/18 kA
14/14 kA
—
20 kA
20 kA
G
65 kA
35 kA
18 kA
20 kA
20 kA
65/65 kA
35/35 kA
18/18 kA
—
20 kA
20 kA
J
100 kA
65 kA
25 kA
20 kA
—
100/100 kA
65/65 kA
25/25 kA
—
20 kA
20 kA
L
125 kA
100 kA
50 kA
20 kA
—
125/125 kA
100/100 kA
50/50 kA
—
20 kA
20 kA
R
200 kA
200 kA
100 kA
—
—
150 kA
125 kA
75 kA
20 kA
—
—
1
250 Vdc ratings only available with PowerPact H or J circuit breakers with thermal-magnetic trip units (not including MCP).
2
UL 500 Vdc ratings only available with PowerPact J circuit breakers with thermal-magnetic trip units (not including MCP).
3
IEC 500 Vdc rating only available on PowerPact J-frame circuit beakers.
8 05/2012
™
© 2011–2012 Schneider Electric All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers General Information Table 6:
Circuit Breakers
Circuit Breaker
150 A H-Frame
Circuit Breaker Type
HD HG HJ
Number of poles1
2, 3
Amperage Range (A)
15-150
250 A J-Frame
HL HR JD JG JJ 3
JL
2, 3
400 A L-Frame LD LG LJ
3
3, 4
3, 4
70-400
200-600
70-250
LL
600 A L-Frame
JR
LR LD LG LJ
LL
LR
UL 489 Circuit Breaker Ratings
UL/CSA/NOM (kA rms)
240 Vac
25 65
100 125 200 25 65 100 125 200 25 65 100 125 200 25 65 100 125 200
480 Vac
18 35
65
100 200 18 35 65
100 200 18 35 65
100 200 18 35 65
100 200
600 Vac
14 18
25
50
100 14 18 25
50
100 14 18 25
50
100 14 18 25
50
100
250 Vdc2
20 20
20
20
---
20 20 20
20
---
--- --- ---
---
---
--- --- ---
---
---
500 Vdc2, 3
---
---
---
---
--- 20 ---
---
---
--- --- ---
---
---
--- --- ---
---
---
---
IEC 947-2 Circuit Breaker Ratings 220/240 Vac
25 65
100 125 150 25 65 100 125 150 25 65 100 125 150 25 65 100 125 150
380/415 Vac
18 35
65
100 125 18 35 65
100 125 18 35 65
100 125 18 35 65
100 125
Ultimate breaking capacity (Icu)
440/480 Vac
18 35
65
100 125 18 35 65
100 125 18 35 65
100 125 18 35 65
100 125
500/525 Vac
14 18
25
50
75
14 18 25
50
50
50
(kA rms)
690 Vac
--- ---
---
---
20
--- --- ---
---
20
--- --- ---
---
20
--- --- ---
---
20
250 Vdc2
--- ---
---
---
---
20 20 20
20
---
--- --- ---
---
---
--- --- ---
---
---
--- ---
---
---
---
20 20 20
20
---
--- --- ---
---
---
--- --- ---
---
---
500 Vdc2, 3
75
14 18 25
75
14 18 25
Service breaking capacity (Ics) % Icu
100%
100%
100%
100%
Insulation Voltage
Vi
750 Vac
750 Vac
750 Vac
750 Vac
Impulse Withstand Voltage
Vimp
8 kVac
8 kVac
8 kVac
8 kVac
Operational Voltage
Ve
690 Vac
690 Vac
690 Vac
690 Vac
Sensor Rating
In
150 A
250 A
400 A
600 A
Utilization Category
---
A
A
A
A
Without Current
4000
5000
5000
5000
With Current
4000
1000
1000
1000
754
Operations (Open-Close Cycles)
Protection and Measurements Short-circuit protection
Overload/short-circuit protection
Magnetic only
Thermal-magnetic
--- --- ---
---
---
--- --- ---
---
---
Electronic
with neutral protection (Off-0.5-1-OSN)5
with ground fault protection
with zone selective interlocking (ZSI)6
Display / I, V, f, P, E, THD measurements / interrupted-current measurement
Options
Front display module (FDM121)
Operating assistance
Counters
Histories and alarms
Metering Com
Device status/control com
Dimensions / Weight / Connections Dimensions 3P (Unit Mount) in. (mm)
Height
6.4 (163)
7.5 (191)
13.38 (340)
13.38 (340)
Width
4.1 (104)
4.1 (104)
5.51 (140)
5.51 (140)
Depth
3.4 (86)
3.4 (86)
4.33 (110)
4.33 (110)
4.8 (2.2)
5.3 (2.4)
13.2 (6.0)
13.7 (6.2)
Unit Mount
I-Line™
Rear Connection
Plug-In
Weight 3P - lb. (Kg)
Connections / Terminations
Drawout
Optional Lugs
1
H and J-frame breakers with Micrologic™ trip units available only with 3P. The HJ, HL and the J-Frame 2P breakers are 3P modules.
2
DC not available with PowerPact H, J or L-frame circuit breakers with Micrologic trip units.
3
500 Vdc specific catalog numbers, ungrounded UPS systems only.
4
Ics for 600 A L-frame circuit breaker at 525 V is 19 kA.
17 © 2011–2012 Schneider Electric All Rights Reserved
™
05/2012
PowerPact™ H-, J-, and L-Frame Circuit Breakers Circuit Breakers Table 13:
PowerPact J-Frame 250 A Unit-Mount Thermal-Magnetic Circuit Breakers with Factory Sealed Trip Unit (Suitable for Reverse Connection)
Adjustable AC Current Magnetic Trip Rating @ 40 C Hold Trip
Interrupting Rating D
G
J1
L1
R1
Standard 100% (80%) Rated2 Rated
Standard 100% (80%) Rated2 Rated
Standard 100% (80%) Rated2 Rated
Standard 100% (80%) Rated2 Rated
Standard 100% (80%) Rated2 Rated
J-Frame, 250 A, 2P, 600 Vac 50/60Hz, 250 Vdc 150 A3
750 A
1500 A
JDL26150 JDL26150C JGL26150 JGL26150C JJL26150
JJL26150C JLL26150
JLL26150C
—
—
175 A3
875 A
1750 A
JDL26175 JDL26175C JGL26175 JGL26175C JJL26175
JJL26175C JLL26175
JLL26175C
—
—
200 A4
1000 A
2000 A
JDL26200 JDL26200C JGL26200 JGL26200C JJL26200
JJL26200C JLL26200
JLL26200C
—
—
225 A4
1125 A
2250 A
JDL26225 JDL26225C JGL26225 JGL26225C JJL26225
JJL26225C JLL26225
JLL26225C
—
—
A4
1250 A
2500 A
JDL26250 JDL26250C JGL26250 JGL26250C JJL26250
JJL26250C JLL26250
JLL26250C
—
—
250
J-Frame, 250 A, 3P, 600 Vac 50/60Hz, 250 Vdc 150 A3
750 A
1500 A
JDL36150 JDL36150C JGL36150 JGL36150C JJL36150
JJL36150C JLL36150
JLL36150C JRL36150 JRL36150C
175 A3
875 A
1750 A
JDL36175 JDL36175C JGL36175 JGL36175C JJL36175
JJL36175C JLL36175
JLL36175C JRL36175 JRL36175C
200 A4
1000 A
2000 A
JDL36200 JDL36200C JGL36200 JGL36200C JJL36200
JJL36200C JLL36200
JLL36200C JRL36200 JRL36200C
225 A4
1125 A
2250 A
JDL36225 JDL36225C JGL36225 JGL36225C JJL36225
JJL36225C JLL36225
JLL36225C JRL36225 JRL36225C
250 A4
1250 A
2500 A
JDL36250 JDL36250C JGL36250 JGL36250C JJL36250
JJL36250C JLL36250
JLL36250C JRL36250 JRL36250C
1
UL Listed/CSA Certified as current limiting circuit breakers.
2
100% rated circuit breakers have copper lugs and can be used with copper wire only.
3
Standard Lug Kit: AL175JD Terminal Wire Range: 4–4/0 AWG Al or Cu
4
Standard Lug Kit: AL250JD Terminal Wire Range: 3/0 AWG–350 kcmil Al or Cu
25 © 2011–2012 Schneider Electric All Rights Reserved
™
05/2012
PowerPact™ H-, J-, and L-Frame Circuit Breakers Trip Units Table 48:
Trip Unit Availability H-, J-Frame
Trip Unit
Trip Unit >30
.9 4
.9 5 .9 6 .9 7
.9 3
5 .2 E
0 >11
.9 8
.9 2 .9
% Ir
A >30
Trip Unit
Io ) 5 6 8
2
10
1 .5
x Is d(
Ir )
2500
1250
Distribution Protection Thermal-Magnetic
Trip Unit
1
Ir (4x
3 2 .5
M icor lo g ic
Trip Unit Type
L-Frame
250A
T-M
N/A lm (= li)
ln
3.2
Distribution Protection LI
30 35 40 25 45 20 50 15 60
Micrologic™ 3.2
Ir (A)
8 16
4 2
4 6
16
1 .5
16
tr
10 12
1.5
tr @ 6 Ir
8
3 2 15
Ii (x In)
Ir
Ii
Micrologic 3.3 200 225 250 300
2
350
1
175 150
125
8
4
16
5
4
6
3 16 .5
450
8 10 12
2 1.5
16
Tr @ 6 Ir
Ir (A)
Ii (x In)
Ii
3.3S Micrologic
3.2S
Distribution Protection LSI Fixed ST and LT delays
30 35 40 25 45 20 50 15 60
Micrologic 3.2S
Ir (A)
4
5 6
4 6 8
3 2 1.5
10 12
Isd (x In)
8
3 2
tr
10 12
1.5
tsd
15
Ir Isd Ii
Ii (x In)
Micrologic 3.3S 200 225 250 300
175
350
150
450
125
Ir (A)
5
4
6
tr
6
3
10 12
2 1.5
5
4
8
3
8 10 12
2 1.5
tsd
Ii (x In)
Isd (x In)
Ir Isd Ii
Micrologic 5.2 A
30
35
25
6
4
200 175
10
2 1.5
Distribution Protection LSIG + Ammeter
12 15
30
35
40 45 50 60
20 15 4
6
2 1.5
Ig
Magnetic Only
tsd Ir Isd Ii
6.3 A Micrologic 200 175
12 15
225
4
Micrologic 6.3 E
Standard
250 300
5
tr
Isd
tsd Ii(xIn)
Ig
tg
6
3 2 1.5
Ir
350 400
150 125
Ii (x In)
M
tr
8 10 12
Ii (x In)
Micrologic 6.3 A
tg
10
Distribution Protection Micrologic 6.2 E LSIG + Energy Monitoring
Motor Circuit Protection
6
3 2 1.5
8
3
250 300 350 400
5
4
Micrologic 5.3 E
25
225
150 125
Ii (x In)
Micrologic 5.2 E
Micrologic 6.2 A
5.3 A Micrologic
8
3
Distribution Protection LSI + Energy Monitoring
Micrologic 5.3 A
40 45 50 60
20 15
6.2E
Distribution Protection LSI + Ammeter
tr
8 10 12
tsd
Ii (x In)
Ir Isd Ii
N/A
Energy Efficient Energie Efficace Energia Eficiente
1.3 M Micrologic
Motor Protection Micrologic 1 M
N/A
Micrologic 1.3M 3200 2800
36004000
2400 2000
4400 4800
Isd (A)
2.2 M Micrologic
Motor Protection Micrologic 2 M
Micrologic 2.2 M
2.3M Micrologic
50
Ii=3750
163
172 181 210 217 FLA (A)
155 145 137 114
Class.
Isd (x FLA)
FLA
Isd
Micrologic 2.3 M 270 290 310 330 348 FLA (A)
250 230 210 190
Class.
Isd (x FLA)
FLA
Isd
56 05/2012
™
© 2011–2012 Schneider Electric All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers Wiring Diagrams
Section 11—Wiring Diagrams Unit-Mount Circuit Breakers Micrologic™ Trip Unit1
Power
Remote Operation 06114460
Z4
Z5
Z2
Z1
NSX cord
Z3
Upstream CB
3P or 4P
Vac (+)
Vac (+)
06114459
N LA LB LC BPO
SDE
81
82
84
BPF
Q
Z5
Z4
Z3
B2
B4
MX
T2 I
A2
A4
C2
Z2
Z1
D2
HL
+ MN
T1
auto manu
or
0
I
Vac (-)
A1
L1
C1
D1
V
manu
SDE Vac (-)
Motor Operator 06114461
Z5
Z4
Z1
LA LB LC
Z2
N
Z3
3P + N
Downstream CB
NSX cord
I
V
B4
Q
Z2
Z1
HL
+ -
Vac (220/240 V) BSCM
T1
Z5
Z4
ENVT
Z3
T2 Q auto manu
I
A1
ENCT H2 T1
0
Vac H1 T2 Schematic of the communicating motor operator .
Communicating Motor Operator Continued on next page
136 05/2012
™
© 2011–2012 Schneider Electric All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers Wiring Diagrams
Unit-Mount Circuit Breakers (continued) Indication Contacts
102
104 VT
124 WH
YE
134 RD
WH 121
GY
CAO1
CAF2 CAF1
131
81
11
Open
101
SD
SDE
91
OF1
21
OF2
31
OF3
Closed
RD
94
Fault
92
84
12
14
22
24
32
Fault
06114462
34
82
Closed
Open
The diagram is shown with circuits de-energized, relays in normal position, and all devices open, connected, and charged. Terminal connections shown as O must be connected by the customer.
Micrologic™ Trip Unit A or E
Remote Operation
Communication
MN
H (WH), L(BL): data
or
-(BK), +(RD): 24 Vdc power supply
MX
ZSI (Zone Selective Interlocking)
Motor Operator
Z1: ZSI OUT SOURCE
A4
Opening Order
Z2: ZSI OUT
A2
Closing Order
Z3: ZSI IN SOURCE
B4, A1
Power Supply to Motor Operator
Z4: ZSI IN ST (short time)
L1
Manual Position (manu)
Z5: ZSI IN GF (ground fault)
B2
Overcurrent Trip Switch Interlocking (mandatory for correct operation)
(Z3, Z4, and Z5 for L-frame circuit breaker only)
BPO
Opening Pushbutton
ENCT: External Neutral Current Transformer: -Shielded cable with 1 twisted pair (T1, T2) -Shielding earthed at CT end only Connection L = 12 in. (30 cm) max. -Maximum length of 33 ft (10 m) -Cable size of 22 AWG -Recommended cable: Belden 9451SB or equivalent
BPF
Closing Pushbutton
ENVT: External Neutral Voltage Tap for Connection to the Neutral using a 3P Circuit Breaker
OF2/OF1
Device ON/OFF Auxiliary Switches
OF3
Device ON/OFF Auxiliary Switches (L-Frame)
Color Code for Auxiliary Wiring
SDE
Overcurrent Trip Switch (short-circuit, overload, ground fault, earth leakage)
RD: Red
VI: Violet
SD
Alarm Switch
WH: White
GY: Gray
CAF2/CAF1
Early-Make Contact (rotary handle only)
YE: Yellow
OR: Orange
CAO1
Early-Break Contact (rotary handle only)
BK: Black
BL: Blue
A/E
A/E
A/E
E
Undervoltage Release Shunt Release
Communicating Motor Operator B4, A1
Motor Operator Power Supply
BSCM
Breaker Status and Control Module
Indication Contacts
GN: Green
137 © 2011–2012 Schneider Electric All Rights Reserved
™
05/2012
PowerPact™ H-, J-, and L-Frame Circuit Breakers Dimensions
PowerPact J-Frame Circuit Breakers
48996-022-01
Figure 15:
150–250 A Bus Bar PowerPact J-Frame 3P Circuit Breaker 7.52 [191,0] 6.22 [158,0] 1.30 [33,0]
1.38 [35,0]
Ø .35 [8,9] (5/16-18 TERMINAL NUT)
Ø .20 [5,1] (MOUNTING HOLE) .37 [9,4]
1.38 [35,0]
2.06 [52,4]
.57 [14,4]
4.12 [104,7]
1.00 [25,5]
1.38 [35,0]
.35 [8,9]
1.37 [34,8]
.70 [17,7]
A 2.60 [66,1]
SECTION B-B SCALE 1:1
5.57 [141,5] 5.74 [145,8] 6.52 [165,5]
Trip Unit Dim. “A” Dim. “B” Thermal-Magnetic 1.76 3.44 and MCP [87,4] [44,7] Micrologic 3.49 1.69 Electronic Trip [88,6] [44,0]
ISOMETRIC VIEW SCALE 1:2 B
19.5° ON
17.9° OFF
.48 [12,2] 1.05 [26,6]
21.5° TRIPPED
B
.16 [4,0]
SEE DETAIL A 3.74 [95,1]
3.24 2.87 [82,4] [72,9]
B
4.25 [108,0]
Figure 16:
.99 [25,2]
in. Dimensions: [mm]
1.91 [48,5]
DETAIL A SCALE 1:1
150–250 A Lug-Lug PowerPact J-Frame 3P Circuit Breaker 7.52 [191,0]
48996-014-01
.73 [18,6]
5.00 [127,0]
Ø .20 [5,1] (MOUNTING HOLE)
6.22 [158,0]
1.30 [33,0]
1.38 [35,0]
1.38 [35,0] 2.06 [52,4]
4.12 [104,7]
1.38 [35,0]
.86 [21,9]
1.37 [34,8]
A 2.60 [66,1]
Trip Unit Dim. “A” Dim. “B” Thermal-Magnetic 1.76 3.44 and MCP [44,7] [87,4] Micrologic 1.69 3.49 Electronic Trip [43,0] [88,6]
5.57 [141,5] 5.74 [145,8] 6.66 [169,2]
ISOMETRIC VIEW SCALE 1:2
19.5° ON
17.9° OFF
.53 [13,4] 1.06 [27,0]
21.5° TRIPPED
.16 [4,0]
SEE DETAIL A B
3.24 [82,4]
3.24 3.74 [82,4] [95,1]
2.87 [72,9]
4.25 [108,0]
.73 [18,6]
5.00 [127,0]
.99 [25,2]
1.91 [48,5]
Dimensions:
in. [mm]
DETAIL A SCALE 1:1
149 © 2011–2012 Schneider Electric All Rights Reserved
™
05/2012
PowerPact™ H-, J-, and L-Frame Circuit Breakers Trip Curves Figure 60:
J-Frame 150–250 A (JD, JG, JJ, and JL) Thermal-Magnetic Trip 80 90 100
70
60
50
40
30
20
15
8 9 10
7
6
5
4
3
2
1.5
.8 .9 1
.7
.6
.5
MULTIPLES OF RATED CURRENT 10000 9000 8000
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
JD, JG, JJ, JL MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 50-5 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix
Continuous Ampere Rating
Maximum AC Voltage
Number of Poles
JD, JG, JJ, JL
150–250
600
2, 3
3000
3000
2000
2000
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies. All time/current characteristic curve data is based on 40°C ambient cold start. Terminations are made with conductors of appropriate length and ratings.
400
400
MAXIMUM SINGLE-POLE TRIP TIMES AT 25°C BASED ON NEMA AB-4 2003
8000 9000 10000
7000
6000
5000
4000
3000
2000
1500
800 900 1000
700
600
500
150 400
200
150
150
200
300
300
200
300
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9 8
10 9 8
7
7
6
6
5
5
4
4
3
3
2
2
TIME IN SECONDS
100 90 80
1.5
1.5
1 .9 .8
LIMITS LOW SETTING
TIME IN SECONDS
100 90 80
1 .9 .8
LIMITS HIGH SETTING
.7
.7
.6
.6
.5
.5
.4
.4
.3
.3
.2
.2 .15
.15
MAGNETIC TRIP ADJUSTMENT RANGE
.1 .09 .08
.1 .09 .08
.07
.07
.06
.06 .05
.05 .04
.04
MAXIMUM CLEARING TIME (AT 60 Hz) (AT 50 Hz)
.03
.03
1 CYCLE (50 Hz)
.02
1 CYCLE (60 Hz)
.015
.02 .015
1/2
.01 .009 .008
CYCLE (50 Hz)
1/2
CYCLE (60 Hz)
.007
.01 .009 .008 .007 .006
.006
.005
© 2004 Schneider Electric All Rights Reserved
250 225 200 175 150
MULTIPLES OF RATED CURRENT
8000 9000 10000
6000
7000
5000
4000
3000
1500
2000
800 900 1000
700
600
500
400
300
200
150
80 90 100
70
60
50
40
30
20
15
8 9 10
7
6
5
4
3
2
1.5
.8 .9 1
.7
.6
.5
.005
TM
Curve No. 0050TC0405 June 2004 Drawing No. 48095-050-05
172 05/2012
™
© 2011–2012 Schneider Electric All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers Trip Curves Figure 76:
J-Frame UL Listed Current -Limiting Circuit Breaker 7+(50$/0$*1(7,&02/'('&$6(&,5&8,7%5($.(56 -² )5$0(&855(17/,0,7,1*&,5&8,7%5($.(56 -$)5$0($7$1'9 ---/$1'-5³$ 3($./(77+528*+&855(17OS Ip
Maximum* Peak Let-Through Current (Amperes) *Based on maximum values obtained throughout the circuit breaker development and UL test programs.
60000
50000
480 V 3Ø 40000
Maximum Available Peak Current at 15% Power Factor
600 V 3Ø
30000
240 V 3Ø
20000
10000 9000 8000
7000
200000
150000
90000
100000
80000
70000
60000
50000
40000
30000
20000
9000
10000
8000
7000
6000
5000
6000
Availability (RMS Symmetrical Amperes) 'UDZLQJ1R $SULO 5HY
6FKQHLGHU(OHFWULFDOOULJKWVUHVHUYHG
189 © 2011–2012 Schneider Electric All Rights Reserved
™
05/2012
PowerPact™ H-, J-, and L-Frame Circuit Breakers Trip Curves Figure 77:
J-Frame UL Listed Current-Limiting Circuit Breaker 7+(50$/0$*1(7,&02/'('&$6(&,5&8,7%5($.(56 -² )5$0(&855(17/,0,7,1*&,5&8,7%5($.(56 -$)5$0($7$1'9 ---/$1'-5³$ /(77+528*+&855(17OW I 2t
Maximum* Let-Through I2t (Amperes2 Seconds x 106) *Based on maximum values obtained throughout the circuit breaker development and UL test programs.
2.0
600 V 3Ø 480 V 3Ø
1.0 .9 .8
.7
240 V 3Ø .6
.5
.4
.3
200000
150000
90000
100000
80000
70000
60000
50000
40000
30000
20000
10000
9000
8000
7000
6000
5000
.2
Availability (RMS Symmetrical Amperes) 'UDZLQJ1R $SULO 5HY
6FKQHLGHU(OHFWULFDOOULJKWVUHVHUYHG
190 05/2012
™