LD SERIES

Report 1 Downloads 107 Views
LD SERIES

ADD A WARNING BLINK TO ANY CONTROL

EXTENDED LIGHTING CONTROL LIGHTING DELAY TIME SWITCH

INPUT VOLTAGE: 120/208/240/277VAC, 50/60Hz. TERMINAL RANGE: #10 - #16AWG. OPERATING TEMPERATURE: -22° to 150°F (-30° to +65°C).

ASHRAE 90.1

APPLICATIONS

CONTACT RATINGS

SPECIFICATIONS

POWER CONSUMPTION: 5VA Maximum.

®

®

ENCLOSURE: Metal Indoor NEMA 1 with lockable hasp (see page 153 for dimensions).

®

®

Open offices Gymnasiums Warehouses Outdoor recreation courts User-activated lights with time limits Match with photocontrol and timer to limit hours of use

RATING

TYPE

VOLTAGE

General Purpose Ballast

24/240VAC 277VAC 120VAC 208-277VAC

Tungsten

120-277VAC

5A

3A

Pilot Duty

120-240VAC 27VAC

470VA 690VA

275VA

Resistive

28VDC

20A

10A

NO

NC

20A 20A 20A 10A

10A 3A 10A 3A

WIRING DIAGRAMS LDSH WIRING

LDS WIRING

TORK TIME SWITCH

TORK TIME SWITCH

OUTPUT TERMINALS

OUTPUT TERMINALS OFF

NO

C

OFF

NC

MOMENTARY PUSH-BUTTON SWITCH

C ON OFF DO NOT APPLY VOLTAGE

N

TIME SWITCH INPUT

120

208 240

H

REMOTE INPUT

277 VAC

H C ON OFF DO NOT APPLY

INPUT POWER

VOLTAGE

NO

N

N

C

277 VAC

INPUT POWER

AUX. OUTPUT TERMINALS NC

208 240

120

TIME SWITCH INPUT

MAIN LOAD OUTPUT TERMINALS NC

120 VAC

ON

ON

N

NC

N

N

H

C

MOMENTARY PUSH-BUTTON SWITCH

H

REMOTE INPUT

NO

MAIN LOAD OUTPUT TERMINALS

NO

C

NC

NO

C

H

H

H

AUX LOAD

ORDERING INFO

FEATURES MAINTAINED INPUT WITH LOAD WARNING BLINK: LDS Series controls output load contacts based on power applied to the time switch input contact. At removal of power from the time switch input, LDS Series provides 1 second blink then keeps load contacts closed for an extra 1 or 5 minutes (user selectable) before turn off. MAINTAINED INPUT WITH AUXILARY WARNING: LDSH Series controls output load contacts based on power applied to the time switch input contact. At removal of power from the time switch input, LDSH Series closes a second set of contacts for a user supplied audible or visual warning device. The warning circuit closes for a selected time of 4 seconds (best for audible device or continuous, then keeps load contacts closed for an extra 1 or 5 minutes (user selectable) before turn OFF.

CATALOG NO.

LDS-A LDS LDSH-A LDSH

UPC CODE

81026 81025 81031 81028

INPUT SUPPLY (VAC) 50/60 Hz

120/208-240/277 120/208-240/277 120/208-240/277 120/208-240/277

MOMENTARY INPUT: Provides timed override when time switch input contact is unpowered (timer OFF). When activated during the warning period, load contacts are kept closed and timing starts. Both series can accept momentary input contact closure for ON to start the timing and OFF to end the timing. TIMED OVERRIDE SETTINGS: User may select override times of 1⁄2, 1, 11⁄2, 2, 6, 9, or 12 hours. Warning before OFF is always active after override time.

LOAD

OUTPUT CONTACTS

ENCLOSURE TYPE

SPDT

Metal Indoor NEMA 1

SPDT SPDT SPDT

Mechanism Metal Indoor NEMA 1 Mechanism

N

TORK TIME SWITCH

TORK TIME SWITCH

OUTPUT TERMINALS

OUTPUT TERMINALS OFF

NO

C

OFF

NC

MOMENTARY PUSH-BUTTON SWITCH

VOLTAGE

N

TIME SWITCH INPUT

N

120

208 240

H 120 VAC

REMOTE INPUT

277 VAC

H C ON OFF DO NOT APPLY

INPUT POWER

VOLTAGE

NO

N

N

C

NO

277 VAC

INPUT POWER

AUX. OUTPUT TERMINALS NC

208 240

120

TIME SWITCH INPUT

MAIN LOAD OUTPUT TERMINALS NC

NC

ON

ON

H

C

N

N

C ON OFF DO NOT APPLY

NO

MOMENTARY PUSH-BUTTON SWITCH

H

REMOTE INPUT

N

LOAD

N

MAIN LOAD OUTPUT TERMINALS C

NC

NO

C

H

H

H ON OFF COMMON

AUX LOAD MECHANICALLY HELD CONTACTOR WITH COIL CLEARING CONTACTS

ON

N

MECHANICALLY HELD CONTACTOR WITH COIL CLEARING CONTACTS

OFF COMMON

PHOTOCONTROL

N

N

TORK TIME SWITCH OUTPUT TERMINALS

APPLICATION EXAMPLE

Lighting for a high school’s tennis courts turns on during normal class hours when natural light diminishes using a 7 day time switch and photocell. After 3pm, staff members sometimes use the courts (the time switch is then off). A momentary pushbutton activates the LDSH for timed override of HID lighting. Five minutes before the lights go out, an auxiliary contact flashes an incandescent warning beacon (HID lighting can not be made to blink). Additional timed override can be arranged for via the momentary pushbutton.

APPLICATION WIRING

NO

C

NC

FLASHING LIGHT

H

120V

N

C

ON

H

OFF

N

N

120 208/240277

REMOTE INPUT TIME SWITCH INPUT

MOMENTARY PUSHBUTTON SWITCH

AUXILLARY OUTPUT NO C

LDSH

NC

INPUT POWER N

MAIN LOAD OUTPUT NO C

NC

120V

OFF N ON

H 120V N OFF

SWITCHED CIRCUIT TO TENNIS COURT LIGHTS

ON

N

MECHANICALLY-HELD 4 POLE LIGHTING CONTACTOR

SWITCHED CIRCUIT TO TENNIS COURT LIGHTS

480V CIRCUITS FROM PANEL

DIGITAL CONTROLS TORK 83

A DIVISION OF NSi INDUSTRIES, LLC USA • 800.321.5847 • www.nsiindustries.com

TORK 84