LIMITRON™ Class RK1 250V

Report 0 Downloads 10 Views
LIMITRON™ Class RK1 250V KTN-R — 250Vac, 1-600A, Fast-Acting Fuses Dimensions – in

10.38" (± 0.094)

2" (± 0.31) 0.56" (± 0.008)

2.59" (± 0.008)

1/10 to 30A 450 to 600A

8.63" (± 0.094)

3" (± 0.31) 0.81" (± 0.008) 35 to 60A

2.06" (± 0.008) 225 to 400A

5.88" (± 0.062)

7.13" (± 0.062) 1.06" (± 0.008)

Description: Advanced protection Class RK1 current-limiting, fast-acting fuses.

70 to 100A

1.56" (± 0.008) 110 to 200A

CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787

Features: • Single-element, fast-acting fuses with minimal time-delay • Provides a high degree of short-circuit current-limitation (component protection) • Particularly suited for circuits and loads with no heavy surge currents of motors, transformers, solenoids and welders • Commonly used to protect circuit breakers with lower interrupting ratings • If used in circuits with surge currents (motors, etc.) must be sized to prevent unwanted opening and thus only provide short-circuit protection • Incorporate Class R rejection feature. Can be inserted in non-rejection type fuse holders to physically and electrically replace fast-acting Class H, K1, K5, RK5, and other fastacting fuses.

Catalog Numbers (amps)

Recommended Fuse Blocks

Catalog Symbol: KTN-R-(amp) Ratings: Volts — 250Vac — 250Vdc (70-600A) Amps — 1-600A IR — 200kA Vac RMS Sym. — 100kA Vdc Agency Information: UL Listed, Std. 248-12, Class RK1, Guide JDDZ, File E4273

KTN-R-1 KTN-R-2 KTN-R-3 KTN-R-4 KTN-R-5 KTN-R-6 KTN-R-8 KTN-R-10 KTN-R-12 KTN-R-15 KTN-R-20 KTN-R-25

KTN-R-30 KTN-R-35 KTN-R-40 KTN-R-45 KTN-R-50 KTN-R-60 KTN-R-70 KTN-R-80 KTN-R-90 KTN-R-100 KTN-R-110 KTN-R-125

Carton Quantity and Weight (250Vac)* Amp Rating 1–30 40–60 70–100 110–200 225–400 450–600

Carton Qty. 10 10 5 1 1 1

KTN-R-150 KTN-R-175 KTN-R-200 KTN-R-225 KTN-R-250 KTN-R-300 KTN-R-350 KTN-R-400 KTN-R-450 KTN-R-500 KTN-R-600

Fuse Amps 0-30 35-60 70-100 110-200 225-400 450-600

1-Pole H25030-1 R25030-1 H25060-1 R25060-1 RM25100-1CR RM25200-1CR RM25400-1CR RM25600-1CR

2-Pole H25030-2 R25030-2 H25060-2 R25060-2 RM25100-2CR RM25200-2CR RM25400-2CR RM25600-2CR

3-Pole H25030-3 R25030-3 H25060-3 R25060-3 RM25100-3CR RM25200-3CR RM25400-3CR RM25600-3CR

For additional information on 250 volt fuse blocks, see Data Sheet # 1110 (R250) and # 1112 (H250) and product brochure # 3192 (RM Series). Fuse Reducers For Class R Fuses Equipment Fuse Clips

60A 100A 200A 200A 400A 600A

Desired Fuse (Case) Size

Catalog Numbers (Pairs) 250V

30A 30A 60A 60A

NO.263-R NO.213-R NO.216-R NO.226-R

100A 100A 200A 100A 200A 400A

NO.2621-R NO.2641-R NO.642-R NO.2661-R NO.2662-R NO.2664-R†

† Single reducer only (pair not required).

For additional information on Class R fuse reducers, see Data Sheet 1118. 0713

BU-SB13739

Page 1 of 3

Data Sheet # 1043

LIMITRON™ Class RK1 250V KTN-R — 250Vac, 1-600A, Fast-Acting Fuses

600A

400A

200A

100A

60A

30A

Time-Current Curves - Average Melt

300

AMP RATING

100

TIME IN SECONDS

10

1

RMS SYMMETRICAL CURRENT IN AMPS

0713

BU-SB13739

Page 2 of 3

10,000

1,000

100

0.01

40

0.1

Data Sheet # 1043

LIMITRON™ Class RK1 250V KTN-R — 250Vac, 1-600A, Fast-Acting Fuses Current-Limitation Curves B AMP RATING

100,000

600 400 200 100 10,000

60 30

10,000

200,000

1,000

100,000

A

1,000

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS

400,000

RMS SYMMETRICAL CURRENTS IN AMPS A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYMM RMS AMPS)

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 0713

BU-SB13739

Page 3 of 3