Metalux VT3 Vaportite Industrial spec sheet - CapitalTristate

Report 3 Downloads 110 Views
COOPER LIGHTING - METALUX

®

Des c r i pti on

Type

Catalog #

The VT3 Series is a contemporary looking energy efficient industrial Vaportite fixture that features rugged and durable construction. The VT3 incorporates a full metal gear tray inside a reinforced fiberglass housing with a high impact diffuser. This Vaportite series is suitable for interior and exterior applications and can be surface or chain mounted.

Project Date

Comments

The VT3 Series has been designed for maximum operation in commercial institutional and industrial environments where weathering, high temperature, humidity and dust or corrosive fumes are present.

Prepared by

Spec i fi c a ti on F ea t u r e s

Construction

Ele ctrica l*

Shielding

Fiberglass housing is reinforced polyester and self-extinguishing (ASTM-D635-74) plastic of a permanent pearl gray color. Top of housing has five embossments (2' unit), nine embossments (4' unit) and thirteen embossments (8' unit), providing mounting flexibility on uneven surfaces. A watertite hub for 1/2" conduit entry is provided at each end of housing (standard) for continuous feed. Polyurethane gasketing is formed in the housing providing a continuous seamless seal for the diffuser. Six sturdy cam latches clamp diffuser tightly for a positive seal between housing, gasketing and diffuser.

Unit has full metal gear tray secured by internal fasteners and tethers providing maximum protection and rigidity. Ballasts are CBM/ETL Class “P” certified suitable to 70°F. (Cold temperature ballasts are available for less than 0°F starting with EHT (T5HO only), EB/PLUS and ER/PLUS ballasts). Rotor lock lampholders. Electrical components and fixture are UL/ CUL listed for Wet Locations.** IP65 approved with optional IP67 rating (4' only) with 8 latches. NSF certified.

New contemporary styled lens clear acrylic w/impact resistant additives and linear prisms. “DR” - Clear low brightness pattern acrylic with 15% high impact additive. “DR-100” - Clear low brightness pattern acrylic with 100% high impact additive. Example: VT3-232DR-100. Mounting

Surface mount fixture using two (2) galvanized brackets (included per 4' section). Optional chain mount hanging set or snap-on brackets are also available.

VT3 132 232 332 154T5 254T5 354T5

4-7/8" [123mm]

4' or 8' Industrial 1, 2 or 3 Lamp

6-15/16" [177mm]

Vaportite Industrial Lam p C onfi gur a ti o n s

Mount ing Da t a 2 LAMP

1 LAMP

41-1/2" [1054mm] Optional Back Hub Locations 4 FOOT

X

X 4-7/8" [123mm]

4-7/8" [123mm]

X=1-13/32" [36mm]

6-15/16" [177mm]

3 LAMP

X=1-13/32" [36mm] Y=2-1/2" [64mm]

38-3/4" [984mm] 1/4" x 28" Stud (2 Places)

6-5/8" [168mm] Y

X=5-3/8" [137mm]

6-15/16" [177mm]

Energy Data X

49-13/16" [1265mm]

4-3/16" [106mm]

X 4-7/8" [123mm]

X=1-13/32" [36mm] Y=2-1/2" [64mm]

Y

Luminaire Efficacy Rating LER = FL-73 Catalog Number: VT3-232 DR Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.29

6-15/16" [177mm]

Ins ta lla ti on D a ta

Relative Light Output Factors

MOUNTING BRACKETS Furnished Two per 4' Unit Four per 8' Unit

Input Watts: EB Ballast & STD Lamps 132 (30) 232 (61) 154T5 (54) 254T5 (106)

To accurately predict how luminaires will perform in cold temperatures, Cooper Lighting individually tested each configuration in the different ambient environments. The relative light output factor should be applied as an additional light loss factor component.

*Reference the lamp/ballast data in the Technical Section for specific lamp/ballast requirements. **Not Suitable for Wet Locations if EL4 Option is added. Consult Pre Sales Technical Support.

VT3 Series OPTIONAL CHAIN HANGING SET (VT2-CHAIN/SET-U) Includes 6 ft. of chain, 4 large S-Hooks and 4 small S-Hooks Order Two (2) Kits for each 8' Fixture

-15°F (-26°C) 0°F (-18°C)

20°F (-6°C)

33°F (0°C)

50°F (10°C)

0.67

0.97

0.99

VT3-232

n/a

n/a

VT3-254

0.73

0.76

0.86

0.90

0.94

VT3-332

n/a

n/a

0.96

0.98

0.98

VT3-354

0.91

0.93

n/a

n/a

n/a

Specifications and dimensions subject to change without notice. Consult your representative for additional options and finishes.

LAMPS CONTAIN MERCURY. DISPOSE ACCORDING TO LOCAL, STATE OR FEDERAL LAWS

Safe and convenient means of disconnecting power.

ADF071376 2014-01-18 10:34:30

VT3

Ph otom etr i c s

VT3-232DR-UNVEB81-WL-U (1) Electronic Ballasts (2) 32W T8 lamps 2850 lumens Spacing criterion: (II) 1.3 x mounting height, (⊥) 1.5 x mounting height Efficiency 77.4% Test Report: LTL10864.IES LER =FL72 Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.34

VT3-254T5DR-UNV- C a n d e l a EHT1-WL-U (1) Electronic Ballasts Angle Along II ⊥ 1546 (2) 54W T5 lamps 0 1540 4400 lumens 5 1519 10 1483 Spacing criterion: 15 1436 (II) 1.2 x mounting 20 1375 height, (⊥) 1.5 x 25 1300 mounting height 30 1215 35 1118 Efficiency 69.7% 40 1012 Test Report: 45 896 50 770 LTL10777.IES 55 634 LER =FL59 60 496 352 Yearly Cost of 1000 65 70 219 lumens, 3000 hrs 75 113 at .08 KWH = $4.05 80 47

Candela Angle 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90

Along II 1103 1097 1083 1059 1025 983 932 870 801 725 640 548 451 352 251 155 77 28 6

45° 1103 1108 1107 1091 1089 1058 1035 991 952 892 831 753 683 611 550 471 367 290 217

Across ⊥ 1103 1107 1106 1127 1113 1098 1088 1052 1024 971 920 878 814 771 698 592 513 427 342

C o e f fi c i e n t s o f U t i l i z a t i o n

rc rw RCR 0 1 2 3 4 5 6 7 8 9 10

Effective floor cavity reflectance 80% 70% 70 50 30 10 70 50 30 10 91 82 74 67 61 56 51 47 43 40 37

91 78 67 58 51 45 40 36 32 29 26

91 74 61 52 44 38 33 29 25 22 20

91 70 56 46 39 32 28 24 20 17 15

89 79 71 65 59 54 49 45 42 38 36

89 75 65 57 50 44 39 35 31 28 26

89 72 60 51 43 37 32 28 25 22 19

89 69 55 46 38 32 27 23 20 17 15

20% 50% 50 30 10

30% 50 30 10

50

84 71 61 54 48 42 37 33 30 27 24

79 67 58 51 45 40 36 32 29 26 23

75 64 55 49 43 38 34 30 27 25 22

84 68 57 49 42 36 31 27 24 21 19

84 66 53 44 37 31 27 23 20 17 15

79 65 54 47 40 34 30 27 23 20 18

79 63 51 43 36 30 26 23 19 17 15

10% 30 10 75 62 52 45 39 33 29 26 23 20 18

0% 0

75 60 49 42 35 30 26 22 19 16 14

Luminance Data

Zone 0-30 0-40 0-60 0-90 0-180

Angle in Deg 45

Average 0-Deg cd/sm 5519

Average 45-Deg cd/sm 7213

Average 90-Deg cd/sm 7212

55 65 75 85

5083 4347 3001 1349

6756 6377 6097 5151

7098 7074 6510 6092

%Lamp 15.8 26.5 49.9 73.1 77.4

%Fixture 20.4 34.3 64.5 94.5 100.0

rc rw RCR 0 1 2 3 4 5 6 7 8 9 10

73 58 47 40 33 28 24 20 17 15 13

Zonal Lumen Summary Lumens 899 1512 2847 4169 4413

85 90

C o e f fi c i e n t s o f U t i l i z a t i o n Effective floor cavity reflectance 80% 70% 70 50 30 10 70 50 30 10 82 74 66 60 55 50 46 42 39 36 33

82 70 60 52 46 40 36 32 29 26 23

82 66 55 46 40 34 29 26 23 20 18

82 63 50 41 35 29 25 21 18 16 14

80 72 64 58 53 48 44 41 38 35 32

80 68 58 51 45 40 35 32 28 25 23

80 65 54 45 39 33 29 25 22 19 17

80 62 49 41 34 29 24 21 18 15 14

45° 1546 1525 1548 1514 1509 1487 1446 1396 1315 1267 1174 1081 954 827 771 704 578 432 285

13

Across 1546 1533 1525 1546 1566 1530 1509 1502 1425 1384 1308 1179 1107 1101 1044 936 807 614 431

20% 50% 50 30 10

30% 50 30 10

50

76 65 55 49 43 38 34 30 27 24 22

72 61 53 46 41 36 32 29 26 23 21

69 58 50 44 39 34 31 28 25 22 20

76 62 51 44 38 32 28 25 22 19 17

76 59 48 40 33 28 24 21 18 15 13

72 59 49 42 36 31 27 24 21 18 17

72 57 46 39 33 27 24 20 17 15 13

10% 30 10 69 57 47 41 35 30 26 23 20 18 16

69 55 45 38 32 27 23 20 17 15 13

0% 0 67 53 43 36 30 25 22 18 16 13 12

Zonal Lumen Summary

Luminance Data

Zone 0-30 0-40 0-60 0-90 0-180

Angle in Deg 45

Average 0-Deg cd/sm 7704

Average 45-Deg cd/sm 10245

Average 90-Deg cd/sm 10279

55 65 75 85

7142 6126 4240 2265

9700 8631 9114 7674

9531 10102 10293 8760

Lumens 1253 2112 3985 5908 6137

%Lamp 14.2 24.0 45.3 67.1 69.7

%Fixture 20.4 34.4 64.9 96.3 100.0

Order ing Infor m a ti on SAMPLE NUMBER: VT3-232DR-UNV-EB81-WL-U

Tandem Blank= 4' Length 8T=8' Length Series VT3=Vaportite (Gasketed Enclosure) Number of Lamps (3) 1=1 Lamp 2=2 Lamps 3=3 Lamps (Lamps not included)

Voltage (1) 120V=120 Volt 277V=277 Volt 347V=347 Volt UNV=Universal Voltage 120/277 (2) UNC=Universal Voltage 347/480 (6) GL=Single Element Fuse GM=Double Element Fuse VT-REM- (specify battery)= Remote Emergency Enclosure (4)

Wattage (Length) 32=32W T8 (48") 28T5=28W T5 (48") 54T5=54W T5HO (48") (3) Lens DR=Internal Prismatic Lens/15% DR High Impact Additive (Standard) DR-50=50% High Impact Additive DR-100=100% High Impact Additive (Extreme) NOTES: (1) Ballast type used only if ballast & voltage is chosen. (2) Not available when specifying emergency ballasts, voltage must be specific. (3) EHT2 ballasts are recommended for ambient temperatures above 102°F (40°C) 3 Lamp 54W T5HO configurations. (4) Rated for operation up to 30C. (5) Top Hub required when stem mounting. (6) 2/3 lamp ballast configurations in EB8/PLUS only for T8 UNC version. (7) Use EHT1 ballast in ambient temperatures below 0°F (-18°C) on 3 Lamp 54W T5HO configurations. (8) Example: VT3-232DR-UNV-EB81-WL-GT4-U. See stock guide online for stock items. (9) Order one (1) kit for 4ft. fixture, or two (2) kits for 8ft. fixture. Specifications & dimensions subject to change without notice. Consult your Cooper Lighting Representative for availability and ordering information.

Ballast Type (1) EB8 =T8 Electronic Start. Total Harmonic Distortion < 10% EB8 /PLUS= T8 Electronic Start. (6) Total Harmonic Distortion < 10%. High Ballast Factor > 1.13. ER8 =T8 Electronic Program Rapid Start. Total Harmonic Distortion < 10% ER8 /PLUS= T8 Electronic Program Rapid Start. Total Harmonic Distortion < 10%. High Ballast Factor > 1.15. EBT =T5/T5HO Electronic Program Rapid Start. Total Harmonic Distortion < 10%. Standard Ballast Factor=1.0 EHT = T5HO Linear Electronic (3) (7) Start High Ambient. Total Harmonic Distortion < 10% Number of Ballasts 1=1 Ballast 2=2 Ballasts

SH IPPING DATA Catalog No. VT3-132 DR-WL VT3-232 DR-WL VT3-154T5 VT3-254T5

WL=Wet Location Label

Packaging U=Unit Pack PALC=Job Pack in Carton

Options 8L=8 Latches (IP67 Rating), (4' only) RIF1=Radio Interference Suppressor TH=(2) Top Watertite Hubs (5) TEH=(2) Top & (2) End Watertite Hubs (all Watertite Hubs have 1/2" Conduit Entry) (5) BKS=(2) Snap-on Brackets for Chain or Surface Mount M4=Specular Reflector SSL=Stainless Steel Latches VRS=Vandal Resistant Screws for Latches GT4=Stock product only (8)

Accessories (order separately) VT2 Stem Bushing=1/2" – 3/8" (Required when using Stem/Sets, Requires (1) per (Stem/Set) VT2-Chain/Set-U=Chain Hanging Set Includes 6 ft. of chain, 4 large S-Hooks and 4 small S-Hooks. (9) VT2-SS-MBK=Stainless Steel Mounting Brackets. (9) VT3-BKS2-PK=(2) Snap-on Brackets for Surface or Chain Mount. Adjustable along length of fixture. VT3-4FT-M4 PK=4' Specular Interior Reflector Pack for VT3 (stock product)

Wt. 16 lbs. 16 lbs. 16 lbs. 16 lbs.

Specifications and dimensions subject to change without notice. Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 468.4801

ADF071376 2014-01-18 10:34:30