Mini Waterless In-Line Condensate Trap - RectorSeal

Report 2 Downloads 71 Views
83180 Model No.

(EZT180)

(EZT113)

U.S. Patent Numbers 5,069,042 5,522,229

®

Mini Waterless In-Line Condensate Trap

Kit Contents Mini Trap (1) Rubber Adaptor (1) Cleaning Label (1)

Scan for more info

2 Year

LIMITED WARRANTY. RectorSeal ® warrants to the original consumer purchaser (“Purchaser”) of its product, EZ Trap®, that it is free from defects in material or workmanship. If within two years (24 months) from the date of the original consumer purchase this product shall prove to be defective, it shall be repaired or replaced at RectorSeal’s option. Your original receipt of purchase is required to determine warranty eligibility.

RectorSeal® 2601 Spenwick Drive - Houston, TX 77055 ph: 713.263.8001 - 800.231.3345 fax: 713.263.7577 - 800.441.0051 www.rectorseal.com - Like Us on Facebook 961735

0

21449 83180

2

INSTALLATION INSTRUCTIONS

EZT-180 1. Trap must be fitted at least 12” below indoor unit (Figure 1). 2. Ensure that Black Valve Assembly is perpendicular to or facing away from wall to facilitate cleaning. 3. For 5/8” (16mm) drain hose, insert end of upper drain hose into top of Trap (Wide End) and seat firmly (Figure 2). 4. For 9/16” (14mm) drain hose, insert Rubber Adaptor into top of Trap and insert hose into Adaptor and seat firmly (Figure 3).

Model EZT-180 83180 EZT-180

Model SLOPE

(EZT180)

12” MINIMUM

Installation instructions

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Figure 1 SLOPE

Figure 1

16mm SLOPE DRAIN HOSE

14mm 12” MINIMUM DRAIN HOSE 12” MINIMUM

WATER FLOW

WATER FLOW

16mm 16mm DRAIN DRAIN HOSEHOSE

14mm DRAIN DRAIN HOSE HOSE

WATER WATER FLOW FLOW

WARNINGS

14mm

Figure 3

EASILY AND SHOULD NOT BE USED FOR THIS WARNINGS WARNINGS APPLICATION. 1. THIS TRAP ISINSTALL DESIGNED 1. THIS TRAP IS DESIGNED 2. DO NOT TRAP FORFOR USEUSE WITH NO-KINK WITH NO-KINK HORIZONTALLY CORRUGATED PE DRAIN CORRUGATED PE DRAIN HOSE (DH-16). THIN WALL UNIT 3. HOSE DRAIN HOSE EXITING (DH-16). THIN WALL VINYL HOSE KINKS VERYTO MUST HAVE SLOPE VINYL HOSE KINKS VERY EASILY AND SHOULD NOT FACILITATE CONDENSATE AND SHOULD NOT BE EASILY USED FOR THIS FLOW BE USED FOR THIS

WATER WATER FLOW FLOW

WATER FLOW

Figure 2

Figure 2

Figure 3

Figure 3 WATER FLOW

WATER 16mm FLOW DRAIN HOSE

WATER FLOW 3”

WATER 16mm FLOW DRAIN HOSE

16mm DRAIN

PVC TAPE

PVC TAPE

WATER FLOW

WATER 14mm FLOW DRAIN HOSE

WATER FLOW 3”

PVC TAPE

3”

Figure 5

Figure 6 14mm DRAIN HOSE

Figure 5 14mm

3”

Figure 6

DRAIN HOSE

Figure 5

Figure 6

FACILITATE CONDENSATE FLOW IMPORTANT NOTES

WATER FLOW

PVC TAPE

APPLICATION. 2. DOAPPLICATION. NOT INSTALL TRAP HORIZONTALLY 2. DO NOT INSTALL TRAP HORIZONTALLY 3. DRAIN HOSE EXITING UNIT MUST HAVEHOSE SLOPE TO 3. DRAIN EXITING UNIT FACILITATE CONDENSATE MUST HAVE SLOPE TO FLOW

3”

PVC TAPE

HOSE4 Figure

Figure 4

3”

PVC TAPE

Figure 4

top of Trap and insert hose into Adaptor and seat firmly (Figure 3). TRAP MUST BE INSTALLED VERTICALLY– CAUTION:

WIDE END AND DOWN – FOR CAUTION: TRAPUP MUST BENARROW INSTALLEDEND VERTICALLY– CONDENSATE FLOW.END INCORRECT INSTALLATION WIDE END UP AND TO NARROW DOWN – FOR WILL CAUSE BACK-UP OF CONDENSATE. CONDENSATE TO FLOW. INSTALLATION 1. THIS TRAPINCORRECT IS DESIGNED WILL CAUSE BACK-UP OF CONDENSATE. 5. Insert bottom end of Trap (Narrow End) into top of lower FOR USE NO-KINK 5. Insertdrain bottom end(Figures of Trap WITH (Narrow End) into top of lower hose 4 & 5). drain hoseCORRUGATED (Figures & 5).connection PE DRAIN 6. Wrap inlet and 4outlet with PVC Tape 6. Wrap(Figure inlet and6). outlet connection with PVC Tape (DH-16). THIN WALL (Figure HOSE 6). 7. Fit Hose/Trap assembly to wall with 2 pipe brackets 7. Fit Hose/Trap assembly to wall with 2 pipe brackets VINYL HOSE KINKS VERY 3” from Trap (Figure 3” from Trap (Figure 5). 5).

Figure 1

Figure 2

CAUTION: TRAP MUST BEEZT-180 INSTALLED VERTICALLY– WIDE END UP AND NARROW END DOWN – FOR 1. Trap must be fitted at least 12” below indoor unit CONDENSATE TO FLOW. INCORRECT INSTALLATION EZT-180 (Figure 1). BACK-UP OF CONDENSATE. WILL CAUSE 2. Ensure Valve is perpendicular to 1. Trap must bethat fittedBlack at least 12”Assembly below indoor unit 5. Insert bottom end of Trap (Narrow End) into top of lower or facing (Figure 1). away from wall to facilitate cleaning. hose (Figures 4hose, & 5). 2. Ensure Black Valvedrain Assembly is insert perpendicular to 3. drain Forthat 5/8” (16mm) end of upper drain hose Wrap inlet and outlet connection withfirmly PVC (Figure Tape or6.facing away to facilitate cleaning. into top offrom Trapwall (Wide End) and seat 2). (Figure 6). 3. For (16mm) drain hose, insert endinsert of upper drainAdaptor hose 4. 5/8” For 9/16” (14mm) drain hose, Rubber into 7. Fit Hose/Trap assembly to wall with 2 pipe brackets into top of Trap (Wide End) and seat firmly (Figure 2). top of Trap and insert hose into Adaptor and seat firmly 4. For 9/16” (14mm) hose,5). insert Rubber Adaptor into 3” from Trap (Figure (Figure 3). drain

1. FOR USE WITH MINISPLIT AIR CONDITIONERS ONLY. 2. REMOVE TRAP BEFORE CLEANING COOLING COIL WITH CHEMICAL CLEANER. 3. DO NOT GLUE THIS TRAP. 4. WHERE POSSIBLE, INSTALL WITHIN 6’ OF GROUND TO FACILITATE INSPECTION AND CLEANING. 5. TRAP IS NOTIMPORTANT REQUIRED IF CONDENSATE PUMP IS FITTED. NOTES 6. CLEAN ATMINISPLIT LEAST ONCE ANNUALLY ORONLY. MORE OFTEN IF 1. FOR USE WITH AIR CONDITIONERS REQUIRED. 2. REMOVE TRAP BEFORE CLEANING COOLING COIL WITH 7. ENSURE THAT BLEED HOLES ARE NOT BLOCKED. CHEMICAL CLEANER. IMPORTANT NOTES IN ACCORDANCE 3. DO THISMUST TRAP. 8.NOT THISGLUE DEVICE BE INSTALLED STRICTLY MANUFACTURER’S INSTRUCTIONS 4. WHERE INSTALL WITHIN 6’ CONDITIONERS OF GROUNDTO TO ENSURE 1. WITH FORPOSSIBLE, USE WITH MINISPLIT AIR ONLY. PROPER FACILITATE INSPECTION AND CLEANING. OPERATION AND IN ACCORDANCE WITH ALL COIL APPLICABLE 2. REMOVE TRAP BEFORE CLEANING COOLING WITH 5. TRAPLOCAL IS NOTPLUMBING, REQUIRED IFDRAINAGE CONDENSATE PUMP ISMECHANICAL FITTED. AND/OR CODES. CHEMICAL CLEANER. 6. CLEAN AT LEAST ONCE ANNUALLY OR MORE OFTEN IF 3. DO NOT GLUE THIS TRAP. REQUIRED. 4. WHERE INSTALL WITHIN 6’ OF GROUND TO 7. ENSURE THATPOSSIBLE, BLEED HOLES ARE NOT BLOCKED. INSPECTION AND CLEANING. 8. THIS FACILITATE DEVICE MUST BE INSTALLED STRICTLY IN ACCORDANCE 5. TRAP IS NOT REQUIRED IF CONDENSATE PUMP IS FITTED. WITH MANUFACTURER’S INSTRUCTIONS TO ENSURE PROPER OPERATION IN ACCORDANCE WITH ALLOR APPLICABLE 6. CLEAN AND AT LEAST ONCE ANNUALLY MORE OFTEN IF LOCAL PLUMBING, DRAINAGE AND/OR MECHANICAL CODES. REQUIRED.

7. ENSURE THAT BLEED HOLES ARE NOT BLOCKED. 8. THIS DEVICE MUST BE INSTALLED STRICTLY IN ACCORDANCE WITH MANUFACTURER’S INSTRUCTIONS TO ENSURE PROPER OPERATION AND IN ACCORDANCE WITH ALL APPLICABLE LOCAL PLUMBING, DRAINAGE AND/OR MECHANICAL CODES.