SUBMITTAL SHEET Model APD

Forced Air Zone Controls

Current Sensing Switch

APPLICATIONS Monitor on/off status of blower motor to: Provide fan proving for S2000 / S2020 Steam Humidifier. Operate Spring type Damper for Fresh Air. Also: Monitor on/off status of various electrical loads. Monitor direct drive units, exhaust fans and other fixed loads.

FEATURES Split core for easy installation. No need to rewire High-Voltage. Mounting bracket provides installation flexibility. Low 0.15 Amp Trip Point. 100% solid-state, no moving parts to fail.

SPECIFICATIONS CORE: Split Type AMPERAGE RANGE: 0.15 - 200A @ 5°F - 140°F OUTPUT TYPE: N.O., Solid State OUTPUT RANGE: 1.0A Max. @ 30V AC/DC HUMIDITY RANGE: 0-95% NON-CONDENSING

0.92” (24 mm)

!

2.87” (73 mm)

This product is not intended for life or safety applications. This product is not intended for installation in hazardous or classified locations.

3.52” (90 mm)

Installing sensors in an energized motor control center or on any energized conductor can be hazardous.

0.68” (17 mm) 2.0” (51 mm)

0.52” (13 mm)

1.28” (33 mm)

Read instructions thoroughly prior to installation.

2.34” (60 mm)

2.0” (51 mm)

Disconnect and lock-out all power sources during installation and service. Applications shown are suggested means of installing sensors, but it is the responsibility of the installer to ensure that the installation is in compliance with all national and local codes. Installation should be attempted only by individuals familiar with codes, standards, and proper safety procedures for high-voltage installations.

2.15” (55 mm)

Excellence Without Compromise

EWC P/N 090377A0122

385 Hwy. 33 Englishtown, NJ 07726 Ph: 800-446-3110 - Fx: 732-446-5362

REV. D 10/2011

Copyright © 2011, Field Controls Inc., All Rights Reserved

Field Controls Inc. 2630 Airport Road Kinston, NC 28504 PH: 252.522.3031 FAX: 252.522.0214 P/N 090377A0122 REV. C Copyright © EWC Controls 2006 All Rights Reserved

CONTROLS INC.

Forced Air Zone Controls SEE WIRING (RIGHT) FOR SPECIFIC APPLICATIONS

POWER SOURCE

SUBMITTAL SHEET Model APD Current Sensing Switch WIRING FOR AIR PROVING ON S2000/S2020 S2000 & S2020 Humidifier Low Voltage Terminal Block G1 R G2 H

BLOWER MOTOR

H

A

A

REMOVE FACTORY JUMPER SEE S2000/S2020 INSTRUCTIONS FOR WIRING SOURCE

LOAD

MODEL APD

FOR AIR PROVING ON BY-PASS OR FLOW-THRU HUMIDIFIER

INSTALLATION 1. Ensure power conductor to be monitored is disconnected and locked out from the power source!

HUMIDIFIER MOTOR OR SOLENOID

2. Install the removable mounting bracket to the back of the electrical enclosure, if desired. C

3. Snap the split core around the conductor to be monitored and close until the core snaps shut. NOTES: To monitor current under .15 Amp see installation note. 4. Connect current switch output to switched load. (See diagrams to the right).

R

MODEL T40-VA 24 VAC TRANSFORMER HUMIDISTAT SOURCE

5. Snap the APD back into the mounting bracket or allow the APD to hang on the conductor. Note: Contacts are solid state and work just like dry contacts. When the switch is closed 1 Ohm is present. When the switch is open more than 1 Megohm is present.

MODEL APD

FOR FRESH AIR WITH ESR DAMPER

6. Reconnect power.

MODEL ND-ESR / URD-ESR POWER OPEN / SPRING CLOSE

INSTALLATION NOTES For currents less than .15 Amp: To provide adequate current, wrap the conductor through the center hole and around the sensor body to produce multiple passes and increase measured current. Measured current = Actual current times the number of passes.

SOURCE

C R

LOAD Excellence Without Compromise

EWC

NO NC C M M

385 Hwy. 33 Englishtown, NJ 07726 Ph: 800-446-3110 - Fx: 732-446-5362

MODEL T40-VA 24 VAC TRANSFORMER SOURCE

MODEL APD

P/N 090377A0122 REV. D 10/2011 © 2011, Field Controls Inc., All Rights Reserved P/N 090377A0122 REV. C CopyrightCopyright © EWC Controls 2006 All Rights Reserved CONTROLS INC. Field Controls Inc. 2630 Airport Road Kinston, NC 28504 PH: 252.522.3031 FAX: 252.522.0214

LOAD

LOAD