Multi F ODU (CHV) - LG DFS

Report 12 Downloads 66 Views
Job Name/Location:

Tag #:

Date:

For:

PO No.: Architect:

GC:

Engr:

Mech:

File

Resubmit

Approval

Other

Rep:

(Company)

(Project Manager)

LMU360HHV

Multi F MAX with LGRED Heat Pump Outdoor Unit Performance:

Cooling (Min‐Rated‐Max, Btu/h)

11,700~36,000~46,733 13,455~41,000~50,200 0.72 ~ 2.40 ~ 3.75 0.96 ~ 2.93 ~ 3.94

Heating (Min‐Rated‐Max, Btu/h) Cooling Power Input (Min‐Rated‐Max, kW)

Heating Power Input (Min‐Rated‐Max, kW) Cooling Nominal Test Conditions: Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB

Electrical: Power Supply (V¹/Hz/Ø) MOP (A)

208‐230/60/1 45

MCA (A) Cooling Rated Amps (A) Heating Rated Amps (A)

25.06 25.06

30.2

20.4 0.73 x 2

MOP ‐ Maximum Overcurrent Protection MCA ‐ Minimum Circuit Ampacity

Piping: 12.34 Ø3/8 x 1 Ø3/4 x 1

Refrigerant Charge (lbs.) Liquid Line (in, OD) Vapor Line  (in, OD) Max Total Piping² (ft) Max ODU to IDU Piping3 (ft) Piping Length4 (no add'l refrigerant, ft) Max Elevation between ODU and IDU (ft) Max Elevation between IDU and IDU (ft)

475.7 229.6 147.6 98.4 49.2

ODU ‐ Outdoor Unit IDU ‐ Indoor Unit

Controls Features: •Auto operation •Auto restart opera. on •Defrost/Deicing

•Inverter (variable speed compressor) •Low ambient operation to 14F (cooling mode)

Optional Accessories: PI‐485 Integration Board ‐ PMNFP14A1 AC Smart IV ‐ PACS4B000 ACP IV - PACP4B000 Power Distribution Indicator ‐  PQNUD1S41 MultiSITE™ CRC1 - PREMTBVC0

•Restart delay (3-minutes) •Self diagnosis •Soft start •Factory installed Drain Pan Heater

AC Smart IV BACnet® Gateway PBACNA000 ACP IV BACnet Gateway ‐ PQNFB17C2 Low Ambient Wind Baffle (Cooling operation to -4°F) - ZLABGP04A x2 2 Port BD Unit ‐ PMBD3620

MultiSITE CM - PBACNBTR0A

3 Port BD Unit ‐ PMBD3630 4 Port BD Unit ‐ PMBD3640 4 Port BD Unit ‐ PMBD3641

Y-Branch - PMBL5620

14 to +118

Heating (°F WB)

-13 to +75

Unit Data:

Net Unit Weight (lbs) Shipping Weight (lbs) Heat Exchanger Coating

R410A EEV

54 / 57 222.7 249.1 GoldFin™

Min Number of Indoor Units Max Number of Indoor Units

2 5

Compressor: Quantity Type

Twin Rotary

Oil/Type

FVC68D

1

Fan: Type Quantity

Propeller

Fan Motor/Drive Airflow Rate (CFM)

2 Brushless Digitally Controlled/Direct 2,119 x 2

Notes: 1. Acceptable operating voltage: 187V‐253V. 2. Piping lengths are equivalent. 3. 180.4 ft of Main Piping + 49.2 ft of Branch Piping. 4. 16 ft of Main Piping + 131 ft of Branch Piping. 5. At least one BD Unit is required for system opera on; a maximum of two can be installed per ODU with use of Y‐branch accessory (PMBL5620). 6. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996. 7. All power/communica on cable to be minimum 16 AWG from the outdoor unit to the BD unit and 18 AWG from the BD unit to the indoor unit. 8. All power/communica on cable to be 4‐conductor, stranded, shielded and must comply  with applicable local and national code. 9. Power wiring cable size must comply with the applicable local and na onal code. 10. See Engineering Manual Capacity Tables for ODU sensible and latent capaci es. 11. See Engineering Manual Combina on Tables for alloca on of ODU rated capacity to  each  connected IDU when all are calling for full capacity.  Allocation percentages should be applied  to ODU capacity at design conditions. 12. This data is rated 0   above sea level, with 115   of refrigerant line and a 0   level difference between outdoor and indoor units.  All capacities are net with a combination ratio  between 95 – 105%. 13. Must follow installa on instruc ons in the applicable LG installa on manual. 14. See Engineering Manual Capacity Tables for ODU capacity at design condi on.

 Required5 Accessories:

MultiSITE CRC1+ - PREMTBVC1 LonWorks® Gateway ‐ PLNWKB100

Cooling (°F DB)

Refrigerant Type Refrigerant Control Sound Pressure³ (Cool/Heat) ±3 dB(A)

Heating Nominal Test Conditions: Indoor: 70°F DB/60°F WB Outdoor: 47°F DB/43°F WB

Compressor (A) Fan Motor (A)

Operating Range:

BACnet® is a registered trademark of ASHRAE. LonWorks is a trademark of Echelon Corporation.

For a complete list of available accessories, contact your LG representative. For continual product development, LG reserves the right to change specifications without notice. ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com.

SB_MultiF_MAX_LGRED_HP_LMU360HHV_2017_10_19_094903

Page 1 of 3

Job Name/Location:

LMU360HHV Multi F MAX with LGRED Heat Pump Outdoor Unit

Tag #: Date: PO No.:

For continual product development, LG reserves the right to change specifications without notice. ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com.

SB_MultiF_MAX_LGRED_HP_LMU360HHV_2017_10_19_094903

Page 2 of 3

Job Name/Location:

LMU360HHV

Multi F MAX with LGRED Heat Pump Outdoor Unit

Tag #: Date: PO No.:

For continual product development, LG reserves the right to change specifications without notice. LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

SB_MultiF_MAX_LGRED_HP_LMU360HHV_2017_10_19_094903

Page 3 of 3