OAC-P, MicroSet Passive Infrared Ceiling Sensor Low Voltage PIR Activated

MicroSet Self-Adjusting

• MicroSet self-adjusting Time Delay and sensitivity

• Optional BAS/HVAC isolated relay • NEMA WD7 Standard robotic method utilized to verify coverage patterns • Selectable Walk Through Mode

Specifications: Technology: Passive Infrared (PIR)) Power Requirements: Input: • 10-30 VDC from Greengate Switchpack or Greengate system. • Maximum current needed is 25mA per sensor. Output: • Open collector output to switch up to ten Greengate Switchpacks. • BAS with Isolated Form C Relay in (-R) model. • Isolated Form C Relay Ratings: 1A 30 VDC/VAC. Time Delays: Self-adjustable, 15 seconds/test (10 min. Auto), or Selectable 5, 15, 30 minutes, or Zero Time Delay Coverage: 500 and 1500 sq. ft. Light Level Sensing (-R models): 0 to 300 footcandles Operating Environment: • Temperature: 32°F - 104°F (0°C - 40°C) • Relative humidity: 20% to 90%, non-condensing • For indoor use only Housing: Durable, injection molded housing. Polycarbonate resin complies with UL 94V0. Size: 4.5”H x 1.42”W (114.3mm x 36.068mm) LED lamp: Red LED for Passive Infrared Warranty: Five year

Overview The MicroSet Passive Infrared Low Voltage Occupancy Sensing Ceiling Sensor is a motion sensing lighting control that is used for energy savings and convenience. Technology The sensor is designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON. These sensors have multi-segmented lenses. For units to sense motion, the person must cross between two segments. The distance between segments increases the farther you are from the sensor, so motion has to be larger the farther you are from the unit. PIR sensors are considered Line-of sight sensors, meaning that the sensor must be able to have a direct Line-of-sight to the person making the motion. The sensor includes self-adaptive technology that continuously self-adjusts sensitivity and Time Delay in real-time, maximizing the potential energy savings that are available in the particular application. In Automatic ON Mode, the lights turn ON when a person enters the room. In Manual ON Mode (-R model only), the lights are turned ON by activating a momentary switch (model # GMDS-*) that is connected to the sensor. The MicroSet Passive Infrared Low Voltage Ceiling Sensor has an ambient light level sensor. When enabled, the daylighting feature (-R units only) prevents lights from turning ON when the room is adequately illuminated by natural light. Applications conference rooms

common areas

open office areas

break rooms

small private offices

restrooms (non-partitioned)

Ordering Catalog #

Recommended Room Size

Field of View

OAC-P-0500-R

500 sq.ft.

360°

OAC-P-0500

500 sq.ft.

360°

OAC-P-1500-R

1500 sq.ft.

360

OAC-P-1500

1500 sq.ft.

360°

FCC Compliant cULus Listed RoHS Compliant

www.coopercontrol.com

utility closets

203 Cooper Circle Peachtree City, GA 30269

P: 800-553-3879 F: 800-954-7016

Features w/BAS Relay & Daylight Sensor

w/BAS Relay & Daylight Sensor

Occupancy Sensors - Ceiling Mount

• Optional built-in light level sensor

OAC-P, MicroSet PIR Low Voltage

Wiring Diagrams One Sensor, One Switchpack

Manual or Automatic-On Control of Two Standard Switchpacks Hot Hot

Line Line

Neutral

SWITCHPACK

Red (15 VDC) Blue (Control) Black (Common)

Blue

SWITCHPACK

Red (15 VDC) Blue (Control) Black (Common)

White

Load

Blue

**Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead.

**Hot

Blue

White

Neutral

**Hot

**Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead.

Load 1

Blue

Hot Red Blue Black Brown Yellow Purple Gray Orange White/Brown

Neutral **Use black lead for 120 VAC Use orange lead for 277 VAC Cap unused lead.

Red (15 VDC) Blue (Control) Black (Common)

Manual Mode Operation: Switches are required to turn corresponding loads ON. Lights turn OFF when sensor times out or with the switch. Automatic Mode Operation: Sensor turns ON both switchpacks. Switches can be used to turn lights ON or OFF. If daylight sensor is enabled and light level is above setpoint, switchpack connected to yellow lead will not turn ON. Recommended Wire: 18-3 AWG Stranded Wire non/shielded.

SENSOR WIRE LEAD LEGEND (Common) Black (10-30VDC) Red (Control - Occupancy) Blue (Control - Occupancy and Daylight) Yellow (Switch-Blue Lead Control) Brown Brown/White (Switch-Yellow Lead Control) Sensor's Isolated Relay Orange (Normally Open) (Common) Gray (Normally Closed) Purple Recommended Wire: 18-3 AWG stranded non-shielded

SWITCHPACK

White

To additional switchpacks Maximum of 10 switchpacks per sensor

Line

Blue

To additional sensors Maximum of 5 sensors per switchpack

**Hot

Red Blue Black

Load 2

Blue

Model GMDS - Load 2 (Normally Open Momentary Switch) Model GMDS - Load 1 (Normally Open Momentary Switch)

(Use GMDS Switch Only in Single Sensor Applications)

Coverage OAC-P-1500-R

OAC-P-0500-R

1500 sq. ft.

20 ft (6.096m)

500 sq. ft.

7 ft (2.13 m)

15 ft (4.57 m)

5 ft (1.5 m)

10 ft (3 m)

5 ft (1.5 m)

0 0

DT1k

5 ft (1.5 m)

5 ft (1.5 m)

10 ft (3 m)

7 ft (2.13 m)

15 ft (4.57 m)

8.5 ft (2.59 m) 20 ft (6.096m) 8.5 ft (2.59 m)

3 ft (0.91) 0

3 ft (0.91) 0

0

7 ft 5 ft (2.13 m) (1.5 m) 20 ft (6.096m)

15 ft (4.57 m)

10 ft (3 m)

5 ft (1.5 m)

0

5 ft (1.5 m)

10 ft (3 m)

15 ft (4.57 m)

5 ft 7 ft (1.5 m) (2.13 m)

20 ft (6.096m)

Minor Motion, IR

Recommended Mounting Height: 8 to 12 ft

Major Motion, IR

Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. The NEMA WD 7 Standard and robotic method were utilized to verify coverage patterns.

Controls

LEDs

(-R model only)

(-R model only)

Full/Half Logic

(-R model only)

PIR Detector

ON

ACC120011

Sweep

Daylight Sensor Adjustment

1 2 3 4 5 6

www.coopercontrol.com 203 Cooper Circle, Peachtree City, GA 30269 P: 800-553-3879 F: 800-954-7016

Override

7 8 9 10 11 12

Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, Revio, Ineo, TracKeeper, IntelliRelay are valuable trademarks of Cooper Industries in the U.S and other countries. You are not permitted to use Cooper Trademarks without the prior written consent of Cooper Industries.

HVAC/Tracking

(-R model only)

Zero Time Delay