Overvoltage & EMI Protection for Home and Office Overvoltage & EMI ...

Report 3 Downloads 98 Views
Overvoltage & EMI Protection for Home and Office Overvoltage Protection Class III EMI protection Sensitive electronic equipment protection Protection solutions for EIB and servers DIN rail mounting

BE ON THE SAFE SIDE

PROFILT D

Overvoltage & EMI Protection for Home and Office

Category IEC/EN/VDE:

Class III / Type 3 / C

Location of use:

Branch sub-distribution box

Connection:

TN-S, TT

Protection modes:

L/N - PE

Protective elements:

MOV, GDT and EMI filter

Surge discharge rating: Uoc/Isc = 6kV/3kA Fault indication:

Light

Complies with:

IEC-61643-1

Product Profilt D 8A is an electromagnetic interference (EMI) and overvoltage protective device of class III. It is designed for complete protection and is installed directly in front of protected devices on DIN rail. Protected electrical device is safe against effects of overvoltage, electrostatic voltage and electromagnetic interferences. These disturbances, which are present in all electrical systems, are caused by other electrical devices, by switching maneuvers, by defects in electrical network and by other activities, such as welding. PROFILT D protect devices such as: - TV - PC - EIB installation - Server - Control and regulation devices Technical characteristics PROFILT D 8A

Type

Max. continuous operating voltage (AC/DC)

Uc

275 V / 50 Hz

Max. load current

IL

8A

Combination wave (1.2/50, 8/20)

Uoc/Isc

Protection lavel

Up

6 kV / 3 kA ≤ 800 V < 70 dB @ 5MHz

Asymetrical attenuation Mechanical characteristics

1.5 mm2 (stranded)

Terminal cross section

Thermoplastic

Housing

33 x 90 x 57 mm

Dimensions (W x H x D) Ordering code

130 061

For effective surge protection we recommend installation of SPD class I and II in electrical distribution board.

ISKRA ZAŠČITE, d.o.o., Surge Voltage Protection Systems, Engineering and Cooperation Stegne 35, 1521 Ljubljana, SLOVENIA T: +386(1)5003 100; F: +386(1)5003 236; E: [email protected] www.iskrazascite.si

Published by: ISKRA ZA[^ITE, d.o.o. / March 2011 /

Electrical characteristics