PIZZATO CS ME EXPANSION MODULES WITH INSTANTANEOUS CONTACTS OR DELAYED CONTACTS AT DE ENERGIZING

5G

Expansion module CS ME-01 Technical data Housing Made of polyamide PA 6.6 self-extinguishing, class V0 (UL94) Protection degree: IP40 (housing), IP20 (terminals) Dimensions: see page 5/81, shape A

Expansion modules with output contacts Main functions • For safety applications up to SIL 3 / PL e • Possibility of control with 1 or 2 channels • Connection of the input channels to opposite potentials • Small 22,5 mm housing • Output contacts: 5 NO safety contacts, 1 NC auxiliary contact, 1 NC feedback contact • Supply voltages: 24 Vac/dc

Utilization categories Alternate current: AC15 (50...60 Hz) Ue (V) 230 Ie (A) 3 Direct current: DC13 (6 operations/minute) Ue (V) 24 Ie (A) 4

up to SIL 3 according to EN IEC 62061 up to PL e according to EN ISO 13849-1 up to cat. 4 according to EN ISO 13849-1 (dependent on the base module) see page 7/34 -25°C...+55°C >10 millions of operations >100.000 operations outside 3, inside 2 4 kV 250 V II 0,3 kg

Power supply Rated operating voltage (Un): Max residual ripple in DC: Supply voltage tolerance: Rated power consumption AC: Rated power consumption DC:

24 Vac/dc; 50...60 Hz 10% 15% of Un < 5 VA < 2W

Control circuit Protection against short circuits: Operating time of PTC: Max input resistance: Operating time tA: Releasing time in absence of power supply tR:

resistance PTC, Ih=0,5 A intervention > 100 ms, reset > 3 s 50 < 40 ms < 40 ms

In conformity with standards: IEC 60947-1, EN 60947-5-1, IEC 60204-1, EN 60204-1, EN ISO 13849-1, EN 999, EN 1037, EN ISO 12100-1, EN ISO 12100-2, EN ISO 13850, IEC 529, EN 60529, EN 61000-6-2, EN 61000-6-3, EN 62326-1, EN 60664-1, EN 60947-5-1, EN 62061, EN 13849-1, UL 508, CSA C22.2 n° 14-95

Markings, quality marks and certificates:

Approval UL: Approval GOST:

General data SIL level (SIL CL): Performance Level (PL): Safety category: Safety parameters: Ambient temperature: Mechanical endurance: Electrical endurance: Pollution degree: Rated impulse with stand voltage (Uimp): Rated insulation voltage (Ui): Over-voltage category: Weight:

Output circuit Output contacts: Contacts type: Contacts material: Max switching voltage: Max switching current per contact: Conventional free air thermal current Ith: Max currents sum Σ Ith2: Min. current: Contacts resistance: Contact protection fuse:

E131787 POCC IT.AB24.B04512

Complying with the requirements requested by: Low Voltage Directive 2006/95/EC, Machinery Directive 2006/42/EC, Electromagnetic Compatibility 2004/108/EC

5 NO safety contacts, 1 NC auxiliary contact, 1 NC feedback contact forced guided contacts silver alloy, gold plated 230/240 Vac; 300 Vdc 6A 6A 72 A2 10 mA 100 m 6 A, F type

Code structure

CS ME-01V024 Kind of connection V

screw terminals

M

connector with screw terminals

X

connector with spring terminals

Supply voltage 024 24 Vac/dc

Data type approved by UL 15%

Rated operating voltage (Un): Rated power consumption AC: Rated power consumption DC: Max switching voltage: Max switching current per contact: Utilization category

24 Vac/dc; 50...60 Hz < 5 VA < 2W 230 Vac 6A C300

Notes: - Use 60° or 75 °C copper (Cu) conductor and wire size No. 30-12 AWG. - Terminal tightening torque of 5-7 Lb In. - Only for 24 Vac/dc version, supply from remote class 2 source or limited voltage and limited energy.

5/51

General Catalog 2013-2014

5G Expansion module CS ME-01 Operations diagram

Terminals layout

13

23

33

Y1 A1/A2 A1

43

53

61 Y1/Y2 13/14, 23/34, 43/44, 53/54 61/62

CH1 CH2

tA

A2 44 14

24

34

54

tR

Legend: tA: Operating time tR: Releasing time in absence of power supply

62

Y2

Internal wiring diagram L/+ A1

13

23

33

43

53

61

Y1

14

24

34

44

54

62

Y2

LED CH1 K1

K2

LED CH2

A2

N/-

Inputs configuration 1 channel control

2 channels control

L/+

L/+ Manual and monitored start wiring

Manual and monitored start wiring

F

F

Automatic start wiring

13

Automatic start wiring

Y1

Start, reset and/or feedback input Base module

23

Y2

13

CS ME-01 Expansion module

14

N/-

A1

Y1

Start, reset and/or feedback input Base module

A2

24

14

Y2

CS ME-01 Expansion module

A1

A2

N/-

The diagram does not show the exact position of clamps in the product

General Catalog 2013-2014

5/52

5G

Expansion module CS ME-02 Technical data Housing Made of polyamide PA 6.6 self-extinguishing, class V0 (UL94) Protection degree: IP40 (housing), IP20 (terminals) Dimensions: see page 5/81, shape A

Expansion modules with output contacts Main functions • For safety applications up to SIL 3 / PL e • Possibility of control with 1 or 2 channels • Connection of the input channels to opposite potentials • Small 22,5 mm housing • Output contacts: 4 NO safety contacts, 2 NC auxiliary contact, 1 NC feedback contact • Supply voltages: 24 Vdc

Utilization categories Alternate current: AC15 (50...60 Hz) Ue (V) 230 Ie (A) 3 Direct current: DC13 (6 operations/minute) Ue (V) 24 Ie (A) 4 Markings, quality marks and certificates:

Approval UL: Approval GOST:

E131787 POCC IT.AB24.B04512

Complying with the requirements requested by: Low Voltage Directive 2006/95/EC, Machinery Directive 2006/42/EC, Electromagnetic Compatibility 2004/108/EC

General data SIL level (SIL CL): Performance Level (PL): Safety category: Safety parameters: Ambient temperature: Mechanical endurance: Electrical endurance: Pollution degree: Rated impulse with stand voltage (Uimp): Rated insulation voltage (Ui): Over-voltage category: Weight:

up to SIL 3 according to EN IEC 62061 up to PL e according to EN ISO 13849-1 up to cat. 4 according to EN ISO 13849-1 (dependent on the base module) see page 7/34 -25°C...+55°C >10 millions of operations >100.000 operations outside 3, inside 2 2,5 kV 250 V II 0,3 kg

Power supply Rated operating voltage (Un): Max residual ripple in DC: Supply voltage tolerance: Rated power consumption DC:

24 Vdc 10% 15% of Un < 2W

Control circuit Protection against short circuits: Operating time of PTC: Max input resistance: Operating time tA: Releasing time in absence of power supply tR:

resistance PTC, Ih=0,5 A intervention > 100 ms, reset > 3 s 50 < 100 ms < 60 ms

In conformity with standards: IEC 60947-1, EN 60947-5-1, IEC 60204-1, EN 60204-1, EN ISO 13849-1, EN 999, EN 1037, EN ISO 12100-1, EN ISO 12100-2, EN ISO 13850, IEC 529, EN 60529, EN 61000-6-2, EN 61000-6-3, EN 62326-1, EN 60664-1, EN 60947-5-1, EN 62061, EN 13849-1, UL 508, CSA C22.2 n° 14-95 Output circuit Output contacts: Contacts type: Contacts material: Max switching voltage: Max switching current per contact: Conventional free air thermal current Ith: Max currents sum Σ Ith2: Min. current: Contacts resistance: Contact protection fuse:

4 NO safety contacts, 2 NC auxiliary contact, 1 NC feedback contact forced guided contacts silver alloy, gold plated 230/240 Vac; 300 Vdc 6A 6A 64 A2 10 mA 100 m 6 A, F type

Code structure

CS ME-02VU24 Kind of connection V

screw terminals

M

connector with screw terminals

X

connector with spring terminals

Supply voltage U24 24 Vdc

Data type approved by UL 15%

Rated operating voltage (Un): Rated power consumption DC: Max switching voltage: Max switching current per contact: Utilization category

24 Vdc < 2W 230 Vac 6A C300

Notes: - Use 60° or 75 °C copper (Cu) conductor and wire size No. 30-12 AWG. - Terminal tightening torque of 5-7 Lb In. - Only for 24 Vdc version, supply from remote class 2 source or limited voltage and limited energy.

5/53

General Catalog 2013-2014

5G Expansion module CS ME-02 Operations diagram

Terminals layout

13

23

33

Y1 A1/A2 A1

43

51

61 Y1/Y2 13/14, 23/34, 33/34, 43/44 51/52, 61/62

CH1 CH2

tA

A2 44 14

24

34

52

tR

Legend: tA: Operating time tR: Releasing time in absence of power supply

62

Y2

Internal wiring diagram + A1

13

23

33

43

51

61

Y1

14

24

34

44

52

62

Y2

LED CH1 K1

LED CH2

K2

A2

-

Inputs configuration 1 channel control

2 channels control

L/+

L/+ Manual and monitored start wiring

Manual and monitored start wiring

F

F

Automatic start wiring

13

Automatic start wiring

Y1

Start, reset and/or feedback input Base module

23

Y2

13

CS ME-02 Expansion module

14

N/-

A1

Y1

Start, reset and/or feedback input Base module

A2

24

14

Y2

CS ME-02 Expansion module

A1

A2

N/-

The diagram does not show the exact position of clamps in the product

General Catalog 2013-2014

5/54

5G

Expansion module CS ME-03 Technical data Housing Made of polyamide PA 6.6 self-extinguishing, class V0 (UL94) Protection degree: IP40 (housing), IP20 (terminals) Dimensions: see page 5/82, shape D

Expansion modules with output contacts Main functions • For safety applications up to SIL 3 / PL e • Module for solid-state output circuits (optical barriers type 2 and 4) • 2 OSSD inputs • Small 22,5 mm housing • Output contacts: 3 NO safety contacts, 1 NC feedback contact/EDM contact • Supply voltages: 24 Vdc

Utilization categories Alternate current: AC15 (50...60 Hz) Ue (V) 230 Ie (A) 3 Direct current: DC13 (6 operations/minute) Ue (V) 24 Ie (A) 4 Markings, quality marks and certificates:

Approval UL: Approval GOST:

E131787 POCC IT.AB24.B04512

Complying with the requirements requested by: Low Voltage Directive 2006/95/EC, Machinery Directive 2006/42/EC, Electromagnetic Compatibility 2004/108/EC

General data SIL level (SIL CL): Performance Level (PL): Safety category: Safety parameters: Ambient temperature: Mechanical endurance: Electrical endurance: Pollution degree: Rated impulse with stand voltage (Uimp): Rated insulation voltage (Ui): Over-voltage category: Weight:

up to SIL 3 according to EN IEC 62061 up to PL e according to EN ISO 13849-1 up to cat. 4 according to EN ISO 13849-1 (dependent on the solid-state output circuits) see page 7/34 -25°C...+55°C >10 millions of operations >100.000 operations outside 3, inside 2 4 kV 250 V II 0,2 kg

Power supply Rated operating voltage (Un): Max residual ripple in DC: Supply voltage tolerance: Rated power consumption DC: Start power consumption:

24 Vdc 10% 20% of Un < 2W < 3W

Control circuit Operating time tA: Releasing time tR1:

< 40 ms < 15 ms

In conformity with standards: IEC 60947-1, EN 60947-5-1, IEC 60204-1, EN 60204-1, EN ISO 13849-1, EN 999, EN 1037, EN ISO 12100-1, EN ISO 12100-2, EN ISO 13850, IEC 529, EN 60529, EN 61000-6-2, EN 61000-6-3, EN 62326-1, EN 60664-1, EN 60947-5-1, EN 62061, EN 13849-1, UL 508, CSA C22.2 n° 14-95 Output circuit Output contacts: Contacts type: Contacts material: Max switching voltage: Max switching current per contact: Conventional free air thermal current Ith: Max currents sum Σ Ith2: Min. current: Contacts resistance: Contact protection fuse:

3 NO safety contacts, 1 NC feedback contact forced guided contacts silver alloy, gold plated 230/240 Vac; 300 Vdc 6A 6A 36 A2 10 mA 100 m 6 A, F type

Code structure

CS ME-03VU24 Kind of connection V

screw terminals

M

connector with screw terminals

X

connector with spring terminals

Supply voltage U24 24 Vdc

Data type approved by UL 15%

Rated operating voltage (Un): Rated power consumption DC: Max switching voltage: Max switching current per contact: Utilization category

24 Vdc < 2W 230 Vac 6A C300

Notes: - Use 60° or 75 °C copper (Cu) conductor and wire size No. 30-12 AWG. - Terminal tightening torque of 5-7 Lb In. - Only for 24 Vac/dc version, supply from remote class 2 source or limited voltage and limited energy.

5/55

General Catalog 2013-2014

5G Expansion module CS ME-03 Operations diagram

Terminals layout

13

23

33 EDM

OS1 A2 OS1 OS2 OS2 13/14, 23/34, 33/34 EDM/EDM

CH1 CH2

tA

tR1

Legend: tA: Operating time tR1: Releasing time 14

24

34 EDM

Internal wiring diagram + OS1

OS2

13

23

33

EDM

14

24

34

EDM

LED CH1 K1

K2

LED CH2

A2

-

Inputs configuration Solid-state output circuits (for example optical barriers) 1 channel

2 channels

+

+ ESPE (PNP)

24 VDC

EDM

-

EDM

EDM

OS1

ESPE (PNP)

24 VDC

OSSD

EDM

-

OS2

CS ME-03

EDM

EDM

OSSD1 OSSD2

OS1

OS2

CS ME-03 A2

A2

The diagram does not show the exact position of clamps in the product

General Catalog 2013-2014

5/56

5G

Expansion module CS ME-20 Technical data Housing Made of polyamide PA 6.6 self-extinguishing, class V0 (UL94) Protection degree: IP40 (housing), IP20 (terminals) Dimensions: see page 5/81, shape A

Expansion module with delayed contacts at de-energizing Main functions • For safety applications up to SIL 3 / PL e • Possibility of control with 1 or 2 channels • 4 delayed time 0,5 - 1 - 2 and 3 s • Small 22,5 mm housing • Output contacts: 4 NO safety contacts, 2 NC auxiliary contact, 1 NC feedback contact • Supply voltages: 24 Vdc

Utilization categories Alternate current: AC15 (50...60 Hz) Ue (V) 230 Ie (A) 3 Direct current: DC13 (6 operations/minute) Ue (V) 24 Ie (A) 4 Markings, quality marks and certificates:

Approval UL: Approval GOST:

E131787 POCC IT.AB24.B04512

Complying with the requirements requested by: Low Voltage Directive 2006/95/EC, Machinery Directive 2006/42/EC, Electromagnetic Compatibility 2004/108/EC

General data SIL level (SIL CL): Performance Level (PL): Safety category: Safety parameters: Ambient temperature: Mechanical endurance: Electrical endurance: Pollution degree: Rated impulse with stand voltage (Uimp): Rated insulation voltage (Ui): Over-voltage category: Weight:

up to SIL 3 according to EN IEC 62061 up to PL e according to EN ISO 13849-1 up to cat. 4 according to EN ISO 13849-1 (dependent on the base module) see page 7/34 -25°C...+55°C >10 millions of operations >100.000 operations outside 3, inside 2 2,5 kV 250 V II 0,2 kg

Power supply Rated operating voltage (Un): Max residual ripple in DC: Supply voltage tolerance: Rated power consumption DC:

24 Vdc 10% 15% of Un < 2W

Control circuit Max input resistance: Operating time tA: Releasing time in absence of power supply tR:

50 < 100 ms see Code structure

In conformity with standards: IEC 60947-1, EN 60947-5-1, IEC 60204-1, EN 60204-1, EN ISO 13849-1, EN 999, EN 1037, EN ISO 12100-1, EN ISO 12100-2, EN ISO 13850, IEC 529, EN 60529, EN 61000-6-2, EN 61000-6-3, EN 62326-1, EN 60664-1, EN 60947-5-1, EN 62061, EN 13849-1, UL 508, CSA C22.2 n° 14-95 Output circuit Output contacts: Contacts type: Contacts material: Max switching voltage: Max switching current per contact: Conventional free air thermal current Ith: Max currents sum Σ Ith2: Min. current: Contacts resistance: Contact protection fuse:

4 NO safety contacts, 2 NC auxiliary contact, 1 NC feedback contact forced guided contacts silver alloy, gold plated 230/240 Vac; 300 Vdc 6A 6A 64 A2 10 mA 100 m 6 A, F type

Code structure

CS ME-20VU24-TF1 Kind of connection V

screw terminals

M

connector with screw terminals

X

connector with spring terminals

Releasing time on de-energisation (tR) TF05 fixed 0,5 s TF1 fixed 1 s

Data type approved by UL Rated operating voltage (Un): Rated power consumption DC: Max switching voltage: Max switching current per contact: Utilization category

24 Vdc < 2W 230 Vac 6A C300

TF2 fixed 2 s TF3 fixed 3 s Notes: - Use 60° or 75 °C copper (Cu) conductor and wire size No. 30-12 AWG. - Terminal tightening torque of 5-7 Lb In. - Supply from remote class 2 source or limited voltage and limited energy.

5/57

General Catalog 2013-2014

5G Expansion module CS ME-20 Operations diagram

Terminals layout

17

27

37

Y1 A1/A2 A1

47

55

65 Y1/Y2 17/18, 27/28, 37/38, 47/48 55/56, 65/66

CH1 CH2

tA

A2 48 18

28

38

56

tR

Legend: tA: Operating time tR: Releasing time in absence of power supply (see “Code structure”)

66

Y2

Internal wiring diagram + A1

LED CH1

17

27

37

47

55

65

Y1

18

28

38

48

56

66

Y2

C1 K1

LED CH2

C2

K2

A2

-

Inputs configuration 1 channel control

2 channels control

+

+ Manual and monitored start wiring

Manual and monitored start wiring

F

F

Automatic start wiring

13

Automatic start wiring

Y1

Start, reset and/or feedback input Base module

23

Y2

13

CS ME-20 Expansion module

14

-

A1

Y1

Start, reset and/or feedback input Base module

A2

24

14

Y2

CS ME-20 Expansion module

A1

A2

-

The diagram does not show the exact position of clamps in the product

General Catalog 2013-2014

5/58

5G

Expansion module CS ME-30 / CS ME-31 Technical data Housing Made of polyamide PA 6.6 self-extinguishing, class V0 (UL94) Protection degree: IP40 (housing), IP20 (terminals) Dimensions: see page 5/82, shape C

Expansion module with delayed contacts at de-energizing Main functions • For safety applications up to SIL 3 / PL e • Possibility of control with 1 or 2 channels • Fixed or adjustable delayed time • 45 mm housing • Output contacts: 4 NO safety contacts, 2 NC auxiliary contact, 1 NC feedback contact • Supply voltages: 24 Vdc

Utilization categories Alternate current: AC15 (50...60 Hz) Ue (V) 230 Ie (A) 3 Direct current: DC13 (6 operations/minute) Ue (V) 24 Ie (A) 4 Markings, quality marks and certificates:

Approval UL: Approval GOST:

E131787 POCC IT.AB24.B04512

Complying with the requirements requested by: Low Voltage Directive 2006/95/EC, Machinery Directive 2006/42/EC, Electromagnetic Compatibility 2004/108/EC

General data SIL level (SIL CL): Performance Level (PL): Safety category: Safety parameters: Ambient temperature: Mechanical endurance: Electrical endurance: Pollution degree: Rated impulse with stand voltage (Uimp): Rated insulation voltage (Ui): Over-voltage category: Weight:

up to SIL 3 according to EN IEC 62061 up to PL e according to EN ISO 13849-1 up to cat. 4 according to EN ISO 13849-1 (dependent on the base module) see page 7/34 -25°C...+55°C >10 millions of operations >100.000 operations outside 3, inside 2 2,5 kV 250 V II 0,4 kg

Power supply Rated operating voltage (Un): Max residual ripple in DC: Supply voltage tolerance: Rated power consumption DC:

24 Vdc 10% 15% of Un < 2W

Control circuit Max input resistance: Operating time tA: Releasing time in absence of power supply tR:

50 < 200 ms see Code structure

In conformity with standards: IEC 60947-1, EN 60947-5-1, IEC 60204-1, EN 60204-1, EN ISO 13849-1, EN 999, EN 1037, EN ISO 12100-1, EN ISO 12100-2, EN ISO 13850, IEC 529, EN 60529, EN 61000-6-2, EN 61000-6-3, EN 62326-1, EN 60664-1, EN 60947-5-1, EN 62061, EN 13849-1, UL 508, CSA C22.2 n° 14-95 Output circuit Output contacts: Contacts type: Contacts material: Max switching voltage: Max switching current per contact: Conventional free air thermal current Ith: Max currents sum Σ Ith2: Min. current: Contacts resistance: Contact protection fuse:

4 NO safety contacts, 2 NC auxiliary contact, 1 NC feedback contact forced guided contacts silver alloy, gold plated 230/240 Vac; 300 Vdc 6A 6A 64 A2 10 mA 100 m 6 A, F type

Code structure

CS ME-30VU24-TF1 Fixed or adjustable time 0

Fixed time

1

Adjustable time

Kind of connection V

screw terminals

M

connector with screw terminals

X

connector with spring terminals

5/59

Releasing time on de-energisation (tR) fixed 1 s TF1 (CS ME-30 only) ... ......... fixed 12 s TF12 (CS ME-30 only) from 1 to 12 s, step 1 s TS12 (CS ME-31 only)

Data type approved by UL Rated operating voltage (Un): Rated power consumption DC: Max switching voltage: Max switching current per contact: Utilization category

24 Vdc < 2W 230 Vac 6A C300

Notes: - Use 60° or 75 °C copper (Cu) conductor and wire size No. 30-12 AWG. - Terminal tightening torque of 5-7 Lb In. - Supply from remote class 2 source or limited voltage and limited energy.

General Catalog 2013-2014

5G Expansion module CS ME-30 / CS ME-31 Operations diagram

Terminals layout 17

27

37

Y1

17

27

37

Y1

A1

47

55

65

A1

47

55

65

A1/A2

ITALY

ITALY

POWER

POWER

CH1

CH1

CH2

CH2

A2 48

56

66

A2 48

56

66

18

38

Y2

18

38

Y2

28

Y1/Y2 17/18, 27/28, 37/38, 47/48

28

CS ME-30

55/56, 65/66

tA

tR

Legend: tA: Operating time tR: Releasing time in absence of power supply (see “Code structure”)

CS ME-31

Release time selection tR (CS ME-31 only) DIP SWITCH

Internal wiring diagram + 17

A1

LED CH1

27

47

37

55

65

Y1

C1 K1

LED CH2

C2

K2

18

A2

28

38

48

56

66

Y2

-

tR (s)

ON OFF

1

ON OFF

2

ON OFF

3

ON OFF

4

ON OFF

5

ON OFF

6

ON OFF

7

ON OFF

8

ON OFF

9

ON OFF

10

ON OFF

11

ON OFF

12

Inputs configuration 1 channel control

2 channels control

+

+ Manual and monitored start wiring

Manual and monitored start wiring

F

F

Automatic start wiring

13

Automatic start wiring

Y1

Start, reset and/or feedback input Base module

23

Y2

13

CS ME-30 / CS ME-31 Expansion module

14

-

A1

Y1

Start, reset and/or feedback input Base module

A2

24

14

Y2

CS ME-30 / CS ME-31 Expansion module

A1

A2

-

The diagram does not show the exact position of clamps in the product

General Catalog 2013-2014

5/60