R8845U Universal Switching Relay INSTALLATION INSTRUCTIONS

APPLICATION

Contact Ratings: 7.4 AFL, 44.4 ALR on each set of line voltage contacts; maximum connected load is 2000 VA.

The R8845U Universal Switching Relay provides intermediate switching of line- and low-voltage devices from a line- or low-voltage controller. The R8845U may be used to replace several Honeywell or competitive switching relays and is typically applied in hydronic heating systems.

Switching Action: 2 Spst, plus Powerpile® rated low-voltage Spst. If normally closed contacts are needed, use RA889A Switching Relay. Electrical Connections: No. 8 captivated wire clamp screw terminals.

SPECIFICATIONS

Dimensions: See Fig. 1.

Electrical Ratings: Voltage: 120 Vac, 60 Hz. Thermostat Heat Anticipator Setting: 0.12A.

Cross Reference: The R8845U replaces Honeywell models R182A,B,C,J; R482A,B,C,J; R845A, R882A,B,C,J and RA832A, as well as several competitive models. See Table 1 for additional cross reference information.

Transformer Ratings: Primary: 120V, 60 Hz. Secondary: 24 Vac, 12 VA maximum; 9 VA available for external loads. Output protected by replaceable 1A automotive fuse.

Replacement Parts: 32002190-001 Replacement Relay. Replacement Fuse: Use a 1A automotive fuse.

Table 1. R8845U Replacement Cross Reference. Connections Manufacturer

Model

Input Line Power Relay Voltage 1

Honeywell R8845U

L1

L2

Honeywell R845A

1

Honeywell RA832A

1

Honeywell R182A

Power Relay 2

Low Voltage Relay

A

B

X1

X2

W(T)

R(T)

C

— —

Thermostat

Comments

COM

N.O.

2

3

4

5

6





T

T



2



3



4

X

X

T

T

— Jumper L1 to COM and A in R8845U.

1

2

7

8









Honeywell R182B

1

3

6

8









Honeywell R182C

1

2

6

8

3

5





Honeywell R182J

L1

L2



4



7





Honeywell R482A

1

2

7

8









See Fig. 8 thermostat connections.

R8845U has lower output load rating. Check load requirements. Use RA889A if normally closed contacts are required.

If used to replace an R182J, install a jumper between L1, COM and A. Jumper R(T) to W(T).

Line voltage switched inputs go to L1 and L2. See Fig. 9B.

(continued)

®U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • All Rights Reserved

X-XX UL

69-1292

R8845U UNIVERSAL SWITCHING RELAY

Table 1. R8845U Replacement Cross Reference (Continued). Connections Manufacturer

Model

Input Line Power Relay Voltage 1

Power Relay 2

Low Voltage Relay

Thermostat

Comments

Honeywell R482B

1

2

6

8









Jumper R(T) to W(T) (continued).

Honeywell R482C

1

2

6

8

3

5





Honeywell R482J

1

2

6

8

3

4





Honeywell R882A





7

8









W



B

R8845U has lower output load rating. Check load requirements.

Honeywell R882B





6

8









W



B B

Use RA889A if normally closed contacts are required.

Use RA889A if normally closed contacts are required. Line voltage switched inputs go to L1 and L2. See Fig. 9B.

Honeywell R882C





6

8

3

5





W



Honeywell R882J





6

8

3

4





1



2

Argo

AR821

1

2

3

4

5

6





T

T



R8845U has lower output load rating. Check load requirements.

Argo

AR822

L1

L2

3

4 N.O.

5

6 N.O.





G(T)

R(T)

C

Erie

SR100AT

L1

N

3

4 N.O.

5

6 N.O.





G(T)

R(T)

C

Use RA889A if normally closed contacts are required.

WhiteRodgers

829-189

1

2

3

4









B

R

W

WhiteRodgers

829-832

1

2



4



3

X1

X2

T

T



Taco

SR501

H

N

3

4 N.O.

5

6 N.O.





W(T)

R(T)

C

69-1292

2

R8845U has lower output load rating. Check load requirements. Use RA889A if normally closed contacts are required.

R8845U UNIVERSAL SWITCHING RELAY

4 5 1 (29) 32

1 (108) 4

MOUNTING In replacement applications, mount the new relay in the same location as the old relay. For new installations, locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled. Select a location that is easily accessible for installation and service.

7 8 (48)

1

7 (22) DIAMETER 8

3 (2) DIAMETER 32 1 (13) DIAMETER 2

NOTE: To reduce the possible transformer hum and relay noise that is sometimes amplified by mounting surfaces such as sheetmetal, plasterboard, and similar materials, place rubber or felt washers between the case and the mounting surface.

KEYHOLE TYPE MOUNTING HOLE

1 2 (114)

1. Position the relay and mark the mounting holes. See Fig. 1. 2. Start a screw in the upper right corner for the keyhole type mounting hole. Screw it down within about 1/8 in. (3 mm) of the surface. 3. Hang the relay on the screw, position the case, and start the bottom screw. 4. Tighten both screws.

4

1 4 (133) 5

WIRING

3 (10) 8 3 (10) 8

1 3 (89) 2 7 (6) DIAMETER MOUNTING HOLE 32

CAUTION

Electrical Shock or Personal Injury Hazard. Power supply can shock. Use only NEC Class 1 wire for all line voltage wiring connections. Class 1 wires must be rated for at least 167°F (75°C).

15 2 16 (75) 7 8 (48)

1

25 (20) 32

1

3 (35) 8

KNOCKOUT FOR 1/2 (13) CONDUIT (3)

All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow all instructions furnished with the controlled equipment.

M3823A

Fig. 1. R8845U dimensions in in. (mm).

IMPORTANT

The switching relay terminals are approved only for use with copper wires.

INSTALLATION

When two or more line-voltage load devices are to be controlled in parallel, the total current must not exceed the rating for the relay load outputs. Never connect load terminals to a load that uses more current than the amount listed in the electrical ratings on the relay. See Table 2 for maximum low-voltage wiring length specifications. See the schematic and typical hookups in Fig. 2 through 9.

When Installing this Product . . . 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. 5. Follow local codes for installation and application.

Table 2. Low-Voltage Maximum Wire Lengths.

WARNING

Electrocution Hazard. Power supply can cause severe injury, or death. Transformer core not bonded. Disconnect power supply before wiring.

3

Total Wire Length

Wire Length of Run to Thermostat

Wire Size (AWG)

Ft

M

Ft

M

22

120

38.0

60

18.0

20

200

61.0

100

30.5

18

300

91.5

150

45.5

16

500

152.5

250

76.0

14

800

244.0

400

122.0

69-1292

R8845U UNIVERSAL SWITCHING RELAY

LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT

HYDRONIC HEATING CONTROL TERMINALS CALL FOR HEAT LED

AUTOMOTIVE FUSE

T

R8845U RELAY

THERM. THERMOSTAT ZONE 1 T

C R(T)

TO ADDITIONAL R8845U RELAYS FOR OTHER ZONES

W(T)

ZC

L2

R(T)

L1

THERMOSTAT W(T) ZONE 2

A ZP

RELAY LED G

L2

L1

B

COM

N.O.

A

X1

B

B1 BURNER BURNER CONTROL B2

X2

N.O. COM

C1 1 L2

1 TO POWER

L1 HOT

1 TO LOAD 1 POWER

CIRC.

LOW-VOLTAGE POWERPILE®

CIRCULATOR ZONE 1

CIRCULATOR ZONE 2

C2

LOAD 2

1 1

POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.

1

LINE M14294

2

L1 HOT

2 3

L2

Fig. 2. R8845U Internal schematic and typical hookup. 1 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. 2 IF CONTROLLING TWO LOADS, USE: N.O. AND COM FOR LINE VOLTAGE LOAD, A AND B FOR LINE OR LOW VOLTAGE LOAD. 3 IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER.

M14296

Fig. 3. R8845U schematic diagram for multizone, hydronic heating system (applies for any number of additional zones).

T87F T87F

L7124A, L8124A R(T)

ZR

R(T)

W(T)

L1 C1 C2 B2 B1

L1

L2 COM

3

2 G

L2

T87F R8845U RELAY

R8845U RELAY

ZC

W(T)

A

B

N.O.

R(T)

W(T)

L1

L2 COM

A

B

N.O.

L2 L1 (HOT) 1

PUMP

PUMP

PUMP

R8184 T

F

T

F

BLACK

WHITE

C554

ORANGE

BURNER AND IGNITION

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2

CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.

3

B1 IS 1/4 IN. TAB TERMINAL.

M14298

Fig. 4. R8845U hookup for L7124A/L8124A in an oil-fired, tankless hot water, zoned, pump system.

69-1292

4

R8845U UNIVERSAL SWITCHING RELAY

T87F

T87F

T87F R8845U

R8845U RELAY

R(T)

L1

L1 (HOT)

1

W(T)

R(T)

COM

L2

N.O.

X1

X2

L1

R(T)

COM

L2

PUMP

R8845U

W(T)

N.O.

X1

X2

L1

W(T)

COM

L2

PUMP

N.O.

X1

X2

PUMP

L2

ORANGE G

2

F

L2

L1

T

T

C1

C2

B2

B1

3

WHITE

C554

F BLACK

BURNER AND IGNITION

T L7148A/L8148A T R8184G

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. M14300

3 B1 IS 1/4 IN. TAB TERMINAL.

Fig. 5. R8845U hookup for L7148A/L8148A in an oil-fired, tankless hot water, zoned, pump system.

T87F

T87F

T87F

R8845U RELAY R(T)

L1 (HOT)

1

R(T)

W(T)

L2

L1

COM

R8845U

N.O.

X1

X2

PUMP

W(T)

L2

L1

R8845U R(T)

COM

N.O.

PUMP

X1

X2

W(T)

L2

L1

COM

N.O.

X1

X2

PUMP

L2

2

G

L2

L1

T

T

TR 3

C1

C2

B2

B1

THTR TH

LOW VOLTAGE GAS VALVE (eg, VR8300)

L7148F/L8148E

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2

CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.

3

B1 IS 1/4 IN. TAB TERMINAL.

M13318

Fig. 6. R8845U hookup for L7148F/L8148E in a gas-fired, 24V, zoned, pump system.

5

69-1292

R8845U UNIVERSAL SWITCHING RELAY

L1 (HOT) L2 3

R8888 1

R

G

L2 L1 L2 L1 L1 ZC

C A B C

20 VA

R8845U L2

4 N.O.

H1 H2

ZONE 1 THERMOSTAT

CIRCULATOR PUMP 1

W

C2 C1

R

ZONE 1

CIRCULATOR PUMP 5

L1

ZC

A

H1

B

H2

TO APPROPRIATE CONNECTIONS AS REQUIRED BY THE SYSTEM. H1-H2 TYPICALLY CONNECTED TO T-T OF BURNER CONTROL SYSTEM.

COM

ZONE 5 THERMOSTAT R(T)

ZONE 2 THERMOSTAT

CIRCULATOR PUMP 2

W

C2 C1

R

ZONE 2

G

ZONE 3 THERMOSTAT

CIRCULATOR PUMP 3

W

C2 C1

R

ZONE 3

1

ZONE 4 THERMOSTAT

CIRCULATOR PUMP 4

W

C2 C1

R

ZONE 4

W(T)

2

1

CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.

3

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2

USE COPPER CONDUCTORS ONLY. FOR ALL CLASS 1 CONNECTIONS, USE WIRE RATED FOR AT LEAST 167°F (75°C).

4

CONNECT L1-ZC JUMPER, IF REQUIRED.

M13315

Fig. 7. R8888 Zone expansion using additional R8845U Universal Switching Relays.

THREE-WIRE LOW VOLTAGE (SERIES 10) 1 THERMOSTAT W(T)

R(T)

R(T)

C

W(T)

TWO-WIRE LOW VOLTAGE (SERIES 80) THERMOSTAT

B

X1

R8845U

X2

R(T)

C

W(T)

X1

R8845U

1 MAKES CONTACT ONLY ON TEMPERATURE FALL.

Fig. 8. R8845U thermostat connections.

69-1292

6

X2

M13319

R8845U UNIVERSAL SWITCHING RELAY

A.

CHECKOUT

FOR 24V THERMOSTAT CONTROL L1, (HOT) NEUTRAL

R(T)

R

L2

W(T)

W

C

COM

LINE VOLTAGE CONTROLLED OUTPUTS

THERMOSTAT

R8845U L1

C OPTIONAL 2

N.O.

B.

1. Keep the cover on the relay during normal operation and remove only for service and checkout. 2. Relay contacts require no cleaning; they are arranged to close with a wiping action and are selfcleaning. The contacts may turn black after being in service for some time; this discoloration does not prevent proper operation. 3. After installation is complete, operate system through at least one cycle from the controller to make certain the relay controls the equipment as intended.

A

X1

B

X2

LOW VOLTAGE POWERPILE® CONTROLLED OUTPUT

FOR LINE VOLTAGE CONTROL

LINE VOLTAGE CONTROL 3 NEUTRAL

R8845U L1

R(T)

L2

W(T)

TROUBLESHOOTING

JUMPER

C

COM

Test Button — This connection is the same as a call for heat connection between the R(T) and W(T) terminals.

N.O.

A

X1

B

X2

Heat Call LED — The LED should light if there is a call for heat or if the test button is pressed. — If the LED remains off during a call for heat and turns on when the Test Button is pressed, the thermostat is not operating correctly. — If the LED remains off on a call for heat and also remains off when the Test Button is pressed, the R8845U is not operating correctly. Check the fuse; if the fuse is intact, replace the control.

C. FOR EXTERNAL SEPARATE LOW VOLTAGE POWER SOURCE R8845U NEUTRAL

L1

R(T)

L2

W(T)

1 COM

C

24V CONTROLLER INPUT SUPPLY

N.O.

A

X1

B

X2

1

REQUIRED FOR OUTPUT LED OPERATION.

2

FOR SERIES 10 OR OTHER HARDWIRED ELECTRONIC 3-WIRE THERMOSTATS.

3

WARNING! ELECTROCUTION HAZARD. POWER SUPPLY CAN CAUSE SEVERE INJURY OR DEATH. DISCONNECT POWER BEFORE WIRING OR SERVICING L1. POWERED RELAYS MUST BE WIRED AS DRY CONTACTS. M13320

Relay LED — This LED lights whenever there is 120 Vac (L1) on the N.O. terminal (when COM/N.O. relay contacts are closed).

Fig. 9. R8845U control options.

7

69-1292

R8845U UNIVERSAL SWITCHING RELAY

Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422

69-1292 J.S. 3-99

Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9