INSTALLATION AND MAINTENANCE INSTRUCTIONS

Series

3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com

RRS-MOD Reversing Relay/Synchronization Module Specifications Operating Voltage Range: Maximum Operating Current: Relay Contacts: Operating Temperature Range: Operating Humidity Range: Dimensions: Wire connections:

NOTE: In an alarm condition, a wiring-fault trouble state may also register at the panel when the RRS-MOD is used.

8.5 to 35 VDC 25mA 2A at 35 VDC 32° to 131° F (0° to 55° C) 5% to 93% non-condensing 21⁄2˝ x 21⁄2˝ x 1˝ 18 AWG stranded, tinned, 16˝ long

General Description The RRS-MOD polarity reversing relay/synchronization module is intended for use with 2-wire and 4-wire i3 series detectors equipped with a built-in sounder, models 2WTA‑B, 4WTA-B, 4WTAR-B, and 4WITAR-B. It is designed to allow all the detectors in the same loop to sound when one of the detectors goes into alarm, and to synchronize their audible output. The RRS-MOD also allows the silencing of the detector sounders from the alarm control panel.

Wiring IMPORTANT: All polarities must be observed! 1. Connect the RRS-MOD module trigger wire to the fire alarm output terminals. A. Alarm/Bell output: (Figures 1 and 2) Connect the purple wire to the Alarm or Bell output. B. Alarm relay, normally open contact: (Figures 3 and 4) 1. Connect one end of the alarm relay contact output to positive auxiliary or detector power fire alarm output. 2. Connect the purple wire to the other end of the alarm relay contact output. 2. Connect the red and black wires to the panel auxiliary or detector power (red to positive, black to negative). 3. 2-wire models Connect the yellow and orange wires to the panel initiating circuit (yellow to positive, orange to negative). 4-wire models Connect the yellow and orange wires to the panel detector power circuit (yellow to positive, orange to negative). 4. 2-wire models Connect the brown and white wires to the smoke detector power supply input (brown to positive, white to negative). 4-wire models Connect the brown and white wires to the smoke detector power circuit (brown to positive, white to negative).

The RRS-MOD may be used with an alarm zone that provides coded output for fire and continuous output for burglary. By default the RRS-MOD’s switch is set to “off”. Therefore, the RRS-MOD will only trigger when the alarm output is coded. In this manner, smoke detectors will only sound from the result of a fire, and not from a burglary alarm. In this mode, the detectors will provide a synchronized, coded output. The RRS-MOD contains a relay that is meant for zone applications, per UL 864. The RRS-MOD can also be set to only trigger on continuous alarm zone signals by selecting the switch to “on”. In this mode, the detectors will provide a synchronized, coded output. NOTICE: This manual shall be left with the owner/user of this equipment Installation Install in a dry indoor location. Choose a mounting location in the control panel within reach of the provided wire leads. Use a water/isopropyl alcohol mixture (50/50) to clean the mounting surface. Allow surface to dry and remove paper backing from the Velcro and catch. Stick the Velcro in the panel and the catch on the back of the module, then mount the module inside the control panel. Route terminals to the appropriate terminals as noted below. WARNING When calculating total current draw of the control panel, remember to add current consumption (25mA) for the polarity reversal relay module (RRSMOD). IMPORTANT: If the fire alarm output signal is coded, set the switch on the RRS-MOD to “OFF”. If the fire alarm output signal is continuous, set the switch to “ON”.

D500-44-00

1

I56-2203-005

NOTE: Please refer to Figures 5 and 6 for Ademco Vista panels and Figures 7 and 8 for DSC Power 832 panels. Figure 1. 2-Wire system triggered from alarm/bell output: UL LISTED ALARM CONTROL PANEL

CAUTION

BELL/ ALARM CIRCUIT (positive signal in alarm state)

2–WIRE + INITIATING DEVICE – CIRCUIT

PURPLE T+

EOL

YELLOW IN+

BROWN OUT+

ORANGE IN–

WHITE OUT–

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 RA+

4 RA+

5 RA-

5 RA-

+ +

RED PWR+



BLACK PWR–

AUX POWER

When using the RRS-MOD with model 2WTA-B, do not mix the 2WTA-B with other model smoke detectors and dry contact closure devices, including mechanical heat detectors, manual pull stations and waterflow switches. Such mixing can cause a direct short on the auxiliary power terminals, damaging the control panel’s internal circuitry and/or damaging devices connected to the initiating device circuit.

+





OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

S0101-01

Figure 2. 4-Wire system triggered from alarm/bell output: UL LISTED ALARM CONTROL PANEL BELL/ALARM CIRCUIT (positive signal in alarm state)

DETECTOR POWER

PURPLE T+

+

YELLOW IN+



ORANGE IN–

EOL RELAY (SHOWN ENERGIZED)

BROWN OUT+

WHITE OUT –

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 N.O.

4 N.O.

5C

5C

RED PWR+

AUX POWER + OR DETECTOR POWER –

BLACK PWR–

EOL

+

INITIATING DEVICE CIRCUIT –

S0102-00

Figure 3. 2-Wire system triggered from alarm relay contact: UL LISTED ALARM CONTROL PANEL ALARM RELAY (NO Contact)

PURPLE T+

EOL

2–WIRE + INITIATING DEVICE – CIRCUIT

YELLOW IN+ ORANGE IN–

BROWN OUT+

WHITE OUT–

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 RA+

4 RA+

5 RA-

5 RA-

+ +

RED PWR+



BLACK PWR–

AUX POWER

+





OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

S0103-01

D500-44-00

2

I56-2203-005

Figure 4. 4-Wire system triggered from alarm relay contact: UL LISTED ALARM CONTROL PANEL ALARM RELAY (NO Contact)

PURPLE T+

EOL RELAY (SHOWN ENERGIZED)

DETECTOR POWER

+

YELLOW IN+



ORANGE IN–

BROWN OUT+

WHITE OUT–

AUX POWER + OR DETECTOR POWER –

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 N.O.

4 N.O.

5C

5C

RED PWR+ BLACK PWR–

EOL

+

INITIATING DEVICE CIRCUIT –

S0104-00

Connection Diagrams with Ademco Vista Panels The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the System Sensor polarity reversal relay module (RRS-MOD). Please make sure that the smoke detectors are connected properly to the zones specified in the wiring diagrams for proper operation of the smoke detectors. Figure 5. Connecting 2WTA-B smoke detectors to Ademco controls using RRS-MOD module triggered from bell/alarm circuit: SYSTEM SENSOR REVERSING RELAY/SYNCHRONIZATION MODULE ( RRS-MOD) (MOUNT INSIDE CONTROL ENCLOSURE)

UL LISTED ALARM CONTROL PANEL BELL/ ALARM CIRCUIT (positive signal in alarm state)

PURPLE T+

EOL 2K OHMS

ADEMCO CONTROL PANEL APPCLICABLE CONTROLS: VISTA-20 VISTA-40 VISTA-50P VISTA-32FB VISTA-100 VISTA-128FB

BROWN

2 -WIRE + INITIATING CIRCUIT



1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 N.O.

4 RA+

YELLOW

ORANGE WHITE

5C

+

RED



BLACK

RRS-MOD Configuration: • Set switch on RRS-MOD to “OFF”.

+





OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

470 1/2 WATT*

• T  he supervisory feature for the bell circuit must be turned off. See applicable control manual for procedure.

5C

+ AUX POWER

Programming information:

OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

SYSTEM SENSOR 2WTA-B SMOKE DETECTORS (UP TO 16 DETECTORS PER ZONE)

S0105-02

*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET

Figure 6. Connecting 2WTA-B smoke detectors to Ademco controls using RRS-MOD module triggered from auxiliary relay: NOT REQUIRED ON 5110XM WHEN 5100XM JUMPER W3 INTACT

UL LISTED ALARM CONTROL PANEL AUXILIARY RELAY

SYSTEM SENSOR REVERSING RELAY/SYNCHRONIZATION MODULE (RRS-MOD) (MOUNT INSIDE CONTROL ENCLOSURE)

Programming information: PURPLE T+

EOL 2K OHMS ADEMCO CONTROL PANEL APPCLICABLE CONTROLS: 5110XM 5140XM VISTA-32FB VISTA-100 VISTA-128FB

BROWN

2 – WIRE SMOKE ZONE

+ –

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 RA+

4 RA+

5 RA-

5 RA-

YELLOW ORANGE WHITE

+ AUXILIARY POWER OUTPUT

+

RED



BLACK

470 1/2 WATT*

TAKE POWER FROM CONTROLS AUXILIARY POWER OUTPUT ONLY

• Assign Auxiliary relay as an output for zones programmed for fire alarm response only (Types 9, 16, or 17) RRS-MOD Configuration: • Set switch on RRS-MOD to “ON”.

+

– OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

• Program Auxiliary relay to activate on alarms

– SYSTEM SENSOR 2WTA-B SMOKE DETECTORS (UP TO 16 DETECTORS PER ZONE)

OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)

S0106-02

*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET

D500-44-00

3

I56-2203-005

Connection diagrams with DSC Power 832 Panels Figure 7. Connecting 4WTA-B, 4WTAR-B, and 4WITAR-B smoke detectors to DSC Power 832 controls using RRS-MOD module with PGM output: UL LISTED ALARM CONTROL PANEL

NOTE: • Program zone section attributes for bell output to be pulsing.

DSC POWER 832 PGM 1

PURPLE

EOL RELAY (SHOWN ENERGIZED)

BROWN

AUX (+)

YELLOW

PGM 2

ORANGE WHITE

5.6 K� *

AUX +

RED

AUX –

BLACK

All smoke detectors on the 4-wire fire zone will be synchronized in alarm and will sound 1 sec ON, 1 sec OFF only from a fire alarm event.

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 N.O.

4 N.O.

5C

5C

• PGM2 must be programmed for sensor reset. • PGM1 must be programmed as Burglary and Fire Bell Output (01) with ON, ON, OFF attributes. • RRS-MOD switch must be set to OFF (factory default setting).

EOL

ZONE + ZONE (COM) –

S0107-02 *NOTE: 5.6K� resistor must be rated for 1/4W or greater. Must be present for panel to reset.

Figure 8. Connecting 2WTA-B smoke detectors to DSC Power 832 controls using RRS-MOD module with PGM output: UL LISTED ALARM CONTROL PANEL DSC POWER 832 PGM 1

EOL

PURPLE

BROWN

AUX (+)

YELLOW

PGM 2

ORANGE WHITE

5.6 KΩ*

AUX + AUX –

All smoke detectors on the 2-wire fire zone will be synchronized in alarm, and will sound 1 sec ON, 1 sec OFF only from a fire alarm event. NOTE: • Program zone section attributes for bell output to be pulsing. • PGM2 must be programmed for 2-wire smoke zone (04). Jumper J1 on the main board must be removed.

1 + IN

1 + IN

2 + OUT

2 + OUT

3 - IN/OUT

3 - IN/OUT

4 N.O.

4 N.O.

5C

5C

• PGM1 must be programmed as Burglary and Fire Bell Output (01) with ON, ON, OFF attributes. • RRS-MOD switch must be set to OFF (factory default setting).

RED

S0108-02

BLACK

*NOTE: 5.6KΩ resistor must be rated for 1/4W or greater. Must be present for panel to reset.

Testing Before testing, notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service.

3. Reset the system from the control panel. All smoke detector sounders should be silent. 4. If the fire alarm panel also functions in burglary, initiate a burglary alarm and ensure the smoke detectors do not sound.

Test in accordance with NFPA 72 test methods, inspections, and testing frequency. 1. Confirm that all smoke detectors connected to the RRS-MOD module(s) contain a sounder and the sounders are activated upon power reversal. 2. Initiate an alarm with one of the smoke detectors connected to the RRSMOD module using any approved test method. In the alarm state, all the detectors connected to the RRS-MOD module must be sounding their sounders.

Three-Year Limited Warranty System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA

D500-44-00

#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

4