TECHNICAL BROCHURE BCP0 R6

FEATURES Rugged NEMA 4X construction withstands even the most severe weather con­ditions and prevents corrosion. Hinged door with lockable stainless steel latch for safe operation indoors and out. High level alarm circuit with external, on/off, alarm horn silence switch. Alarm test switch insures proper operation of the alarm circuit without the need to actuate the alarm float. Inside mounted pump run light. Top mounted high intensity red light provides 360° visibility. Corrosion proof alarm horn. Color coded wiring, screw type terminals, ensure ease of field servicing. Field wiring diagram, panel schematic and installation instructions included. Entire unit is UL and CUL listed Non-modifiable

S10015 1Ø CONTROL PANELS SIMPLEX / WEATHERPROOF CONTROLLER WITH ALARM

CentriPro Wastewater APPLICATIONS

SPECIFICATIONS

Simplex liquid level controller, automatically maintains pump operation, includes high level alarm warning for a variety of sump, effluent, sewage and water transfer applications.

• Accepts single or dual power feed. • Hand-off-automatic (H-O-A) pump selection switch. • Magnetic contactor. • Numbered terminal strip-screw type. • NEMA 4X, 30 watt, red alarm light. • NEMA 4X, fiberglass enclosure with gasketed, hinged door and stainless steel hardware.

• NEMA 4X, alarm horn – 95db. Single Phase

• 115 or 230 volt, 60 Hz.

Maximum Order No. Running Amps S10015 20 S10015WF 20

Float Switches None - Order Separately (3 required) ➀ Inc. (3) N.O. Narrow Angle Mech. Control Switches

➀ Includes weights. Replacement switch is order No. A2N33.

TERMINAL STRIP WIRING

NOTE: WHEN USING SEPARATE 115 VAC CONTROL POWER SUPPLY, REMOVE JUMPER (J1) FROM TERMINALS (L1) AND (LL1). CONNECT 15 AMP MAX. PROTECTED 115 VAC SUPPLY TO TERMINALS (LL1) AND (N). WITH THE NEUTRAL OF THE SUPPLY TO (N).

J1

L1

L2

LL1

N

1

2

115/230 VAC * SINGLE PHASE 60 HZ

4

T1

T2

ALARM FLOAT ON FLOAT

* FOR 115 VAC OPERATION, USE TERMINALS L1 AND N, JUMP TERMINALS L2 AND N. OFF FLOAT

PAGE 2

3

PUMP

CentriPro Wastewater COMPONENTS

2

1. NEMA 4X FRP enclosure 2. Alarm light (RB63) 3. Alarm horn (RB50)

5, 6, 7

4. Horn on-off selector switch 5. H-O-A selector switch 6. Pump run light

8

7. Alarm test switch

4

8. Motor contactor 9. Wiring terminal strip

9

1

ENCLOSURE DIMENSIONS (in inches)

3

A

Single Phase A B C D E F 6 11.5 13.5 11.75 5.63 9.25

C

B

D

F

E

PAGE 3

115/230 VAC (FOR 115 VAC, USE TERMINALS L1 AND N, JUMP L2 AND N). SINGLE PHASE, 60 Hz S1

L1

T1

L2

T2

PUMP

N J1

GND LL1

A 230 VOLT SYSTEM REQUIRES A 4 WIRE POWER SUPPLY LINE L1, L2, N AND GND. WITHOUT A NEUTRAL THE CONTROL CIRCUIT WILL NOT WORK.

NOTE: WHEN USING SEPARATE 115 VAC CONTROL POWER SUPPLY, REMOVE JUMPER (J1) FROM TERMINALS (L1) AND LL1). CONNECT 15 AMP MAX. PROTECTED 115 VAC SUPPLY TO TERMINALS (LL1) AND (N) WITH THE NEUTRAL OF THE SUPPLY TO (N).

CONTROL ON-OFF

RUN HAND S1-AUX

1

2 OFF FLOAT

OFF 3

S1

AUTO

ON FLOAT

HIGH LEVEL 4 ALARM FLOAT

HORN * ON - OFF HORN

TEST

*NOTE: THE HORN ON/OFF SELECTOR SWITCH MUST BE PLACED BACK INTO THE (ON) POSITION AFTER THE ALARM CONDITION HAS BEEN CORRECTED IN ORDER TO MAINTAIN THE AUDIO ALARM ANNUNCIATION