AMP-TRAP®–Form 101
A60Q
SEMICONDUCTOR PROTECTION FUSES A60Q Amp-trap Form 101 Semiconductor Protection fuses feature the only 600 volt AC/DC rating in the industry of similar size (1-1/2” x 13/32”) fuses protecting semiconductors. A60Q also has the lowest l2t of all similar fuses and excellent cycling ability. Applications include inverters and small equipment requiring extremely fast response to faults, without the need to carry sustained heavy overloads. ®
Features/Benefits ➤ Lowest l t of any fuse this size for greater protection ➤ Excellent cycling ability gives advantage in equipment design ➤ 600V AC/DC rated 2
Ratings ➤ AC: 5-40A 600VAC, 200kA I.R.
Approvals ➤ UL Recognized Component
➤ DC: 5-40A 600VDC, 100kA I.R. L/R = 10ms
➤ AC: UL Guide JFHR2 File E60314 ➤ DC: UL File E60314
HIGHLIGHTS: ➤ 600VAC/DC Rated ➤ Extremely Fast Acting ➤ Current Limiting ➤ Lowest l t ➤ Excellent Cycling Ability 2
APPLICATIONS: ➤ Protection of small inverters and drives, and equipment requiring the highest degree of protection
5 6 8 10 12 15
A60Q5-2 A60Q6-2 A60Q8-2 A60Q10-2 A60Q12-2 A60Q15-2
AMPERE RATING
CATALOG NUMBER
20 25 30 35 40
A60Q20-2 A60Q25-2 A60Q30-2 A60Q35-2 A60Q40-2
Amp-trap Fuse ®
A 60 Q 30 - 2
A
Rated Volts - 600 Style
60
Amperes
30
Mounting Type Ferrule, midget dims. (1-1/2” x 13/32”)
Standard Fuse Ampere Ratings, Catalog Numbers AMPERE CATALOG RATING NUMBER
Numbering System Catalog
Q
2
fuse holders for a60Q fuses USM Series . . . . UltrasafeTM Fuse Holders 303 Series . . . . . Midget Fuse Blocks 1-1/2” (38.1 mm)
13/32” (10.3 mm)
For ampere ratings and styles not listed, call Technical Services.
D 18 Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com ·
[email protected] AMP-TRAP®–Form 101
A60Q
SEMICONDUCTOR PROTECTION FUSES
I t at 600VAC, 100kA
Watts Loss Data
2
AMPERE RATING 5 8 10 12 15 20 25 30 35 40
AMPERE WATTS LOSS @ WATTS LOSS @ RATING 80% RATING (W) 100%RATING (W)
2 2 MELTING I t CLEARING I t (A2s) (A2s)
5 6.5 10 17 26 41 69 132 197 276
60 70 110 150 180 330 440 860 1300 1800
5 8 10 12 15 20 25 30 35 40
0.5 0.7 0.9 1.3 1.9 2.6 2.9 3.0 3.3 3.6
0.7 1.1 1.5 2.0 3.0 4.4 5.3 5.8 6.4 7.0
D
A60Q5 to 40 Melting Time – Current Data, 600V Fuses
Time in Seconds
Max. Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A60Q5 to 40, 600 Volts AC
Available Current in RMS Symmetrical Amperes
I t at 600VDC,100kA, L/R = 10 ms 2
AMPERE RATING 5 8 10 12 15 20 25 30 35 40
CLEARING I2t (A2s) 40 42 70 90 110 200 260 520 780 1100
Current in Amperes D 19 Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com ·
[email protected]