Submittal #0107-004.0 0107 - FLUSHING CLEANING ...

Report 15 Downloads 31 Views
Reviewed and APPROVED with NOTE: See notes below Kevin M. Odlum KMO 18Aug16

Submittal #0107-004.0 0107 - FLUSHING CLEANING PASSIVATION AND AND DOCUMENTATION REQUIREMENTS Project: X-5-8654 - 51 NYA Gas Shed Construction 11 Forbes Road Northborough, Massachusetts 01532

A/Z Corporation One Research Drive Westborough, Massachusetts 01581 Phone: (800) 400-2420  Fax: (508) 836-3293

MicroPure Filtration System SPEC SECTION:

0107 - FLUSHING CLEANING PASSIVATION AND AND DOCUMENTATION REQUIREMENTS 

CREATED BY:

Henry Williams (A/Z Corporation)

STATUS: 

Draft

DATE CREATED:

07/12/2016 

ISSUE DATE:

07/12/2016  

REVISION:

0

RESPONSIBLE CONTRACTOR:

A/Z Mechanical

RECEIVED FROM:

Kurt Kashuba

RECEIVED DATE:   08/01/2016

SUBMIT BY: 

08/08/2016  

FINAL DUE DATE: 08/08/2016

LOCATION: 

 

TYPE:

Product Information

COST CODE: 

APPROVERS:

Kevin Odlum (Genzyme Corporation), Craig Parker (A/Z Design Services, LLC)

Sub Section: BALL IN COURT: DISTRIBUTION: John McDermott (A/Z Corporation) , Lisa Gates (Genzyme Corporation) , Henry Williams (A/Z Corporation) , Craig Parker (A/Z Design Services, LLC) , Kevin Odlum (Genzyme Corporation) , Glen Nonemaker (Genzyme Corporation) , Roger McClure (A/Z Corporation) , Kurt Kashuba (A/Z Mechanical) , Kevin Boudreau (Genzyme Corporation) DESCRIPTION: Kevin O. and Craig,   Please use the links provided to access the referenced submittal, for your review & approval. Please provide approval when the document has been reviewed. If you have any questions, please do not hesitate to contact myself or Kurt Kashuba.   Thank you, Henry Williams ATTACHMENTS:

  SUBMITTAL WORKFLOW #

NAME

SUBMITTER/ APPROVER



Kurt Kashuba

Submitter 



Kevin Odlum

Approver 



Craig Parker

Approver 

SENT DATE

8/1/2016 8/1/2016

   

To Review

Architectural Structural Mechanical Electrical Plumbing Process

A/Z Corporation

DATE

Fire Protection

8/1/2016

8/8/2016

Pending

Reviewed

ATTACHMENTS

COMMENTS

Submitted Pending

Assigned to:

Civil

RETURNED RESPONSE DATE

8/8/2016

Craig Parker Discipline

BY

DUE DATE

Our review is for the general conformance with the design concept and contract documents. Any marking or comments must not be construed as relieving the Revise & Resubmit subcontractor / supplier from compliance Rejected with the project plans and specifications nor departures there from. Subcontractor / For Record supplier remains responsible for details and accuracy, for confirming and correlating all quantities and dimensions, for selecting fabrication processes for the techniques of assembly, and for performing this work safely and in accordance with all applicable codes. Approved

Approved as Noted

Our review is for the general conformance with the design concept and contract documents. Any marking or comments must not be construed as relieving the subcontractor/supplier from compliance with the project plans and specifications nor departures there from. The subcontractor / supplier remains responsible for details and accuracy, for confirming and correlating all quantities and dimensions, for selecting fabrication processes for the techniques of assembly, and for performing this work in a safe manner and in accordance with all applicable codes.

COPIES TO

Date: Reviewed by:

Page 1 of 1

Date:

Printed On: 08/01/2016  09 :48 AM 8/1/2016

Reviewed by:

Submittal Request Form (please route to Project Controls) Requested By: Kurt Kashuba

Date: Saturday, August 06, 2016

Project Name & #: 51 NYA Gas Shed Installation Project E16141

Purchase Order/Contract #:

(X-5-8654)

Spec Section/Cost Code to Reference: 15110

F-9630-001, F-9630-002, F-9630-003 Tag Numbers: F-2215-007 & F-2215-008

Submittal Title: Micropure Filtration Filter Submittal

# of Copies Required: 1

Submitting To& Contact Name: Craig Parker/Kevin Odlum

Supplier & Contact Name: Micropure, Inc. (Trey Senney 952-472-2323)

C:\Users\hwilliams\Documents\2016\01_Genzyme\C-5-8618 Gas Shed Design Phase\Submittals\Swagelok Submittals 2\Micropure FIltration Revised 10/07/05 Filter\Micropure Filtration Filter Submittal rev 1

Sterile Filter Type PSF PSF Sterile Filter is used for 100% contamination free filtration of air, compressed air, CO2 and other gases. Micropure Sterile Filters are equipped with the variable Ecofilter element and PTFE media. Micropure Sterile Filter membranes are made of PTFE which have an extremely high pore distribution (95%) which allows for high through-put and very little pressure loss.

Technical Data

Filter Capacity @

Filter Type

7 bar Nm3/h

100 psig Scf/m

PSF-0602 PSF-0604 PSF-0606 PSF-0802 PSF-0804 PSF-0806 PSF-0808 PSF-0810 PSF-1008 PSF-1010 PSF-1012 PSF-1014 PSF-1408 PSF-1410 PSF-1412 PDF-1414 PSF-1416 PSF-1418 PSF-1420 PSF-1426 PSF-1432

40 80 120 120 240 360 480 600 680 850 1020 1190 1360 1700 2040 2380 2720 3060 3400 4420 5440

24 48 72 72 144 216 288 360 408 510 612 714 816 1020 1224 1428 1632 1836 2040 2652 3264

Housing Connections DN in 15 15 15 25 25 40 40 40 50 50 50 50 50 50 50 50 65 65 80 80 80

½ ½ ½ 1 1 1½ 1½ 1½ 2 2 2 2 2 2 2 2 2½ 2½ 3 3 3

Micropure PTFE media are hydrophobic, so no bacteria growth is possible. Micropure Sterile Filters make 100% reverse flow filtration possible. Standard equipment is a stainless steel glycerin filled pressure gauge and drain hole plugs. Micropure Sterile Filters are designed for upstream and downstream sampling as well as draining condensate. Micropure Sterile Filters can be sterilized in place using steam up to 140°C for six minutes in both directions up to 150 times

Weight of unit Kgs

Lbs

3.8 4 4.2 6.4 6.6 6.8 7.2 7.4 13.4 13.8 14.2 14.6 20 20.5 21.5 22.5 24.5 25.5 26.5 28 29.5

8 9 9 14 15 15 16 16 30 30 31 32 44 45 48 50 54 556 58 62 65

Replacement Media

FMT-06-S20 FMT-06-S20 FMT-06-S20 FMT-08-S20 FMT-08-S20 FMT-08-S20 FMT-08-S20 FMT-08-S20 FMT-10-S20 FMT-10-S20 FMT-10-S20 FMT-10-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20 FMT-14-S20

Max. Pressure of Housing Bar psig 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

232 232 232 232 232 232 232 232 232 232 232 232 232 232 232 232 232 232 232 232 232

Working Bar 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Pressure PSI 15 30 45 58 72 87 100 115 130 145 160 174 189 203 217 232 Conversion .25 .38 .5 .65 .75 .88 1 1.13 1.25 1.38 1.5 1.6 1.75 1.88 2.0 2.13 Factor Filter housing Material: Stainless steel aisi 304

Recommended sterilization procedures

Filter Element Material: Stainless steel aisi 304

Saturated steam: 20 minutes at 121°C

Material Warranty: 5 years except membranes

10 minutes at 130°C

Retaining rate of media: .02 micron (nominal)

6 minutes at 140°C

.2micron (absolute)

Hot air:

12 hours at 121°C

Specialized Sterile Gas, Sterile Air, Culinary Steam, and Liquid Filtration

Page 2 of 4

(http://micropure.com/Organizations-Professional-Affiliations.html)

(http://micropure.com/Organizations-Professional-Affiliations.html)

Sterile Air/Gas Mini Filter Series DATA SHEET

DATASHEET

PSF-602

PSF-604

DATA SHEET PSF-606

Technical Data

Technical Data

Technical Data

Capacity @ 100 psig

24 scfm

Capacity @ 100 psig

48 scfm

Capacity @ 100 psig

72 scfm

Maximum Pressure

16 Bar/232 psig

Maximum Pressure

16 Bar/232 psig

Maximum Pressure

16 Bar/232 psig

Connection

1/2” FNPT

Connection

1/2” FNPT

Connection

1/2” FNPT

Weight

4.2 pounds

Weight

4.4 pounds

Weight

4.6 pounds

Material

Aisi 304

Material

aisi 304

Material

aisi 304

Micron Rating

0.2um Absolute

Micron Rating

0.2um Absolute

Micron Rating

0.2um Absolute

Filter Membrane

2 x FMT-06-S20 PTFE (Teflon)

Filter Membrane

4 x FMT-06-S20 PTFE (Teflon)

Filter Membrane

6 x FMT-06-S20 PTFE (Teflon)

Photo of PDF-602 without housing cover

Photo of PDF-604 without housing cover

Photo of PDF-606 without housing cover

Dimensions - Inches

http://www.micropure.com/sterileAirGasMiniFilterSeries.html

A

B

C

D

E

5.5

7

9

3

14

7/17/2016

Specialized Sterile Gas, Sterile Air, Culinary Steam, and Liquid Filtration

Page 3 of 4

Note: PSF-602 Filter is illustrated. PSF-604 has 4 layers and uses the same housing. PSF-606 has 6 layers and uses the same housing.

Photo of Sterile Air/Gas Filter Housing with ½ NPT Connections. Flow through housing is bidirectional, so you can install the filter in any orentation.

Picture of Drain Port on base of housing. A single drain valve or plug can be installed. Recommendation varies by application.

Photo of PSF-602 expanded to show PTFE media.

Articles of Interest: • Case Study: The Ebb and Flow of Brewing Yeast: (CS-The-Ebb-and-Flow-of-Brewing-Yeast.html)A liquid yeast producer is adding several new tanks and process lines it is important that the air going in to start the fermentation is sterile, as well as the air transfer during filling and emptying.

http://www.micropure.com/sterileAirGasMiniFilterSeries.html

7/17/2016