Submittal - ALPS Controls

Report 2 Downloads 116 Views
Submittal

C 667

Snow Detector & Melting Control 667

01/11 Snow Melting

Job ___________________________

Designer_ ______________________

Replaces: New

Contact_ _______________________

The Snow Detector & Melting Control 667 is designed to operate mechanical equipment to melt snow off an outdoor slab. It can be used in hydronic snow melting applications with one boiler with mixing. This product uses a tekmar snow/ice detection sensor in order to automatically melt snow while protecting the boiler and slab with mixing. It is capable of controlling 1 on/off boiler, a variable speed injection pump for mixing, a boiler pump, and a mix system pump.

Front View

Side View

Mounting Base

1/2” (13 mm) 7/8” (23 mm)

CL

Idle Demand

Melt Demand Idle Demand

Melt Demand

WWSD Minimum

Test

Maximum Water

off red red

Melting

Start Item

Made in Canada by tekmar Control Systems Ltd. 900-04

Snow Detector & Melting Control 667 Variable Speed Injection

C

uS

Meets Class B: Canadian ICES FCC Part 15 Power 115 V ±10% 50/60 Hz 600 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA Var. Pump 230 V (ac) 2.4 A (FLA), 5A (LRA) fuse T2.5 A 250 V Demand 20 to 260 V (ac) 2 VA

Date Code

Menu

not testing testing testing paused

For maximum heat, press and hold Test button for 3 seconds

Signal wiring must be rated at least 300 V.

Do not apply power

 2

3 4 5 6 7 8 9 0  2 3 4

Var Pwr Mix

Red Blk Blu Yel Brn/ Boil Com tN2 Mix Mix Com Out Slab Ret Sup

5 6 7 8 9 20 Melt/Idle Demand

System Pmp 2

Boiler

2 22 23 24 25 Melting

Sys P1

Power L N

H2029C

6–5/8” (170 mm)

Stop

1/2” (14 mm) 1–7/8” (49 mm) 7–5/8” (193 mm)

2–7/8” (72 mm)

Ø 3/16” (5 mm)

1/2” Knock-out (x 5 back) (x 5 bottom)

Specifications------------------------------------------------------ Features--------------------------Snow Detector & Melting Control 667 Variable Speed Injection Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Relays Variable pump Demand Sensors –Included –Optional Warranty

D667, A667, U667, D001, D070 Microprocessor control. This is not a safety (limit) control 3.1 lb. (1400 g) 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Blue PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Noncondensing 115 V (ac) ±10%, 50/60 Hz, 600 VA 230 V (ac) 5 A, 1/3 hp 230 V (ac) 2.4 A (FLA), 5 A (LRA), fuse T2.5 A 250 V 20 to 260 V (ac) 2 VA NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 and 3 of Universal Sensor 082 tekmar Type #: 039, 040, 072, 073, 082, 090, 091, 094 Limited 3 Year (See D667 for full warranty)

• Automatic snow detection and melt control (090 Sensor) • Slab temperature control • Mixing Control (Variable Speed) • Temporary Idle • Slab protection for the snow melting system • Boiler control • Boiler Protection • Manual Override • Warm Weather Shut Down • Cold Weather Cut Out • Remote display and adjustment capabilities • Test sequence to ensure proper component operation • Equipment Exercising • CSA C US certified (approved to applicable UL standards)

Special requirements

090 Snow/Ice Sensor or Slab Sensor www.tekmarcontrols.com

 of 2

© 2011

C 667 - 01/11

Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram

667 070 S5

S1

S2 P3

P1

S4

P2

B1 S3

Sample Electrical diagram Legend

Idle Demand

Melt Demand

B1 = On/Off Boiler P1 = Boiler Pump P2 = Mix System Pump P3 = Variable Speed Pump S1 = Boiler Sensor S2 = Mix Supply Sensor S3 = Mix Return Sensor S4 = Snow Sensor S5 = Outdoor Sensor

Idle Demand

Melt Demand

WWSD Minimum

Test

Maximum Water

off red red

Melting

For maximum heat, press and hold Test button for 3 seconds

Item

Made in Canada by tekmar Control Systems Ltd. 900-04 Power Relays Var. Pump

Snow Detector & Melting Control 667

C

Variable Speed Injection

US

Demand

Meets Class B: Canadian ICES FCC Part 15

115 V ±10% 50/60 Hz 600 VA 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA 230 V (ac) 2.4 A (FLA), 5A (LRA) fuse T2.5 A 250 V 20 to 260 V (ac) 2 VA

Signal wiring must be rated at least 300 V.

Do not apply power

1 2

3 4 5 6 7 8 9 10 11 12 13 14

Var Pwr Mix

Red Blk Blu Yel Brn/ Boil Com tN2 Mix Mix Com Out Slab Ret Sup

S1

S3

S2

15 16 17 18 19 20 Melt/Idle Demand

System Pmp 2

Boiler

Melting

Sys P1

Power L N

B1 S5 P2

P3

21 22 23 24 25

Date Code

Menu

Stop

H2029C

Start

not testing testing testing paused

P1

S4

L N

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

2 of 2

All specifications are subject to change without notice. Printed in Canada. C 667 - 01/11.