Submittal
C 667
Snow Detector & Melting Control 667
01/11 Snow Melting
Job ___________________________
Designer_ ______________________
Replaces: New
Contact_ _______________________
The Snow Detector & Melting Control 667 is designed to operate mechanical equipment to melt snow off an outdoor slab. It can be used in hydronic snow melting applications with one boiler with mixing. This product uses a tekmar snow/ice detection sensor in order to automatically melt snow while protecting the boiler and slab with mixing. It is capable of controlling 1 on/off boiler, a variable speed injection pump for mixing, a boiler pump, and a mix system pump.
Front View
Side View
Mounting Base
1/2” (13 mm) 7/8” (23 mm)
CL
Idle Demand
Melt Demand Idle Demand
Melt Demand
WWSD Minimum
Test
Maximum Water
off red red
Melting
Start Item
Made in Canada by tekmar Control Systems Ltd. 900-04
Snow Detector & Melting Control 667 Variable Speed Injection
C
uS
Meets Class B: Canadian ICES FCC Part 15 Power 115 V ±10% 50/60 Hz 600 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA Var. Pump 230 V (ac) 2.4 A (FLA), 5A (LRA) fuse T2.5 A 250 V Demand 20 to 260 V (ac) 2 VA
Date Code
Menu
not testing testing testing paused
For maximum heat, press and hold Test button for 3 seconds
Signal wiring must be rated at least 300 V.
Do not apply power
2
3 4 5 6 7 8 9 0 2 3 4
Var Pwr Mix
Red Blk Blu Yel Brn/ Boil Com tN2 Mix Mix Com Out Slab Ret Sup
5 6 7 8 9 20 Melt/Idle Demand
System Pmp 2
Boiler
2 22 23 24 25 Melting
Sys P1
Power L N
H2029C
6–5/8” (170 mm)
Stop
1/2” (14 mm) 1–7/8” (49 mm) 7–5/8” (193 mm)
2–7/8” (72 mm)
Ø 3/16” (5 mm)
1/2” Knock-out (x 5 back) (x 5 bottom)
Specifications------------------------------------------------------ Features--------------------------Snow Detector & Melting Control 667 Variable Speed Injection Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Relays Variable pump Demand Sensors –Included –Optional Warranty
D667, A667, U667, D001, D070 Microprocessor control. This is not a safety (limit) control 3.1 lb. (1400 g) 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Blue PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Noncondensing 115 V (ac) ±10%, 50/60 Hz, 600 VA 230 V (ac) 5 A, 1/3 hp 230 V (ac) 2.4 A (FLA), 5 A (LRA), fuse T2.5 A 250 V 20 to 260 V (ac) 2 VA NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 and 3 of Universal Sensor 082 tekmar Type #: 039, 040, 072, 073, 082, 090, 091, 094 Limited 3 Year (See D667 for full warranty)
• Automatic snow detection and melt control (090 Sensor) • Slab temperature control • Mixing Control (Variable Speed) • Temporary Idle • Slab protection for the snow melting system • Boiler control • Boiler Protection • Manual Override • Warm Weather Shut Down • Cold Weather Cut Out • Remote display and adjustment capabilities • Test sequence to ensure proper component operation • Equipment Exercising • CSA C US certified (approved to applicable UL standards)
Special requirements
090 Snow/Ice Sensor or Slab Sensor www.tekmarcontrols.com
of 2
© 2011
C 667 - 01/11
Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram
667 070 S5
S1
S2 P3
P1
S4
P2
B1 S3
Sample Electrical diagram Legend
Idle Demand
Melt Demand
B1 = On/Off Boiler P1 = Boiler Pump P2 = Mix System Pump P3 = Variable Speed Pump S1 = Boiler Sensor S2 = Mix Supply Sensor S3 = Mix Return Sensor S4 = Snow Sensor S5 = Outdoor Sensor
Idle Demand
Melt Demand
WWSD Minimum
Test
Maximum Water
off red red
Melting
For maximum heat, press and hold Test button for 3 seconds
Item
Made in Canada by tekmar Control Systems Ltd. 900-04 Power Relays Var. Pump
Snow Detector & Melting Control 667
C
Variable Speed Injection
US
Demand
Meets Class B: Canadian ICES FCC Part 15
115 V ±10% 50/60 Hz 600 VA 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA 230 V (ac) 2.4 A (FLA), 5A (LRA) fuse T2.5 A 250 V 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Do not apply power
1 2
3 4 5 6 7 8 9 10 11 12 13 14
Var Pwr Mix
Red Blk Blu Yel Brn/ Boil Com tN2 Mix Mix Com Out Slab Ret Sup
S1
S3
S2
15 16 17 18 19 20 Melt/Idle Demand
System Pmp 2
Boiler
Melting
Sys P1
Power L N
B1 S5 P2
P3
21 22 23 24 25
Date Code
Menu
Stop
H2029C
Start
not testing testing testing paused
P1
S4
L N
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
2 of 2