Submittal - Boston Heating Supply

Report 0 Downloads 201 Views
Submittal

C 360

Mixing Control 360

01/11 HVAC Systems Replaces: New

Job ___________________________

Designer_ ______________________

Contact_ _______________________

The Mixing Control 360 is designed to operate a mixing valve using Outdoor Temperature Reset. It can be used in applications ranging from in-floor radiant to commercial baseboard systems for boiler protection with full reset. This control regulates a single heating water temperature through Outdoor Temperature Reset. It controls the mixing by opening or closing a floating action type mixing valve actuator (3 or 4 way valves), and also provides control of the mix system pump.

Front View

Side View

Advanced

To increase or decrease the building temperature.

Open Close Mixing Demand

7/8” (23 mm)

CL

30% Enable Return

Installer

Supply 10% Enable

installer instructions

Display defaults back to VIEW menu after 20 sec.

Item

Test

ROOM - Set to desired room temp. OUTDR DSGN - Set to coldest (design) outdoor temp. Terminal Unit Set to High Mass Radiant  Low Mass Radiant 2 Fan Coil 3 Convector 4 Radiator 5 Baseboard 6 Refer to brochure for more information

Made in Canada by tekmar Control Systems Ltd.

Mixing Control 360 Floating Action

58033

Powered Output

 2 3 4 5 6 Mixing Demand

Power L N

Sys Pmp N

7 8 9 0  Boiler

R R Opn Cls

C

Power: 120 V ±10% 50/60 Hz 1300 VA Floating Output: 24 V (ac) 0.34 A 8 VA Relays: 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA Demand: 20 to 260 V (ac) 2 VA Do not apply power

2 3 4 5 6 7 8 UnO Com Boil Mix Com Out Indr Sw

Signal wiring must be rated at least 300 V. Use supply wires suitable for 120°F (50°C) above ambient

H1170C

6–5/8” (170 mm)

Motor Speed

1/2” (13 mm)

Boiler Sensor

• Press the Item, , buttons simultaneously for 1 sec. to enter the ADJUST menu • Use the, , buttons to adjust the ROOM setting

Terminal Unit

Mounting Base

1/2” (14 mm) 1–7/8” (49 mm) 7–5/8” (193 mm)

2–7/8” (72 mm)

Ø 3/16” (5 mm)

1/2” Knock-out (x 5 back) (x 5 bottom)

Specifications------------------------------------------------------ Energy Saving Features-----------Mixing Control 360 Floating Action Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Floating output Relays Demand Sensors –Included –Optional Warranty

D360, A360, D001, D070 Microprocessor control. This is not a safety (limit) control 3.1 lb. (1420 g) 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Blue PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Noncondensing 120 V (ac) ±10%, 50/60 Hz, 1300 VA 24 V (ac) 0.34 A 8 VA 240 V (ac) 10 A 1/3 hp 20 to 260 V (ac) 2 VA NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 and 2 of Universal Sensor 082 tekmar type #: 033, 076, 077, 084 Limited 3 Year (See D360 for full warranty)

• Outdoor Temperature Reset • Indoor Temperature Feedback (with optional indoor sensor) • Warm Weather Shut Down • Automatic Boiler Differential

Additional Features----------------

• Floating Action Mixing Control • Quick setup for easy installation and programming of control • User comfort adjustment to increase or decrease building space temperature • Advanced settings to fine-tune building requirements • Powered mixing system pump output • Optional indoor sensor for room air temperature control • Test sequence to ensure proper component operation • Setback input for energy savings • 120 V (ac) power supply • CSA C US certified (approved to applicable UL standards)

Special requirements N/A

www.tekmarcontrols.com

 of 2

© 2011

C 360 - 01/11

Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram

360

070 S3

S1

S2 M1 P1

B1

For zoning by tekmar visit www.tekmarcontrols.com

Sample Electrical diagram Legend B1 = Boiler 1 D1 = Mix Demand (From thermostat or end switch) S1 = Boiler Supply Sensor S2 = Mix Supply Sensor S3 = Outdoor Sensor P1 = Mix System pump M1 = Floating Action Actuator

Advanced

To increase or decrease the building temperature.

Boiler Sensor

• Press the Item, , buttons simultaneously for 1 sec. to enter the ADJUST menu • Use the, , buttons to adjust the ROOM setting

Terminal Unit

Motor Speed

Open Close Mixing Demand

30% Enable Return

Installer

Supply 10% Enable

Installer Instructions

Display defaults back to VIEW menu after 20 sec.

Item

Test

ROOM - Set to desired room temp. OUTDR DSGN - Set to coldest (design) outdoor temp. Terminal Unit Set to High Mass Radiant 1 Low Mass Radiant 2 Fan Coil 3 Convector 4 Radiator 5 Baseboard 6 Refer to brochure for more information

Made in Canada by tekmar Control Systems Ltd.

Floating Action

158033

Powered Output

1 2 3 4 5 6 Mixing Demand

Power L N

7 8 9 10 11 Boiler

Sys Pmp N

R R Opn Cls

Power: Floating Output: Relays: Demand:

120 V ±10% 50/60 Hz 1300 VA 24 V (ac) 0.34 A 8 VA 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA 20 to 260 V (ac) 2 VA

Do not apply power

12 13 14 15 16 17 18

C

UnO Com Boil Mix Com Out Indr Sw

Signal wiring must be rated at least 300 V. Use supply wires suitable for 120°F (50°C) above ambient

H1170C

Mixing Control 360

S3

D1 S1 S2

P1 C R

120 V (ac)

B1

C 1

Opn

2

Cls

3

M1

L N

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

2 of 2

All specifications are subject to change without notice. Printed in Canada. C 360 - 01/11.