C 406

Submittal tekmarNet®2 House Control 406

11/11 Alternative Energy

Job __________________________

Replaces: New

Contact _______________________

Designer ______________________

The tekmarNet ®2 House Control 406 is designed to operate the equipment in a 2-pipe, single tank, hydronic heating and cooling system. It operates two heat pump stages (water-to-water or air-to-water) with a backup heat source (boiler or electric resistance). The heat pump provides either hot or chilled water to a storage tank loop and optional mixed temperature loop. For radiant heating, the water temperature is calculated using outdoor temperature reset. For radiant cooling, the chilled water temperature is maintained at an adjustable setpoint, or is adjusted using dew-point reset with a humidity sensor. A backup boiler can provide an outdoor reset water temperature as well as domestic hot water and setpoint water temperatures. The 406 operates 4 on-board heating and cooling zones and is expandable up to 52 zones on the boiler, tank, and mix water temperatures.

Front View

Side View 1/2” Knock-out (x 4)

Back View

Control designed to mount on 4” x 4” electrical box (not included). For systems that require 2 power sources of 115 V (ac), a box extension ring is required to increase box fill capacity.

Item

DHW Call H8009B

7/8” (22 mm)

House Control 406 Zone 1 C Vlv

Zone 2 C Vlv

Zone 3 C Vlv

Rc2 Y2

Setpoint Call

Menu

Backup

Sensors - No Power

Tank Com Boil HPRt Com Out

5–1/2” (140 mm)

Mod dc/mA Boil / Mix Tank + tN4 C tN4 C

Mix/DHW tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O/B No Power Zone 1 Zone 2 Zone 3 Zone 4

Zone 4 Input Power C Vlv C R

CL 1–1/8” (30 mm) 5–1/2” (140 mm)

2–1/4” (57 mm) 4–1/2” (114 mm)

1/2” x 5/8” (12 mm x 16 mm) Knock-out (x 4)

Ø 1/8” (3 mm)

7/8” x 1/2” (23 mm x 12 mm) Knock-out (x 4)

--------Specifications --------------------------------------------------------------------------------------- Energy Saving Features ---tN2 House Control 406 Heat Pump & Backup, Four Zone Valves Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Control Load Zone, Y1 and O/B Relays Y2, Backup Relays Pump Relays Variable Power Pump Power Sensors –Included Warranty

D406, Q406 Microprocessor control. This is not a safety (limit) control 1.4 lb. (640 g) 5.5” H x 5.5” W x 2.25” D (140 x 140 x 57 mm) NEMA 1 rated, blue PC+ABS plastic CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 104°F (0 to 40°C), RH 90% Noncondensing 24 V (ac) ±10% 60 Hz, 100 VA max, Class 2

• • • • • • • • •

Outdoor Temperature Reset Indoor Temperature Feedback Warm Weather Shut Down Zone Synchronization Automatic differential for heat pump and boiler DHW Post Purge Intelligent heat/cool switchover System setback (with optional timer) One touch overrides (with optional User Switch)

2 VA

Additional Features ------------------

24 V (ac) 3.7 A combined

• • • • • • • • •

24 V (ac) 5 A 115 V (ac) 5 A 1/6 hp 115 V (ac) 2.4 A 115 V (ac) 12 A NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 and 4 of Universal Sensors 082 Limited 3 Year (See D406 for full warranty)

Expandable up to 52 zones Controls 2-stage heat pump Controls on/off or modulating boiler Electric resistance backup optional Variable speed mixing control DHW control with priority Equipment exercising Floor cooling capable Four 24 V (ac) powered zone valve outputs

SPECIAL REQUIREMENTS This control is designed to mount on a 4” x 4” electrical box, and must use tekmarNet ® thermostats to communicate heat demands. For floor cooling or hydronic cooling with a fan coil, use tekmarNet ® 2 thermostats 527, 528, 529, 530 or tekmarNet ® 4 thermostats 537, 538, and 540 with a date code of December 2011 or newer. www.tekmarcontrols.com

1 of 2

© 2011

C 406 - 11/11

Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram

S1

070

tekmarNet®2 Thermostats

406

S5

P6 S3

P7 Z1

S2

Z3

Z4

S4

P4

Modulating Condensing Boiler

Z2

P2

Water to Water Heat Pump

Expansion Tank

Sample Electrical diagram tekmarNet®2 Thermostats

Legend S5

Water to Water Heat Pump

S4

Menu

Item

DHW Call H8009B

House Control 406 Zone 1 C Vlv

Zone 2 C Vlv

Zone 3 C Vlv

Modulating Condensing Boiler

Rc2 Y2

Setpoint Call

S1

Backup

Sensors - No Power

S2

Mod dc/mA Boil / Mix Tank + tN4 C tN4 C

Mix/DHW tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O/B No Power Zone 1 Zone 2 Zone 3 Zone 4

S3

Tank Com Boil HPRt Com Out

P2 = Heat Pump Loop Pump P4 = Tank System Pump P6 = DHW Pump P7 = Transfer Pump Z1 = Zone 1 Z2 = Zone 2 Z3 = Zone 3 Z4 = Zone 4 S1 = Outdoor Sensor S2 = Heat Pump Return Sensor S3 = Boiler Sensor S4 = Tank Sensor S5 = DHW Sensor

Zone 4 Input Power C Vlv C R

R

L N

C

Z1

Z2

Z3

24 V (ac) Transformer 009

Z4

Back of House Control 406

P4

Tank Sys

(black) (black)

P2

HP Sys

(black) (red)

Tank Sys Pump Mix Sys Pump Boil Sys Pump

(black) (black)

DHW

P6

(black)

Transfer

P7

HP Loop Pmp Transfer Pump Pump Power (L)

L (blue)

DHW Pump

Pump Power (L)

(red)

L Variable Speed Pump

N

N to pump grounds

to pump grounds

L N G

G N

115 V (ac)

L

115 V (ac)

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

2 of 2

All specifications are subject to change without notice. Printed in Canada. C 406 - 11/11.