Surgelogic® Surge Protective Device I-Line® Plug-On Unit Series Class 1310 Catalog 1310CT0201R5/07

2007

CONTENTS Description Page Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Selection and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Surgelogic® Surge Protective Device Description

Description Surge protective device (SPD) units protect electronic equipment from transients. The I-Line® Plug-On Unit with Surgelogic® Transient Voltage Surge Suppressor (TVSS) is a modular parallel TVSS device designed for service entrance, distribution, or branch panel applications. The device is a multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm metal oxide varistors (MOVs). Each MOV is thermally protected for low current faults, and each module is fused. The I-Line plug-on unit with Surgelogic TVSS device is a high performance surge suppressor package incorporating individual modules for each phase. Modes of protection include:

• • • •

I-Line Plug-On Unit with Surgelogic TVSS

Line-to-Neutral (L–N) Line-to-Ground (L–G) Neutral-to-Ground (N–G) Line-to-Line (L–L)

A filter provides EMI/RFI noise filtering. The suppression elements are encapsulated in a UL® Recognized thermosetting epoxy material—another performance element that provides additional protection. Each surge suppression mode is individually fused and uses circuitry with thermal cutouts to isolate the TVSS and ensure shutdown in the event of MOV damage during severe overvoltages—even when operated on high fault current power systems. Online diagnostics continuously monitor the unit status, and LEDs signal a loss of a suppression circuit. An audible alarm with an enable/disable feature and dry contacts are included in the standard diagnostic package.

Design Features • • •

Same easy installation as I-Line circuit breaker



Can be applied in a six-disconnect panel or switchboard (TVSS counts as one disconnect)



High-energy parallel design for ANSI/IEEE C62.41 and C62.45 category B and C3 applications.

Requires 13.50 in. (343 mm) of mounting space FC units mount in the same mounting slots as FA circuit breakers. FI units mount in the same mounting slots as KA circuit breakers

2 © 2007 Schneider Electric All Rights Reserved

05/2007

Surgelogic® Surge Protective Device Application Information

Application Information The effects of lightning and the damage caused by lightning-generated transients are well known. The failure of electronic equipment in a facility located in a high lightning area can easily be attributed directly to lightning-generated transients. Transient protection can be installed on the power distribution system to protect this equipment from these externally generated transients. Lower magnitude transients generated within a facility and their effect on microprocessor-based equipment are less obvious than the transients induced by lightning. Transient voltage generated from inductive motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they can cause equipment to malfunction. A damaging transient voltage can enter a facility from several locations. The highest level of protection should be provided at the service entrance. A second level of protection should be provided at distribution points serving critical areas, for example, computer rooms, accounting areas, and laboratories. Other facility entry points that should be protected include panels serving outdoor lights, or outdoor equipment such as motors. Protection should also be provided for critical areas with equipment essential to the company. Square D® brand TVSS products offered by Schneider Electric provide protection at every level of the electrical distribution system. Typical applications include:

• Banking • Education • Government • Petrochemical • Military • Publishing

• Transportation • Wastewater/Sanitation • Medical • Financial • Telecommunications • Automated Manufacturing

• Retail • Utility • Insurance • Data Processing

3 05/2007

© 2007 Schneider Electric All Rights Reserved

Surgelogic® Surge Protective Device Selection and Specifications

Selection and Specifications Model Number Format The model number format consists of: Device Type, Voltage Code, TVSS Model, Surge Current Rating Code, and Option Code. The possible device types and codes are shown in the tables below.

FC 4 IMA 16 C

Option Code Surge Current Rating Code TVSS Model (IMA only) Voltage Code Device Type

In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac 3-phase, 4-wire, 160 kA surge capacity with surge counter.

Specifications Device Types, Interrupting Ratings, and Continuous Current Ratings Device Type

Interrupting Rating

Continuous Current Rating

@ 240 Vac

@ 480 Vac

@ 600Y/347 Vac

FC

100 kA

65 kA



60 A

FI

200 kA

200 kA

100 kA

60 A

Voltage Codes and Systems Voltage Code

Voltage System

1

120/240 Vac 1-phase, 3-wire

2

208Y/120 Vac 3-phase, 3-wire or 4-wire

3

240/120 Vac 3-phase, 4-wire (high leg Delta)

4

480Y/277 Vac, 3-phase, 3-wire or 4-wire

7

380Y/220 Vac, 3-phase, 3-wire or 4-wire

8

600Y/347 Vac, 3-phase, 3-wire or 4-wire

Surge Current Rating Codes and Surge Capacities Per Mode Surge Current Rating Code

Per Phase

12

120 kA

L–N

L–G

N–G

60 kA

60 kA

120 kA

16

160 kA

80 kA

80 kA

120 kA

24

240 kA

120 kA

120 kA

120 kA

Surge Suppressor Options, Descriptions, and Option Codes Option

Description

Option Code

Surge counter

Displays the combined total number of transient voltage surges detected from L–N, L–G, N–G, and L–L since the counter was last reset.

Remote monitor

Displays the alarm status of the surge protective device up to 1000 ft (305 m) away from the unit. This option uses the dry contacts.

Dry contacts

Provides available Form C type contacts.

Standard

Audible alarm with enable/disable switch

Provides audible indication that there is a loss of protection.

Standard

C Order catalog number TVS12RMU

4 © 2007 Schneider Electric All Rights Reserved

05/2007

Surgelogic® Surge Protective Device Selection and Specifications UL Suppression Voltage Ratings IMA Series Voltage Specifications Partial Catalog Number

Voltage Service

L–N

L–G

N–G

L–L

MCOV▲

FC1IMA FI1IMA

120/240 Vac, 1-phase, 3-wire

400

400

400

800

150

FC2IMA FI2IMA

208Y/120 Vac, 3-phase, 3-wire or 4-wire

400

400

400

800

150

400

1500/800

275/150

FC3IMA FI3IMA

Surgelogic® I-Line® Plug-on TVSS Unit

UL Suppression Voltage Rating (SVR)

240/120 Vac, 800/400 800/400

3-phase, 4-wire (high leg Delta)

FC4IMA FI4IMA

480Y/277 Vac,

FC7IMA FI7IMA FI8IMA ■

800

800

800

1600

320

380Y/220 Vac 3-phase, 3-wire or 4-wire

800

800

800

1600

320

600Y/347 Vac, 3-phase, 3-wire or 4-wire

1200

1200

1200

2000

420

3-phase, 3-wire or 4-wire

▲ MCOV = Maximum Continuous Operating Voltage ■ Not available as FC device

Standard Features and Descriptions Feature Environmental

Description Relative humidity: 0 to 95% non condensing Operating frequency: 47–63 Hz Surge suppression operating temperature: -40–+65 °C (-40–+149 °F) ✪ Storage temperature: -40–+65 °C (-40–+149 °F)

Compliance standards (TVSS unit only)

UL 1449, Second Edition, UL 1283 cULus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5 Meets 2002 NEC® Article 285.6

Fused suppression paths

Fused with individual surge-rated fuses (200 kAIR)

Thermal protection

Thermal cutout for low current faults On-line test functions

Diagnostics

Indication per phase Service indicator shown on the front panel of each TVSS unit

Replaceable modules

Separate, replaceable modules for each phase

LED indicators

Indication of loss of protection

Suppression modules

Individually-fused

Self-contained suppression circuits and filtering for each module

Solid state

Bi-directional

Front panel alarm

Includes an enable/disable switch

High-energy parallel design

Category A, B, and C3 applications

EMI/RFI Filtering

Up to -50 dB (100 kHz to 100 MHz)

Short-circuit current rating

200 kA (TVSS modules only)

Duty cycle tested ANSI C62.41 C3, 10 kA 20 kV

Minimum 5000 impulses

Warranty

Five years

✪ Surge counter liquid crystal display may not indicate at temperatures less than -20 °C (-4 °F)

5 05/2007

© 2007 Schneider Electric All Rights Reserved

Surgelogic® Surge Protective Device Replacement Parts

Replacement Parts MA Module Replacements Voltage System ●

120/240 Vac, 1-phase, 3-wire

208Y/120 Vac, 3-phase, 3 wire or 4-wire

240/120 Vac, 3-phase, 4-wire (high leg Delta) ▼

480Y/277 Vac, 3-phase, 3-wire or 4-wire

380Y/ 220 Vac, 3-phase, 3-wire or 4-wire

600Y/347 Vac, 3-Phase, 3-wire or 4-wire

Catalog Number

Peak Surge Current Rating

Phase A

Phase B

Phase C

120 kA

MA1IMA12

Empty

MA1IMA12

160 kA

MA1IMA16

Empty

MA1IMA16

240 kA

MA1IMA24

Empty

MA1IMA24

120 kA

MA1IMA12

MA1IMA12

MA1IMA12

160 kA

MA1IMA16

MA1IMA16

MA1IMA16

240 kA

MA1IMA24

MA1IMA24

MA1IMA24

120 kA

MA1IMA12

MA3IMA12

MA1IMA12

160 kA

MA1IMA16

MA3IMA16

MA1IMA16

240 kA

MA1IMA24

MA3IMA24

MA1IMA24

120 kA

MA4IMA12

MA4IMA12

MA4IMA12

160 kA

MA4IMA16

MA4IMA16

MA4IMA16

240 kA

MA4IMA24

MA4IMA24

MA4IMA24

120 kA

MA7IMA12

MA7IMA12

MA7IMA12

160 kA

MA7IMA16

MA7IMA16

MA7IMA16

240 kA

MA7IMA24

MA7IMA24

MA7IMA24

120 kA

MA8IMA12

MA8IMA12

MA8IMA12

160 kA

MA8IMA16

MA8IMA16

MA8IMA16

240 kA

MA8IMA24

MA8IMA24

MA8IMA24

● With all system voltages, TVSS devices must be grounded in accordance with all applicable standards. ▼ Phase B modules are different than Phase A and Phase C modules.

Surgelogic® Device Mounted in Panel with 4-Piece Trim Installed

6 © 2007 Schneider Electric All Rights Reserved

05/2007

Surgelogic® Surge Protective Device Dimensions and Weights

Dimensions and Weights

5.07 [129]

12.16 [309]

13.50 [345]

Weight: 18.90 lb (8.60 kg)

in. Dimensions: [mm]

FC I-Line® Plug-On Unit (Front View)

5.07 [129]

12.16 [309]

13.50 [345]

Weight: 23.30 lb (10.60 kg)

in. Dimensions: [mm]

FI I-Line Plug-On Unit (Front View)

7 05/2007

© 2007 Schneider Electric All Rights Reserved

Schneider Electric USA

Schneider Electric Canada

1601 Mercer Road Lexington, KY 40511 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com

19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario 1-800-565-6699 www.schneider-electric.ca

1310CT0201R5/07 © 2007 Schneider Electric All Rights Reserved Replaces 1310CT0201R3/03 April 2003. 05/2007