Surgelogic® Surge Protective Device I-Line® Plug-On Unit Series Class 1310 Catalog 1310CT0201R5/07
2007
CONTENTS Description Page Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Selection and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Surgelogic® Surge Protective Device Description
Description Surge protective device (SPD) units protect electronic equipment from transients. The I-Line® Plug-On Unit with Surgelogic® Transient Voltage Surge Suppressor (TVSS) is a modular parallel TVSS device designed for service entrance, distribution, or branch panel applications. The device is a multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm metal oxide varistors (MOVs). Each MOV is thermally protected for low current faults, and each module is fused. The I-Line plug-on unit with Surgelogic TVSS device is a high performance surge suppressor package incorporating individual modules for each phase. Modes of protection include:
• • • •
I-Line Plug-On Unit with Surgelogic TVSS
Line-to-Neutral (L–N) Line-to-Ground (L–G) Neutral-to-Ground (N–G) Line-to-Line (L–L)
A filter provides EMI/RFI noise filtering. The suppression elements are encapsulated in a UL® Recognized thermosetting epoxy material—another performance element that provides additional protection. Each surge suppression mode is individually fused and uses circuitry with thermal cutouts to isolate the TVSS and ensure shutdown in the event of MOV damage during severe overvoltages—even when operated on high fault current power systems. Online diagnostics continuously monitor the unit status, and LEDs signal a loss of a suppression circuit. An audible alarm with an enable/disable feature and dry contacts are included in the standard diagnostic package.
Design Features • • •
Same easy installation as I-Line circuit breaker
•
Can be applied in a six-disconnect panel or switchboard (TVSS counts as one disconnect)
•
High-energy parallel design for ANSI/IEEE C62.41 and C62.45 category B and C3 applications.
Requires 13.50 in. (343 mm) of mounting space FC units mount in the same mounting slots as FA circuit breakers. FI units mount in the same mounting slots as KA circuit breakers
2 © 2007 Schneider Electric All Rights Reserved
05/2007
Surgelogic® Surge Protective Device Application Information
Application Information The effects of lightning and the damage caused by lightning-generated transients are well known. The failure of electronic equipment in a facility located in a high lightning area can easily be attributed directly to lightning-generated transients. Transient protection can be installed on the power distribution system to protect this equipment from these externally generated transients. Lower magnitude transients generated within a facility and their effect on microprocessor-based equipment are less obvious than the transients induced by lightning. Transient voltage generated from inductive motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they can cause equipment to malfunction. A damaging transient voltage can enter a facility from several locations. The highest level of protection should be provided at the service entrance. A second level of protection should be provided at distribution points serving critical areas, for example, computer rooms, accounting areas, and laboratories. Other facility entry points that should be protected include panels serving outdoor lights, or outdoor equipment such as motors. Protection should also be provided for critical areas with equipment essential to the company. Square D® brand TVSS products offered by Schneider Electric provide protection at every level of the electrical distribution system. Typical applications include:
• Banking • Education • Government • Petrochemical • Military • Publishing
• Transportation • Wastewater/Sanitation • Medical • Financial • Telecommunications • Automated Manufacturing
• Retail • Utility • Insurance • Data Processing
3 05/2007
© 2007 Schneider Electric All Rights Reserved
Surgelogic® Surge Protective Device Selection and Specifications
Selection and Specifications Model Number Format The model number format consists of: Device Type, Voltage Code, TVSS Model, Surge Current Rating Code, and Option Code. The possible device types and codes are shown in the tables below.
FC 4 IMA 16 C
Option Code Surge Current Rating Code TVSS Model (IMA only) Voltage Code Device Type
In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac 3-phase, 4-wire, 160 kA surge capacity with surge counter.
Specifications Device Types, Interrupting Ratings, and Continuous Current Ratings Device Type
Interrupting Rating
Continuous Current Rating
@ 240 Vac
@ 480 Vac
@ 600Y/347 Vac
FC
100 kA
65 kA
—
60 A
FI
200 kA
200 kA
100 kA
60 A
Voltage Codes and Systems Voltage Code
Voltage System
1
120/240 Vac 1-phase, 3-wire
2
208Y/120 Vac 3-phase, 3-wire or 4-wire
3
240/120 Vac 3-phase, 4-wire (high leg Delta)
4
480Y/277 Vac, 3-phase, 3-wire or 4-wire
7
380Y/220 Vac, 3-phase, 3-wire or 4-wire
8
600Y/347 Vac, 3-phase, 3-wire or 4-wire
Surge Current Rating Codes and Surge Capacities Per Mode Surge Current Rating Code
Per Phase
12
120 kA
L–N
L–G
N–G
60 kA
60 kA
120 kA
16
160 kA
80 kA
80 kA
120 kA
24
240 kA
120 kA
120 kA
120 kA
Surge Suppressor Options, Descriptions, and Option Codes Option
Description
Option Code
Surge counter
Displays the combined total number of transient voltage surges detected from L–N, L–G, N–G, and L–L since the counter was last reset.
Remote monitor
Displays the alarm status of the surge protective device up to 1000 ft (305 m) away from the unit. This option uses the dry contacts.
Dry contacts
Provides available Form C type contacts.
Standard
Audible alarm with enable/disable switch
Provides audible indication that there is a loss of protection.
Standard
C Order catalog number TVS12RMU
4 © 2007 Schneider Electric All Rights Reserved
05/2007
Surgelogic® Surge Protective Device Selection and Specifications UL Suppression Voltage Ratings IMA Series Voltage Specifications Partial Catalog Number
Voltage Service
L–N
L–G
N–G
L–L
MCOV▲
FC1IMA FI1IMA
120/240 Vac, 1-phase, 3-wire
400
400
400
800
150
FC2IMA FI2IMA
208Y/120 Vac, 3-phase, 3-wire or 4-wire
400
400
400
800
150
400
1500/800
275/150
FC3IMA FI3IMA
Surgelogic® I-Line® Plug-on TVSS Unit
UL Suppression Voltage Rating (SVR)
240/120 Vac, 800/400 800/400
3-phase, 4-wire (high leg Delta)
FC4IMA FI4IMA
480Y/277 Vac,
FC7IMA FI7IMA FI8IMA ■
800
800
800
1600
320
380Y/220 Vac 3-phase, 3-wire or 4-wire
800
800
800
1600
320
600Y/347 Vac, 3-phase, 3-wire or 4-wire
1200
1200
1200
2000
420
3-phase, 3-wire or 4-wire
▲ MCOV = Maximum Continuous Operating Voltage ■ Not available as FC device
Standard Features and Descriptions Feature Environmental
Description Relative humidity: 0 to 95% non condensing Operating frequency: 47–63 Hz Surge suppression operating temperature: -40–+65 °C (-40–+149 °F) ✪ Storage temperature: -40–+65 °C (-40–+149 °F)
Compliance standards (TVSS unit only)
UL 1449, Second Edition, UL 1283 cULus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5 Meets 2002 NEC® Article 285.6
Fused suppression paths
Fused with individual surge-rated fuses (200 kAIR)
Thermal protection
Thermal cutout for low current faults On-line test functions
Diagnostics
Indication per phase Service indicator shown on the front panel of each TVSS unit
Replaceable modules
Separate, replaceable modules for each phase
LED indicators
Indication of loss of protection
Suppression modules
Individually-fused
Self-contained suppression circuits and filtering for each module
Solid state
Bi-directional
Front panel alarm
Includes an enable/disable switch
High-energy parallel design
Category A, B, and C3 applications
EMI/RFI Filtering
Up to -50 dB (100 kHz to 100 MHz)
Short-circuit current rating
200 kA (TVSS modules only)
Duty cycle tested ANSI C62.41 C3, 10 kA 20 kV
Minimum 5000 impulses
Warranty
Five years
✪ Surge counter liquid crystal display may not indicate at temperatures less than -20 °C (-4 °F)
5 05/2007
© 2007 Schneider Electric All Rights Reserved
Surgelogic® Surge Protective Device Replacement Parts
Replacement Parts MA Module Replacements Voltage System ●
120/240 Vac, 1-phase, 3-wire
208Y/120 Vac, 3-phase, 3 wire or 4-wire
240/120 Vac, 3-phase, 4-wire (high leg Delta) ▼
480Y/277 Vac, 3-phase, 3-wire or 4-wire
380Y/ 220 Vac, 3-phase, 3-wire or 4-wire
600Y/347 Vac, 3-Phase, 3-wire or 4-wire
Catalog Number
Peak Surge Current Rating
Phase A
Phase B
Phase C
120 kA
MA1IMA12
Empty
MA1IMA12
160 kA
MA1IMA16
Empty
MA1IMA16
240 kA
MA1IMA24
Empty
MA1IMA24
120 kA
MA1IMA12
MA1IMA12
MA1IMA12
160 kA
MA1IMA16
MA1IMA16
MA1IMA16
240 kA
MA1IMA24
MA1IMA24
MA1IMA24
120 kA
MA1IMA12
MA3IMA12
MA1IMA12
160 kA
MA1IMA16
MA3IMA16
MA1IMA16
240 kA
MA1IMA24
MA3IMA24
MA1IMA24
120 kA
MA4IMA12
MA4IMA12
MA4IMA12
160 kA
MA4IMA16
MA4IMA16
MA4IMA16
240 kA
MA4IMA24
MA4IMA24
MA4IMA24
120 kA
MA7IMA12
MA7IMA12
MA7IMA12
160 kA
MA7IMA16
MA7IMA16
MA7IMA16
240 kA
MA7IMA24
MA7IMA24
MA7IMA24
120 kA
MA8IMA12
MA8IMA12
MA8IMA12
160 kA
MA8IMA16
MA8IMA16
MA8IMA16
240 kA
MA8IMA24
MA8IMA24
MA8IMA24
● With all system voltages, TVSS devices must be grounded in accordance with all applicable standards. ▼ Phase B modules are different than Phase A and Phase C modules.
Surgelogic® Device Mounted in Panel with 4-Piece Trim Installed
6 © 2007 Schneider Electric All Rights Reserved
05/2007
Surgelogic® Surge Protective Device Dimensions and Weights
Dimensions and Weights
5.07 [129]
12.16 [309]
13.50 [345]
Weight: 18.90 lb (8.60 kg)
in. Dimensions: [mm]
FC I-Line® Plug-On Unit (Front View)
5.07 [129]
12.16 [309]
13.50 [345]
Weight: 23.30 lb (10.60 kg)
in. Dimensions: [mm]
FI I-Line Plug-On Unit (Front View)
7 05/2007
© 2007 Schneider Electric All Rights Reserved
Schneider Electric USA
Schneider Electric Canada
1601 Mercer Road Lexington, KY 40511 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com
19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario 1-800-565-6699 www.schneider-electric.ca
1310CT0201R5/07 © 2007 Schneider Electric All Rights Reserved Replaces 1310CT0201R3/03 April 2003. 05/2007