Installation Instructions TH/SLEEVE – P/R/S/T/M Series Wall Sleeves
TH/SLEEVE-T Shown With Attached Architectural Louver
TH/SLEEVE-T Shown THDC/THHP-TG Series Unit Installed
THDC / THHP Series Wall Sleeve Dimensions Model High Wide Deep P-Series 19.50 36.50 8.50 R-Series 23.50 30.50 8.50 S-Series 29.00 27.00 8.50 T-Series 32.50 24.50 8.50 M-Series 23.50 43.00 8.50 Thank you for selecting a TH/SLEEVE- P/R/S/T/M Series Wall Sleeve from AeroSys Inc. Please read the entire manual before assembling and installing the Wall Sleeve. With proper site preparation and assembly your wall sleeve installation will fit and function as designed. 929 Eldridge Drive, Hagerstown, Maryland 21740 Phone: 301-620-0002 Fax: 301-620-0685 www.aerosysinc.com Specifications are subject to change without notice
IMPORTANT SAFETY INSTRUCTIONS As a professional installer, you have the obligation to know the product better than the customer. This includes all safety precautions and related items. Prior to actual installation, thoroughly familiarize yourself with this Installation Manual. Pay special attention to all safety warnings. Remember, it is your responsibility to install the product safely. The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
WARNING Falling Objects This wall sleeve will be placed in an opening where it will need to protrude past the building structure. You as the installer must take every precaution necessary when installing the product to not allowing it go past the opening and drop from the structure / opening. When installing best practice is to make sure all areas below the installation area are clear of people and other items that may be damaged if the sleeve is accidently pushed past the structure / opening.
SHIPPING INSPECTION Upon receiving the product, inspect it for damage from shipment. Shipping damage and subsequent investigation is the responsibility of the carrier. Verify the model number, are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transport damage or installation of incorrectly shipped units.
CODES AND REGULATIONS This product is designed and manufactured to comply with national codes. Installation is accordance with such codes and /or prevailing local codes / regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations.
REPLACEMENT PARTS When reporting shortages or damage, or ordering repair parts, give the complete product model numbers as indicated on the product label. Replacement parts for this product are available through your contractor or local distributor.
PRE-INSTALLATION INSTRUCTIONS Carefully read all instructions for the installation prior to installing the product. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. Make sure everything needed to install the product is on hand before starting. Before attempting any installation, the following points should be considered: Structural strength of supporting members Clearances and provisions for servicing
SITE PREPARATION AND INSTALLATION
To insure a satisfactory air supply, locate condensing units in a clean area, away from loose dirt and foreign matter that may clog the coil. The condensing unit’s coil/blower side must not be located near any exhaust of steam, hot air, grease or corrosive fumes.
The condensing unit should be located at least 30 inches from a wall, adjacent unit or other obstruction that may restrict accessibility for maintenance. For multiple unit installations, space the units so that the hot exhaust air is not directed toward the air inlet of an adjacent unit.
Install on a solid base, capable of supporting the weight of the condensing unit. The base should be higher than the surrounding grade and larger than the dimensions of the condensing unit base.
The base of the unit is sloped to drain water away from the maintenance access side (inside face) of the equipment. When installing the unit(s), make sure to maintain the drainage angle toward the coil side of the condensing unit.
The wall sleeve should be installed to allow any condensation or rain water to drain from the bottom of the equipment. The unit will need to protrude past the wall a minimum of ½” for this to be achieved.
Condenser Air Ducting (if used)
The total external static pressure for any inlet and outlet ducting, including louvers, must not exceed 0.3 inches of water.
If the condensing unit draws ducted air from the outside of the building, rain hoods must be installed. In addition, install screens over the rain hood openings to eliminate the possibility of birds, water or debris entering the unit.
Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work areas. Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit to control vibration transmission to the building.
Locate the unit and ductwork so that the discharge air does not short circuit to the condenser air inlet. Avoid directing the hot exhaust air toward adjacent doors or windows.
TYPICAL THROUGH THE WALL INSTALLATION
Getting Started The AeroSys wall sleeve is shipped as 4 parts plus the hardware. Verify all parts and hardware before starting the assembly. Left Panel Right Panel Top Panel Bottom Panel 8 1/8” Rivets Architectural Louver (Optional Purchased Separate)
Wall Sleeve Assembly Step 1-1A Place the Left Side Panel on the outside of the Bottom Panel. Attach the Left Side Panel to the Bottom Panel using 2 1/8” rivets. Rivet from the outside of the wall sleeve. Step 2-2A Place the Left Side Panel on the outside of the Bottom Panel. Attach the Left Side Panel to the Bottom Panel using 2 1/8” rivets. Rivet from the outside of the wall sleeve. Step 3-3A Place the Top Panel on the Left and Right Side Panel so it overlaps both Panels. The Left Panel and Right Panel should be located inside the Top Panel. Rivet the Top Panel to the Left Side Panel using 2 1/8” rivets. Rivet from the outside of the wall sleeve. Step 4-4A Place the Top Panel on the Left and Right Side Panel so it overlaps Both Panels. The Left Panel and Right Panel should be located inside the Top Panel. Rivet the Top Panel to the Right Side Panel using 2 1/8” rivets. Rivet from the outside of the wall sleeve.
(Continue If Optional Architectural Louver Is Required) Step 5-5A For models S, M, &T attach the Architectural Louver to the front of the Wall Sleeve using the screws removed from the grille. Attach the louver with the flange facing the Wall Sleeve keeping the weep holes toward the bottom (5B) For the R & P models attach the Architectural Louver to the front of the unit and slide both through the Wall Sleeve. Attach the louver with the flange facing the Wall Sleeve using the screws removed from the grille. keeping the weep holes toward the bottom (5B). (CAUTION) If you use other hardware other than the provided hardware by the manufacture you run the risk of puncturing the condensing coil. AeroSys Inc. will not be responsible for damaged coils due to improper Installation .
R112912